| 2006-09-08 00:00:00 | BUILDING REVISION CHECKLIST: |
| | 1- THIS IS NOT A REVISION. ORIGINAL |
| | PERMIT APPLICATION WAS FOR STUCCO |
| | REMOVAL ON THE 1ST TWO FLOORS. |
| | INFORMATION SUBMITTED NOW IS FOR NEW |
| | CONCRETE BLOCK WALL AND STRUCTURAL |
| | REPAIRS THROUGHOUT BUILDING. THEREFORE, |
| | NEED TO CLOSE THIS PERMIT BY CALLING FOR |
| | FINAL INSPECTION AND APPLY FOR A NEW |
| | PERMIT TO INCLUDE ALL PROPOSED WORK. |
| | |
| | 2- NEW PERMIT APPLICATION TO INCLUDE THE |
| | FOLLOWING INFORMATION TO ALLOW PLAN |
| | REVIEWER EXPEDITE REVIEW PROCESS: |
| | A) TOTAL PROJECT VALUATION, INCLUDING |
| | ENGINEER'S FEES. |
| | B) RECORDED NOTICE OF COMMENCEMENT. |
| | C) COMPLETE ENGINEERING DRAWINGS AND |
| | SPECIFICATIONS SHOWING ALL STRUCTURAL |
| | WORK IN DETAIL AND EXACT LOCATIONS. |
| | INFORMATION SUBMITTED DOESN'T SPECIFY IN |
| | DETAIL SCOPE OF WORK TO BE PERFORMED. |
| | D) MAKE SURE ENGINEERED DRAWINGS ARE |
| | CITING FBC 2004 AND UPDATED REFERENCE |
| | STANDARDS. SEE CHPATER 35 FBC 2004. |
| | E) NEW CONCRETE BLOCK WALL IN ROOF NEED |
| | TO PROVIDE DIMENSIONS (HEIGHT). |
| | F) NEW CONCRETE BLOCK WALL FOR ROOF |
| | WINDOW. THERE IS NOT INFORMATION GIVEN |
| | FOR THE WINDOW. NEED WINDOW PRODUCT |
| | APPROVAL, SIZE AND STRUCTURAL BUCK |
| | DETAILS. |
| | G) ENGINEER OF RECORD TO REVIEW ALL |
| | PRODUCT APPROVALS IN WRITTING AS |
| | REQUIRED BY SEC. 106.3.3 OF CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |