Plan Review Details - Permit 06040145
Plan Review Stops For Permit 06040145
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-08-11 Cont ID  
Sent By mjacobs Date 2006-08-11 Time 11:23 Rev Time 0.00
Received By mjacobs Date 2006-08-11 Time 08:22 Sent To PC
Notes
2006-08-11 00:00:00 
  
  
 1) OK.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. THESE
 INCLUDE ALL ROOFING
 MATERIALS/GLASS BLOCK AND
 CONNECTORS.
  
 5) OK.
  
 6) TRUSS DESIGN
 R802.10.1 TRUSS DESIGN DRAWINGS.
 TRUSS DESIGN DRAWINGS, PREPARED IN
 CONFORMANCE WITH SECTION R802.10.1 ,
 SHALL BE PROVIDED TO THE BUILDING
 OFFICIAL AND APPROVED PRIOR TO
 INSTALLATION. TRUSS DESIGN DRAWINGS
 SHALL INCLUDE, AT A MINIMUM, THE
 INFORMATION SPECIFIED BELOW. TRUSS
 DESIGN DRAWING SHALL BE PROVIDED WITH
 THE SHIPMENT OF TRUSSES DELIVERED TO THE
 JOBSITE.
  
 7) R802.10.2 DESIGN .
 WOOD TRUSSES SHALL BE DESIGNED IN
 ACCORDANCE WITH ACCEPTED ENGINEERING
 PRACTICE. THE DESIGN AND MANUFACTURE OF
 METAL PLATE CONNECTED WOOD TRUSSES SHALL
 COMPLY WITH ANSI/TPI 1. THE TRUSS DESIGN
 DRAWINGS SHALL BE PREPARED BY A
 REGISTERED PROFESSIONAL WHERE REQUIRED
 BY THE STATUTES OF THE JURISDICTION IN
 WHICH THE PROJECT IS TO BE CONSTRUCTED
 IN ACCORDANCE WITH SECTION R106.1.
  
 8) R1305.1.3 AND 1305.1.3.2. SHOW IN
 DETAIL HOW THE AIR/HU WILL
 WILL BE INSTALLED IN THE ATTIC.
  
 9) OK.
  
 10) OK.
  
 11) NOTE: ALL MATERIALS AROUND MOISTURE
 AREAS SHALL BE MOISTURE RETARDANT.
 SEE. R319 AND R320 FOR MORE INFORMATION
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-05 Cont ID  
Sent By mjacobs Date 2006-07-05 Time 09:55 Rev Time 0.00
Received By mjacobs Date 2006-07-05 Time 06:16 Sent To PC
Notes
2006-07-05 00:00:00 
  
 ** PREVIIOUS COMMENTS WERE NOT
 ADDRESSED.SEE NOTES IN PACKAGE.
 ADDITIONAL FEES ARE DUE $568.91
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-23 Cont ID  
Sent By mjacobs Date 2006-05-23 Time 16:31 Rev Time 0.00
Received By mjacobs Date 2006-05-19 Time 13:02 Sent To PC
Notes
2006-05-22 00:00:00 
 1) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 FEFFERENCE IS ICC (BVD), MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES. WPB
 AMENDMENTS 108.3
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. THESE
 INCLUDE WINDOWS/DOORS/ALL ROOFING
 MATERIALS/GLASS BLOCK AND
 CONNECTORS.VENTILATION
  
 5) R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER
 SPACES FORMED WHERE CEILINGS ARE APPLIED
 DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR
 EACH SEPARATE SPACE BY VENTILATING
 OPENINGS PROTECTED AGAINST THE ENTRANCE
 OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE
 MESH, WIT H 1 / 8 INCH (3.2 MM) MINIMUM
 TO 1/4 INCH (6.4 MM) MAXIMUM OPENINGS.
  
 6) TRUSS DESIGN
 R802.10.1 TRUSS DESIGN DRAWINGS.
 TRUSS DESIGN DRAWINGS, PREPARED IN
 CONFORMANCE WITH SECTION R802.10.1 ,
 SHALL BE PROVIDED TO THE BUILDING
 OFFICIAL AND APPROVED PRIOR TO
 INSTALLATION. TRUSS DESIGN DRAWINGS
 SHALL INCLUDE, AT A MINIMUM, THE
 INFORMATION SPECIFIED BELOW. TRUSS
 DESIGN DRAWING SHALL BE PROVIDED WITH
 THE SHIPMENT OF TRUSSES DELIVERED TO THE
 JOBSITE.
  
 7) R802.10.2 DESIGN .
 WOOD TRUSSES SHALL BE DESIGNED IN
 ACCORDANCE WITH ACCEPTED ENGINEERING
 PRACTICE. THE DESIGN AND MANUFACTURE OF
 METAL PLATE CONNECTED WOOD TRUSSES SHALL
 COMPLY WITH ANSI/TPI 1. THE TRUSS DESIGN
 DRAWINGS SHALL BE PREPARED BY A
 REGISTERED PROFESSIONAL WHERE REQUIRED
 BY THE STATUTES OF THE JURISDICTION IN
 WHICH THE PROJECT IS TO BE CONSTRUCTED
 IN ACCORDANCE WITH SECTION R106.1.
  
 8) SHOW IN DETAIL HOW THE AIR/HU WILL
 WILL BE INSTALLED IN THE ATTIC.
  
 9) R613.6.2 MASONRY, CONCRETE OR OTHER
 STRUCTURAL SUBSTRATE. WHERE THE WOOD
 SHIM OR BUCK THICKNESS IS LESS THAN 1?
 INCHES (38 MM), WINDOW AND DOOR
 ASSEMBLIES SHALL BE ANCHORED THROUGH THE
 MAIN FRAME OR BY JAMB CLIP OR SUBFRAME
 SYSTEM, IN ACCORDANCE WITH
 THE MANUFACTURERS PUBLISHED INSTALLATION
 INSTRUCTIONS. ANCHORS SHALL BE SECURELY
 FASTENED DIRECTLY INTO THE MASONRY,
 CONCRETE OR OTHER STRUCTURAL SUBSTRATE
 MATERIAL. UNLESS OTHERWISE TESTED, BUCKS
 SHALL EXTEND BEYOND THE INTERIOR FACE OF
 THE WINDOW OR DOOR FRAME SUCH THAT FULL
 SUPPORT OF THE FRAME IS PROVIDED.
  
 10) 1506.3 VENTILATION RATE.
 VENTILATION SYSTEMS SHALL BE DESIGNED TO
 HAVE THE CAPACITY TO EXHAUST THE MINIMUM
 AIR FLOW RATE DETERMINED IN ACCORDANCE
 WITH TABLE M1506.3 .
  
 11) NOTE: ALL MATERIALS AROUND MOISTURE
 AREAS SHALL BE MOISTURE RETARDANT.
 SEE. R319 AND R320 FOR MORE INFORMATION
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-08-06 Cont ID  
Sent By dpalmer Date 2006-08-06 Time 12:01 Rev Time 0.00
Received By dpalmer Date 2006-08-06 Time 11:20 Sent To M
Notes
2006-08-06 00:00:00****** UNSAT 3RD REVIEW ********
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED ALONG
 WITH NEW COMMENTS AS PLANS DO NOT MEET
 CODE COMPLAINCE.
  
  
 1) NOTE: **IMPORTANT**
 PLEASE REMOVE ALL
 OLD/VOIDED SHEETS FROM EXISTING SETS AND
 INSERT ONLY NEW REVISED SHEETS INTO "TWO
 COMPLETE SETS" FOR REVIEW AND STAMPING.
 PLEASE SEE SEPARATE SHEETS ARE IN
 MULTIPLE LOCATIONS ON PACKAGE SUBMITTED.
 SETS SHALL BE MADE UP INTO SETS BY THE
 RESPONSIBLE PARTY TO AVOID DELAYS AND
 EXPEDITE THE REVIEW PROCESS.
 106.1 ADMIN SECT FBC
  
 2) NOTE: NO, PLEASE SEE THIS IS STILL
 NOT DONE. PLEASE SEE MECHANICAL PLANS
 WHICH SHOW DIFFERENT SIZE AHU/HEAT ETC.
 PLEASE ALSO SEE ONLY ONE SET CONTAINS A
 "M" SHEETS. SEE MECH REVIEW NOTES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRLEATE MECHANICAL
 PLANS WITH ELECTRICAL PLANS AS THERE ARE
 MORE THAN ONE HEAT KW SIZE SHOWN. PLEASE
 ALSO SEE MULTIPLE SETS OF "M" SHEETS AE
 SUBMITTED AND SEEING THAT NOW REVISIONS
 ARE SHOWN WITH CLOUDS/TRIANGLESS OR
 REVISED DATES, IT IS UNCLEAR WHICH "M"
 SHEETS APPLY. PLEASE SEE BOTH CONTAIN A
 DATE OF MARCH 13??????
 215.5, 106.1.2
  
 3) NOTE: NO, SAME COMMENT NOT ADDRESSED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 424.3B FOR MIN OCP
 TO BE SIZED FOR AHU. (125% MIN). PLEASE
 ALSO ADJUST CONDUCTOR SIZES PER 310.16.
 FOR BOTH AHU'S.
  
 4) NOTE:NO, NOT DONE, AS REQUESTED
 SHOW ALL MEETING CURRENT CODE OR NEW
 WHICH WILL MEET CURRENT CODE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOW THE ENTIRE EXISTING
 DWELLING AS SD'S ARE REQUIRED IN ALL
 EXISTING BEDRMS INSIDE AND OUTSIDE ROOMS
 AND ONLY PART OF THE EXISTING DWELLING
 IS SHOWN.
 PLEASE KNOW, ALL NEW SD'S ARE REQUIRD TO
 BE INSTALLED PER CURRENT NFPA-72
 11.5.1.1,11.8.3.
 R313, 2004 FBC.
  
 5) NOTE: NO, SAME WALL REDLINED ON
 PREVIOUS PLANS STILL DOES NOT CONTAIN
 ELECTRICAL RECEPT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING RECEPT(S) PER
 210.52.
  
 6) NOTE: NO, PLEASE SEE DISCONNECT IS
 STILL NOT SHOWN . NOTE MENTIONS THIS IS
 "CEILING HUNG" THIS WOULD PALCE UNIT IN
 THE ROOM?
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING DISCONNECT
 FOR AHU IN ATTIC. 440.11.
  
 7) NOTE:NO, DSAME COMMENT. PLEASE SEE
 THIS WAS NOTED ON THE FIRST REVIEW TO
 CORRELATE ALL LOADS, AND ITEMS ON PANEL
 SCHEDULES. THIS IS STILL NOT DONE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THERE ARE NUMEROUS
 ITEMS ON PANEL SCHEDULE AND THE LOAD
 CALCULATIONS WHICH DO NOT CORRELATE.
 PLEASE SEE MANY ITEMS WHICH ARE SHOWN IN
 LOAD CALCULATIONS, ARE NOT ON PANEL
 SCHEDULE.IE: RANGE, COOKTOP, WHIRLPOOL,
 WATER HEATER, ETC ETC ETC
 215.5, 106.1.2, 408.4, 220.31B
  
 8) NOTE: OK.
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
 11) NOTE: NO, SAME NOTE: STILL SHOWS #8
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE ONE OF THE NEW BATH
 CIRCUITS WITH #8 AWG??
 210.11C3 (20A #12).
  
 12) NOTE: NO.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 220.31B FOR LOAD
 CALCULATIONS AND REQUIRED METHOD TO BE
 SHOWN.
 215.5,106.1.2
  
 13) NOTE:PLEASE A 4X FEE FOR PLAN
 REVIEW HAS NOW BEEN ASSESSED TO THE
 DEISGN PROFESSIONAL. PLEASE ALSO KNOW,
 AS PLANS FOR THIS PROJECT AND OTHER
 PROJECTS HAVE BEEN RETIANED BY THIS
 OFFICE FOR REPEAT CODE COMPLIANT
 COMMENTS THESE SHALL BE FORWARDED TO THE
 STATE OF FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS AND THE STATE'S LEGAL COUNSEL
 TO THE BOARD.
 PLEASE KNOW THE FEE OF $1,539.93 IS NOW
 DUE FROM THE DESIGN PROFESSIONAL BEFORE
 PLANS CAN BE RESUBMITTED.
 ** THIS IS NOT THE RESPONSIBLITY OF THE
 OWNER OR CONTRACTOR.
 A 3RD REVIEWED SET IS ALSO NOW RETAINED
 AND WILL BE PLACED WITH OTHER PLANS.
  
 ** PLEASE SEE FS 471.025(3) WHICH
 STATE'S:
 "NO LICENSEE SHALL AFFIX OR PERMIT TO BE
 AFFIXED HIS OR HER SEAL, NAME, OR
 DIGITAL SIGNATURE TO ANY PLAN,
 SPECIFICATION, DRAWING, FINAL BID
 DOCUMENT, OR OTHER DOCUMENT THAT DEPICTS
 WORK WHICH HE OR SHE IS NOT LICENSED TO
 PERFORM OR WHICH IS BEYOND HIS OR HER
 PROFESSION OR SPECIALTY THEREIN."
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FS 553.80(2)(B)
 WITH RESPECT TO REPEAT COMMENTS.
 PLEASE KNOW, THIS IS ONLY NOTICE GIVEN
 AT THIS TIME.
 ** PLEASE KNOW, TWO "E" SHEETS ARE BEING
 RETAINED FOR FILE.
  
 ** NEW NOTE **
  
 14) NOTE: PLEASE SEE PREVIOUS LOAD CALCS
 CONTIANED A GARAGE DOOR OPENER.? IF THIS
 LOAD IS AT LOCATION OF DWELLING, THEN
 THIS SHOULD BE INCLUDED ON PANEL
 SCHEDULE AND LOAD CALCS.
 220
  
 15) NOTE: PLEASE SEE PLANS CONTAIN A
 MAIN DISCONNECT OUTSIDE AND ONLY A PANEL
 IS BEING SHOWN ON RISER.
 PLEASE CORRELATE. IF THERE IS NOW A NEW
 MAIN DISCONNECT, PLEASE INLCUDE ITS AIC
 RATING, CONDUCTORS, SIZE ETC.
 UNABLE TO VERIFY AT THIS TIME.
 240.4,310.16,,250.24B,250.122, 215.5
 ETC
  
  
 ** PLEASE KNOW, THE NOTES ABOVE HAVE NO
 WAY SPECIFICALLY NOTED EVERY ITEM NOT
 CORRECT, HOWEVER ALL CODES HAVE BEEN
 GIVEN FOR ITEMS WHICH ARE NOT CORRECT ON
 PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-07-28 Cont ID  
Sent By dpalmer Date 2006-07-28 Time 14:26 Rev Time 0.00
Received By dpalmer Date 2006-07-28 Time 14:03 Sent To PC
Notes
2006-07-28 00:00:00*** CALLED OWNER AND LEFT MESSAGE AS
 PREVIOUS NOTES REQUESTED PLANS TO BE
 PLACED INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. SHEETS ARE IN DISARRAY AND
 NEED TO BE TAKEN OUT AND DONE AS NOTED
 ABOVE.
 NO REVIEW DONE AND PLANS MAY COME BACK
 IN WITH A RESUB FEE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-27 Cont ID  
Sent By dpalmer Date 2006-06-27 Time 17:39 Rev Time 0.00
Received By dpalmer Date 2006-06-27 Time 16:26 Sent To M
Notes
2006-06-27 00:00:00****** UNSAT 2ND REVIEW ********
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED ALONG
 WITH NEW COMMENTS AS PLANS DO NOT MEET
 CODE COMPLAINCE.
  
  
 1) NOTE: **IMPORTANT** PLEASE REMOVE ALL
 OLD/VOIDED SHEETS FROM EXISTING SETS AND
 INSERT ONLY NEW REVISED SHEETS INTO "TWO
 COMPLETE SETS" FOR REVIEW AND STAMPING.
 PLEASE SEE SEPARATE SHEETS ARE IN
 MULTIPLE LOCATIONS ON PACKAGE SUBMITTED.
 SETS SHALL BE MADE UP INTO SETS BY THE
 RESPONSIBLE PARTY TO AVOID DELAYS AND
 EXPEDITE THE REVIEW PROCESS.
 106.1 ADMIN SECT FBC
  
 2) NOTE: PLEASE CORRLEATE MECHANICAL
 PLANS WITH ELECTRICAL PLANS AS THERE ARE
 MORE THAN ONE HEAT KW SIZE SHOWN. PLEASE
 ALSO SEE MULTIPLE SETS OF "M" SHEETS AE
 SUBMITTED AND SEEING THAT NOW REVISIONS
 ARE SHOWN WITH CLOUDS/TRIANGLESS OR
 REVISED DATES, IT IS UNCLEAR WHICH "M"
 SHEETS APPLY. PLEASE SEE BOTH CONTAIN A
 DATE OF MARCH 13??????
 215.5, 106.1.2
  
 3) NOTE: PLEASE SEE 424.3B FOR MIN OCP
 TO BE SIZED FOR AHU. (125% MIN). PLEASE
 ALSO ADJUST CONDUCTOR SIZES PER 310.16.
 FOR BOTH AHU'S.
  
 4) NOTE: PLEASE SHOW THE ENTIRE EXISTING
 DWELLING AS SD'S ARE REQUIRED IN ALL
 EXISTING BEDRMS INSIDE AND OUTSIDE ROOMS
 AND ONLY PART OF THE EXISTING DWELLING
 IS SHOWN.
 PLEASE KNOW, ALL NEW SD'S ARE REQUIRD TO
 BE INSTALLED PER CURRENT NFPA-72
 11.5.1.1,11.8.3.
 R313, 2004 FBC.
  
 5) NOTE: PLEASE SEE MISSING RECEPT PER
 210.52.
  
 6) NOTE: PLEASE SEE MISSING DISCONNECT
 FOR AHU IN ATTCI. 440.11.
  
 7) NOTE: PLEASE SEE THERE ARE NUMEROUS
 ITEMS ON PANEL SCHEDULE AND THE LOAD
 CALCULATIONS WHICH DO NOT CORRELATE.
 PLEASE SEE MANY ITEMS WHICH ARE SHOWN IN
 LOAD CALCULATIONS, ARE NOT ON PANEL
 SCHEDULE.IE: RANGE, COOKTOP, WHIRLPOOL,
 WATER HEATER, ETC ETC ETC
 215.5, 106.1.2, 408.4, 220.31B
  
 8) NOTE: PLEASE SEE MANY ITEMS LISTED IN
 LOAD CALCS ARE MENTIONED IN"PLURAL"??
 PLEASE VERIFY AS SOME ARE ONLY SHOWN AS
 ONE/SINGULAR ON PANEL SCHEDULE.
 IE: WASHERS, WATER HEATERS,DISHAWSHERS,
 ETC ETC
 215.5,106.1.2, 408.4
  
 9) NOTE: PLEASE SEE 310.16, 240.4 FOR
 MIN OCP AND AWG REQUIRED FOR DRYER.
 215.5, 106.1.2
  
 10) NOTE: PLEASE SEE 20A LIGHTING
 CIRCUIT BEING SHOWN IN LOAD CALCS WHICH
 INDICATE 3KW LOAD????
 PLEASE SEE MAX KVA ON THE 20A CIR IS
 1920VA.
 240.4, ETC
  
 11) NOTE: PLEASE SEE ONE OF THE NEW BATH
 CIRCUITS WITH #8 AWG??
 210.11C3 (20A #12).
  
 12) NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCULATIONS AND REQUIRED METHOD TO BE
 SHOWN.
 215.5,106.1.2
  
 13) NOTE: PLEASE SEE FS 553.80(2)(B)
 WITH RESPECT TO REPEAT COMMENTS.
 PLEASE KNOW, THIS IS ONLY NOTICE GIVEN
 AT THIS TIME.
 ** PLEASE KNOW, TWO "E" SHEETS ARE BEING
 RETAINED FOR FILE.
  
 ** PLEASE KNOW, THE NOTES ABOVE HAVE NO
 WAY SPECIFICALLY NOTED EVERY ITEM NOT
 CORRECT, HOWEVER ALL CODES HAVE BEEN
 GIVEN FOR ITEMS WHICH ARE NOT CORRECT ON
 PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-19 Cont ID  
Sent By btrobaug Date 2006-04-19 Time 07:50 Rev Time 1.00
Received By btrobaug Date 2006-04-18 Time 17:52 Sent To P
Notes
2006-04-18 00:00:00 
 FAILED
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE INDICATE THE LOCATION OF THE
 NEW SERVICE ON THE PLAN. SHOW THE
 LOCATION OF THE PANEL AND HOW FED FROM
 THE METER.INDICATE IF A DISCONNECT IS TO
 BE USED.
  
 2} THE 2/0 FEEDER CONDUCTORS DO NOT
 COMPLY WITH 310.15(B)(6) FOR A 225 AMP
 SERVICE..
  
 3} PROVIDE THE FAULT CURRENT RATING FOR
 THE SERVICE EQUIPMENT PER 110.9 & 10.
  
 4} PLEASE SEE THE WASHER AND DRYER
 WATTAGES ARE TOO LARGE IN THE
 CALCULATIONS AND DO NOT CORRELATE TO THE
 PANEL SCHEDULE.
  
 5} THE SMALL APPLIANCES IN THE CALC DO
 NOT COMPLY WITH 220.16(A), 1500VA EACH,
 AND DO NOT CORRELATE WITH THREE SHOWN ON
 THE SCHEDULE.
  
 6) THERE IS AN ERROR ON CIRCUIT #26 @ 40
 AMPS ON A #12 CONDUCTOR. SEE 310.16.
  
 7} PLEASE CLARIFY THE AIR HANDLER
 MOUNTING IN THE MASTER BEDROOM. IS IT IN
 AN ATTIC SPACE, AN DIF SO SHOW
 COMPLIANCE WITH THE REQUIRED LIGHT AND
 RECEPTACLE REQUIRED BY ARTICLES 210.70
 AND 210.63.
  
 8} A RECEPTACLE SHOULD BE ADDED BETWEEN
 OPENINS, EXISTING AND NEW, IN THE FAMILY
 ROOM EAST WALL, IF IT IS 2' OR MORE PER
 210.52(A)(2), SEE REVIEWED PLAN.
  
 9} THE RANGE IN THE CALCULATIONS IS NOT
 LISTED ON THE PANEL SCHEDULE.
  
 10} THE ARC FAULT CIRCUITS REQUIRED BY
 210.12 ARE NOT SHOWN ON THE PANEL
 SCHEDULE.
  
 11} THE 20 AMP BATH CIRCUIT REQUIRED PER
 210.11(C)(3) IS NOT ON THE PANEL
 SCHEDULE.
  
 12} THE WHIRLPOOL TUB IN THE MASTER BATH
 MUST BE PROTECTED BY A GFI PER
 680.62(A).
  
 13 THE WATER PUMP AND IRRIGATION PUMP IN
 THE LOAD CALCULATION ARE NOT LISTED ON
 THE PANEL SCHEDULE
  
 PLEASE COORDINATE THE APPLIANCES
 ACTUALLY INSTALLED OR TO BE INSTALLED
 WITH THE CONTRACTORS PRIOR TO
 RESUBMITTING, AND INDICATE SAME ON BOTH
 LOAD CALCS PER ARTICLE 220, AN DON THE
 SCHEDULE PER ARTICLE 106.3.5.4-8 FBC AS
 AMMENDED BY THE CITY OF WEST PALM BEACH.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-02 Cont ID  
Sent By adarroug Date 2006-08-02 Time 10:53 Rev Time 0.00
Received By adarroug Date 2006-08-02 Time 10:53 Sent To E
Notes
2006-08-02 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-25 Cont ID  
Sent By adarroug Date 2006-07-25 Time 09:35 Rev Time 0.00
Received By adarroug Date 2006-07-25 Time 09:35 Sent To E
Notes
2006-07-25 00:00:00TO "E" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-22 Cont ID  
Sent By adarroug Date 2006-06-22 Time 14:58 Rev Time 0.00
Received By adarroug Date 2006-06-22 Time 14:58 Sent To E
Notes
2006-06-22 00:00:00TO "E" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-18 Cont ID  
Sent By adarroug Date 2006-04-18 Time 11:17 Rev Time 0.00
Received By adarroug Date 2006-04-18 Time 11:17 Sent To E
Notes
2006-04-18 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-05-23 Time   Rev Time 0.00
Received By adarroug Date 2006-04-06 Time 16:40 Sent To  
Notes
2006-04-06 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-08-10 Cont ID  
Sent By tgordon Date 2006-08-10 Time 08:55 Rev Time 0.25
Received By tgordon Date 2006-08-10 Time 08:55 Sent To B
Notes
2006-08-10 00:00:00*** DENIED ***
 1) AS NOTED IN LAST REVIEW 6-28-06 NOTE
 #2. MANUAL J CALCULATIONS ARE CALLING
 FOR 8,608 TOTAL SENSIBLE BTU'S,
 MECHANICAL PLANS ARE CALLING FOR 16,400
 SENSIBLE BTU'S, THE PLANS CAN ONLY CALL
 FOR 20% MORE THAN THE MANUAL J CAL'S,
 PER 2004 FBC 13-607.1.ABC.1.1, PLEASE
 CORRECT. (THE A/C SYSTEM ON THE
 MECHANICAL PLANS IS TO LARGE).
  
 2) ONLY ONE MECHANICAL PLAN WAS
 SUBMITTED, TWO COPYS NEED TO BE
 SUBMITTED.
  
 3) SHOW ON MECHANICAL PLANS EQUIPMENT
 LIST AIR HANDLER UNIT'S TOTAL CFM'S.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-06-28 Cont ID  
Sent By tgordon Date 2006-06-28 Time 10:22 Rev Time 0.25
Received By tgordon Date 2006-06-28 Time 10:34 Sent To B
Notes
2006-06-28 00:00:00*** DENIED ***
 1) AS REQUESTED IN LAST REVIEW 4-20-06
 NOTE #1, PLEASE SUBMIT TWO COPYS OF THE
 ENERGY CALCULATIONS.
  
 2) MANUAL J CALCULATIONS ARE CALLING FOR
 8,608 TOTAL SENSIBLE BTU'S, MECHANICAL
 PLANS ARE CALLING FOR 16,400 SENSIBLE
 BTU'S, THE PLANS CAN ONLY CALL FOR 20%
 MORE THAN THE MANUAL J CAL'S, PER 2004
 FBC 13-607.1.ABC.1.1, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-04-20 Cont ID  
Sent By tgordon Date 2006-04-20 Time 14:23 Rev Time 0.35
Received By tgordon Date 2006-04-20 Time 14:23 Sent To B
Notes
2006-04-20 00:00:00*** DENIED ***
 1) PROVIDE TWO COPYS OF THE ENERGY
 CALCULATIONS.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT.
  
 3) ENERGY CALCULATIONS ARE CALLING FOR 5
 KW HEAT, THE PLANS ARE CALLING FOR 10 KW
 HEAT, THE TWO MUST COINCIDE PLEASE
 CORRECT.
  
 4) PLEASE SHOW THE SIZES OF ALL A/C
 DUCTS ON MECHANICAL PLANS.
  
 5) PLEASE SHOW MEANS AND SIZE OF RETURN
 AIR TO AHU.
  
 6) PROVIDE RETURN AIR FOR FAMILY ROOM,
 PER 2004 FBC/R M1602.4 .
  
 7) MASTER BATHROOM REQUIRES AN EXHAUST
 FAN FOR TUB & SHOWER AREA, PER 2004
 FBC/R M1506 .
  
 8) PLEASE SHOW THE LOCATION OF THE
 CONDENSER UNIT ON THE MECHANICAL PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-04-20 Cont ID  
Sent By jleech Date 2006-04-20 Time 10:49 Rev Time 0.00
Received By jleech Date 2006-04-20 Time 10:49 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-04-17 Cont ID  
Sent By mmclean Date 2006-04-13 Time 07:09 Rev Time 0.00
Received By mmclean Date 2006-04-13 Time 07:09 Sent To I
Notes
2006-04-17 00:00:00NOTE: PROPOSED ADDITION ONLY.
  
 4/17/06 REC'D PLANS FROM RB WHO REC'D
 FROM INCOMING REGARDING THE STOP NOT
 ENTERED IN THE SYSTEM. ENTERED.