Plan Review Details - Permit 06040227
Plan Review Stops For Permit 06040227
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-06-13 Cont ID  
Sent By amorse Date 2006-06-13 Time 09:10 Rev Time 1.50
Received By amorse Date 2006-06-13 Time 09:09 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-18 Cont ID  
Sent By amorse Date 2006-05-18 Time 10:20 Rev Time 4.00
Received By amorse Date 2006-05-18 Time 10:20 Sent To PC
Notes
2006-05-18 00:00:00 
  
 DENIED
  
 1) CONSTRUCTION DOCUMENTS SHALL INDICATE
 THE WIND DESIGN DATA AS REQUIRED IN
 1603.1.4 FBC INCLUDING EXTERIOR
 COMPONENT AND CLADDING PRESSURES FOR
 WINDOWS, DOORS, ROOFING, ETC. ALSO
 PROVIDE FLOOR AND ROOF LOADS
  
 2) DEMO NOTES ON PAGE D1 STATE ROOF TO
 REMAIN BUT S1 SHOWS NEW WOOD TRUSSES
 PLEASE CLARIFY
  
 3) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
  
 NOTE: PROVIDE PRODUCT APPROVALS FOR
 ROOFING TILES, FLAT ROOF AND WOOD
 CONNECTORS. FL APPROVAL SHEETS FROM
 SIMPSON WEB SITE IS ADEQUATE SEE
 ENCLOSED SAMPLE
  
 4) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 5) CBC LICENCE DOES NOT ALLOW CONTRACTOR
 TO ACT AS ROOFER OR INSTALL ROOFING
 OTHER THAN WOOD SHAKES/SHINGLES OR
 ASPHALT/FIBERGLASS SHINGLES ON A NEW
 BUILDING OF HIS/HER OWN CONSTRUCTION PER
 489.114 (3)(B),(G) FS
  
  
  
  
  
  
  
 6) PROVIDE DETAILS OF STRUCTURAL FRAMING
 AT DOOR AND WINDOW OPENINGS SHOWING WOOD
 CONNECTOR TYPES THAT WILL BE USED IN
 ORDER TO TRANSFER THE PRESSURES FROM NEW
 COMPONENTS TO THE STRUCTURE
  
 7) POWDER ROOM DR TO MEET ACCESSABILITY
 REQUIREMENTS PER R322.1.1 FBC
  
 8) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION
  
 9) ENERGY CALC'S SHOW R30 CEILING
 INSULATION, DETAIL 3 ON A4 HAS R19
 PLEASE CLARIFY
  
 10) ENERGY CALC'S NOT SIGNED AND DATED
 BY OWNER/AGENT
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004
 FBC* = WEST PALM BEACH
 ADMINISTATIVE AMMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-06-26 Cont ID  
Sent By btrobaug Date 2007-06-26 Time 08:35 Rev Time 0.00
Received By btrobaug Date 2007-06-26 Time 08:14 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-04-25 Cont ID  
Sent By btrobaug Date 2006-04-25 Time 18:09 Rev Time 0.50
Received By btrobaug Date 2006-04-25 Time 17:46 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-09-28 Cont ID  
Sent By adarroug Date 2007-09-28 Time 10:58 Rev Time 0.00
Received By adarroug Date 2007-09-28 Time 10:58 Sent To P
Notes
2007-09-28 10:58:39TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-06-24 Cont ID  
Sent By adarroug Date 2007-06-24 Time 14:37 Rev Time 0.00
Received By adarroug Date 2007-06-24 Time 14:37 Sent To E
Notes
2007-06-24 14:38:03TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-10-23 Cont ID  
Sent By adarroug Date 2006-10-23 Time 13:17 Rev Time 0.00
Received By adarroug Date 2006-10-23 Time 13:17 Sent To P
Notes
2006-10-23 13:17:52TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-08 Cont ID  
Sent By adarroug Date 2006-06-08 Time 17:29 Rev Time 0.00
Received By adarroug Date 2006-06-08 Time 17:29 Sent To B
Notes
2006-06-08 00:00:00TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-19 Cont ID  
Sent By adarroug Date 2006-04-19 Time 10:15 Rev Time 0.00
Received By adarroug Date 2006-04-19 Time 10:15 Sent To E
Notes
2006-04-19 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-05-18 Time   Rev Time 0.00
Received By adarroug Date 2006-04-10 Time 10:35 Sent To  
Notes
2006-04-10 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-04-26 Cont ID  
Sent By tgordon Date 2006-04-26 Time 08:58 Rev Time 0.25
Received By tgordon Date 2006-04-26 Time 08:58 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-10-11 Cont ID  
Sent By jleech Date 2007-10-11 Time 08:17 Rev Time 0.00
Received By jleech Date 2007-10-11 Time 08:17 Sent To  
Notes
2007-10-11 08:18:15AS BUILTS DRAWN BY PLUMBING CONTRACTOR.

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-11-17 Cont ID  
Sent By jleech Date 2006-11-17 Time 13:42 Rev Time 0.00
Received By jleech Date 2006-11-17 Time 13:42 Sent To  
Notes
2006-11-17 13:49:50DENIED;
 APPROVED PLANS WERE DRAWN BYTHE ARCHITECUTALGROUP
 AND THE ENGINEER FERM OF PUGA AND ASSOCIATES INC. DID
 THE MEP'S
 ANY CHANGES ON THESE PLANS MUST BE APPROVED BY ABOVE
 COMPANIES. SEALED SIGNED AND ON THEIR LETTER HEAD.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-04-29 Cont ID  
Sent By jleech Date 2006-04-29 Time 10:24 Rev Time 0.00
Received By jleech Date 2006-04-29 Time 10:24 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-04-18 Cont ID  
Sent By mmclean Date 2006-04-18 Time 14:37 Rev Time 0.00
Received By mmclean Date 2006-04-18 Time 14:37 Sent To I
Notes
2006-04-18 00:00:00PROVISO: MUST PROVIDE A SITEPLAN THAT
 TRULY REPRESENTS THE 2ND STORY PROPOSED
 FOR BALCONY & ROOF PROJECTION.