| 2006-05-03 00:00:00 | |
| | |
| | DENIED |
| | |
| | 1) THE PERMIT APPLICATION SHALL INCLUDE |
| | TWO COPIES OF EACH PRODUCT APPROVAL THAT |
| | IS RELEVANT PER 9B-72. THESE SHOULD |
| | INCLUDE THE FLORIDA STATE APPROVAL COVER |
| | PAGES, AND THE PRODUCT NOA THAT LISTS |
| | THE SYSTEM COMPONENTS/ FASTENER LIST |
| | PAGES, THE PAGES WITH THE CHOSEN |
| | ASSEMBLY/ SYSTEM TO BE USED AND THE |
| | GENERAL LIMITATIONS PAGE. ALL CAN BE |
| | FOUND ON WWW.FLORIDABUILDING.ORG |
| | |
| | 2) THOSE PRODUCTS WHICH ARE REGULATED BY |
| | DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | |
| | 3) A DESIGN PROFESSIONAL THAT IS |
| | REGISTERED TO PRACTICE UNDER CHAPTER 481 |
| | OR 471 OF THE FLORIDA STATUTES SHALL |
| | AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND |
| | DATE TO SAID DRAWINGS AND SPECIFICATIONS |
| | PER 106 FBC 2004 |
| | |
| | 4) PROVIDE LAYOUT OF BUILDING WITH |
| | CONSTRUCTION TYPE, OCCUPANCY |
| | CLASSIFICATION, OCCUPANT LOAD,ETC. |
| | |
| | 5) PROVIDE SURVEY/SITE PLAN THAT SHOWS |
| | PROPERTY LINES |
| | |
| | 6) STAIR WIDTH SHALL BE 44" PER 1009.1 |
| | FBC UNLESS NOTE #4 REQUIREMENTALLOW |
| | FOREXCEPTIONS |
| | |
| | 7) PROVIDE STAIR DETAILS SHOW COMPLIANCE |
| | WITH 1009.3 FOR TREAD WIDTH, (MIN 11") |
| | AND 1009.3.2, (SOLID RISERS) OF FBC |
| | |
| | 8) PROVIDE DETAILS FOR HANDRAILS TO SHOW |
| | COMPLIANCE WITH 1009.11.1, (34"-38" HT.) |
| | 1009.11.5, (CONTINUITY) AND 1012.3, |
| | (OPENING LIMITATIONS) OF FBC |
| | |
| | 9) STAIRS SHALL HAVE HANDRAILS ON BOTH |
| | SIDES PER 1009.11 FBC |
| | |
| | 10) EXIT DOORS SHALL BE MARKED WITH AN |
| | APPROVED SIGN THAT COMPLIES WITH 1006.3 |
| | FBC |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |