Plan Review Details - Permit 06040152
Plan Review Stops For Permit 06040152
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-03 Cont ID  
Sent By amorse Date 2006-05-03 Time 10:14 Rev Time 1.00
Received By amorse Date 2006-05-03 Time 10:14 Sent To FIRE
Notes
2006-05-03 00:00:00 
  
 DENIED
  
 1) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
  
 2) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 3) A DESIGN PROFESSIONAL THAT IS
 REGISTERED TO PRACTICE UNDER CHAPTER 481
 OR 471 OF THE FLORIDA STATUTES SHALL
 AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND
 DATE TO SAID DRAWINGS AND SPECIFICATIONS
 PER 106 FBC 2004
  
 4) PROVIDE LAYOUT OF BUILDING WITH
 CONSTRUCTION TYPE, OCCUPANCY
 CLASSIFICATION, OCCUPANT LOAD,ETC.
  
 5) PROVIDE SURVEY/SITE PLAN THAT SHOWS
 PROPERTY LINES
  
 6) STAIR WIDTH SHALL BE 44" PER 1009.1
 FBC UNLESS NOTE #4 REQUIREMENTALLOW
 FOREXCEPTIONS
  
 7) PROVIDE STAIR DETAILS SHOW COMPLIANCE
 WITH 1009.3 FOR TREAD WIDTH, (MIN 11")
 AND 1009.3.2, (SOLID RISERS) OF FBC
  
 8) PROVIDE DETAILS FOR HANDRAILS TO SHOW
 COMPLIANCE WITH 1009.11.1, (34"-38" HT.)
 1009.11.5, (CONTINUITY) AND 1012.3,
 (OPENING LIMITATIONS) OF FBC
  
 9) STAIRS SHALL HAVE HANDRAILS ON BOTH
 SIDES PER 1009.11 FBC
  
 10) EXIT DOORS SHALL BE MARKED WITH AN
 APPROVED SIGN THAT COMPLIES WITH 1006.3
 FBC
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-03 Cont ID  
Sent By dpalmer Date 2006-05-03 Time 13:02 Rev Time 0.00
Received By dpalmer Date 2006-05-03 Time 12:36 Sent To FIRE
Notes
2006-05-03 00:00:00************** UNSAT *************
  
 1) NOTE: PLEASE SEE FS 481.221 WHICH
 REQUIRESTHE SIGNATURE , DATE AND SEAL
 OF SAID ARCHITECT ON TITLE BLOCKS .
  
 2) NOTE: PLEASE PROVIDE MEANS OF EGRESS
 LIGHTING TO THE PUBLIC RIGHT OF WAY.
 PLEASE KNOW, A BATTERY BACK UP FIXTURE
 OF SOME SORT FOR STAIRS IS ALSO
 REQUIRED.
 PLEASE SEE THAT 10 FT CANDLES MININUM IS
 REQUIRED UNDER NORMAL POWER AND 1 FT
 CANDLE MINUNDER EM POWER CONDITIONS.
 PLEASE SEE 2003 NFPA-101 7.8.1.3,7.9.2.2
  
 3)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 ALSO WITH RESPECT TO ANY NEW OR EXISTING
 EXT LT FROM EXISTING EXT IN BUILDING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-05-04 Cont ID  
Sent By nmccray Date 2006-05-04 Time 15:46 Rev Time 0.00
Received By nmccray Date 2006-05-04 Time 15:46 Sent To  
Notes
2006-05-04 00:00:00**********DENIED*********************
  
 1) NEW STAIRS MUST COMPLY WITH NFPA 101
 TABLE 7.2.2.1 (A) MINIMUM WIDTH (44") OR
 (36") WHERE TOTAL OCCUPANT LOAD OF ALL
 STORIES SERVED BY STAIRWAYS IS FEWER
 THAN 50.
  
 2) EGRESS DOORS SHALL COMPLY WITH NFPA
 101 CHAPTER 7.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-14 Cont ID  
Sent By adarroug Date 2006-04-14 Time 10:31 Rev Time 0.00
Received By adarroug Date 2006-04-14 Time 10:31 Sent To B
Notes
2006-04-14 00:00:00TO "MISC" BOX#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2006-04-06 Time 11:49 Sent To  
Notes
2006-04-06 00:00:00TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status F Date 2006-04-13 Cont ID  
Sent By mmclean Date 2006-04-13 Time 09:40 Rev Time 0.00
Received By mmclean Date 2006-04-13 Time 09:40 Sent To HIST
Notes
2006-04-13 00:00:00DENIED,
 1. MUST PROVIDE TWO COPY OF
 SURVEY/SITEPLAN SHOWING THE LOCATION THE
 PROPOSED STARWAY AND SETBACKS FROM
 PROPERTY LINE.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720