| 2006-04-07 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED.PLEASE KEEP THE |
| | NOC PROVIDED IN THE PACKAGE. |
| | |
| | 2.)THE CERTIFICATE OF AUTHORIZATION |
| | NUMBER FOR THE ENGINEERING FIRM IS |
| | REQUIRED TO BE ON THE PLAN, |
| | FAC61G15-23.002. |
| | |
| | 3.)THE ENGINEER'S SEAL IS EXPIRED.IT |
| | IS TO STATE "LICENSE", NOT |
| | "CERTIFICATE", FAC61G15-23.ALSO SEE |
| | THE FPBE WEBSITE, WWW.FBPE.ORG. |
| | |
| | 4.) REVISE THE PROJECT DESCRIPTION ON |
| | THE APPLICATION.REFERRING TO ANOTHER |
| | DOCUMENT IS NOT A DESCRIPTION OF THE |
| | PROJECT. |
| | |
| | 5.)SEE ATTACHED POLICY IN REGARDS TO |
| | INFORMATION REQUIRED FOR REROOF PERMITS. |
| | INCLUDE ALL REQUIRED INFORMATION ON THE |
| | PROJECT DESCRIPTION. |
| | |
| | 6.)YOUR PROJECT DESCRIPTION REFERS TO |
| | SPECIFICATIONS, THE SPECIFICATION REFERS |
| | TO THE CONDO ASSOCIATION AS THE JOB |
| | LOCATION.THE NOC |
| | REFERS TO CLUBHOUSE REPAIRS.THERE IS |
| | NOTHING ON EITHER THE APPLICATION OR THE |
| | ENGINEERING INDICATING THE BUILDING YOU |
| | ARE WORKING ON.PLEASE CLARIFY. |
| | |
| | 7.)PROVIDE INFORMATION IN REGARDS TO |
| | THE EXISTING CONDITIONS.IS FIRE |
| | RESISTANCE REQUIRED BASED ON BUILDING |
| | TYPE?FIRE RESISTANCE INFORMATION WAS |
| | PROVIDED BUT DESIGN CRITERIA WAS NOT |
| | GIVEN.CODE COMPLIANCE CANNOT BE |
| | DETERMINED DUE TO INSUFFICIENT |
| | INFORMATION. |
| | |
| | 8.)THE ENGINEER HAS SPECIFIED 110PSF |
| | AS THE DESIGN PRESSURE.HE HAS |
| | SPECIFIED METAL ROOFING PANELS WHICH |
| | HAVE A DESIGN PRESSURE LIMITATION OF |
| | -41.5PSF, ENHANCED FASTENING NOT ALLOWED |
| | FOR FIELD OR PERMETER ZONES ACCORDING TO |
| | PRODUCT LIMITATION #1 OF THE NOA. |
| | ADDRESS. |
| | |
| | 9.)THE SPECIFICATION STATES TO REMOVE |
| | THE DAMAGED WOODEN SOFFIT TRUSS MEMBERS, |
| | THEN CONSTRUCT NEW METAL TRUSS MEMBERS |
| | TO SUPPORT THE NEW DENSGLASS SOFFIT. |
| | YOUR DRAWING SHOWS STEEL STUDS IN THE |
| | SOFFIT AREA, SIDE ELEVATION.CLARIFY |
| | SCOPE OF WORK.IT APPEARS THAT YOU ARE |
| | REMOVING THE EXISTING WOOD SOFFIT |
| | FRAMING, REBUILDING WITH STEEL FRAMING? |
| | ARE YOU REPLACING ONLY THE ONES WHICH |
| | ARE DAMAGED AS STATED, OR REBUILDING |
| | EVERYTHING?IF YOU ARE REPLACING ONLY |
| | DAMAGED WOOD (WITH STEEL), PROVIDE A |
| | SPECIFICATION FOR FASTENING OF THE |
| | DENSGLASS INTO WOOD.ONLY A STEEL |
| | DETAIL SHOWN. |
| | |
| | 10.) THE SPECIFICATION STATES THAT THIS |
| | IS A WOOD DECK, AND THAT YOU ARE |
| | REPAIRING ROTTED AREAS OF THE WOOD DECK. |
| | THERE IS NO MENTION OF USING DENSDECK, |
| | OR A FASTENING SPECIFICATION, BUT YOU |
| | HAVE INCLUDED THE SPECIFICATION SHEET |
| | FOR DENSDECK.CLARIFY SCOPE OF WORK. |
| | |
| | 11.)SPECIFY DESIGN CRITERIA (WIND) FOR |
| | THE SOFFIT, FBC16. |
| | |
| | 12.)THE SIDE SECTION DETAIL DOES NOT |
| | SHOW A PITCHED ROOF.IT SHOWS A FLAT |
| | DECK.THE FRONT ELEVATION SHOWS WHAT |
| | APPEARS TO BE A PITCHED ROOF.NO ROOF |
| | PITCH IS SPECIFIED ON EITHER THE |
| | APPLICATION, SPECIFICATIONS, OR THE |
| | PLAN.YOU ARE REMOVING A BUILT UP ROOF, |
| | IMPLYING A FLAT DECK, BUT INSTALLING A |
| | METAL ROOF, IMPLYING A PITCHED ROOF. |
| | CLARIFY SCOPE OF WORK AND SITE |
| | CONDITIONS. |
| | |
| | 13.)THE DETAIL ON THE TOP LEFT IS |
| | CONFUSING.YOU SPECIFY TWO FASTENERS, |
| | ONLY ONE IS SHOWN.IT APPEARS TO BE |
| | SHOWING TWO DIFFERENT ATTACHMENTS, |
| | SHOWING THEM ADJACENT, BUT THEY ARE NOT |
| | ADJACENT (ONE AT THE BEAM, THE OTHER AT |
| | THE END OF THE OVERHANG, 4FT AWAY).IT |
| | IS NOT CLEAR WHY THIS EXPLODED DETAIL IS |
| | SHOWN, ESPECIALLY AS IT DIFFERS FROM |
| | BOTH ATTACHMENTS AND SHOWS ONLY ONE |
| | FASTENER WHERE THE TEXT AND OTHER |
| | GRAPHIC SHOWS TWO. |
| | |
| | 14.)FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVAL REQUIRED IN ADDITION TO THE |
| | NOAS SUBMITTED, FAC9B72. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | IF A STATE PRODUCT APPROVAL IS NOT |
| | AVAILABLE, PLEASE ADVISE AND A LOCAL |
| | PRODUCT APPROVAL WILL BE ISSUED. |