Plan Review Details - Permit 06040144
Plan Review Stops For Permit 06040144
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-05-09 Cont ID  
Sent By shill Date 2006-05-09 Time 11:20 Rev Time 0.00
Received By shill Date 2006-05-09 Time 11:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-05-08 Cont ID  
Sent By shill Date 2006-05-08 Time 20:00 Rev Time 0.00
Received By shill Date 2006-05-08 Time 20:00 Sent To  
Notes
2006-05-08 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST
  
 (FROM PREVIOUS LIST) THE INDEX SHEET,
 WHICH YOU REFER TO AS TABLE OF CONTENTS,
 IS TO CLEARLY IDENTIFY EACH SHEET AND IS
 TO BE SEALED. THE INDEX (TABLE OF
 CONTENTS) NUMBERING IS NOT CONSISTENT
 WITH THE CONTENTS OF THE PACKAGE.SEE
 FAC61G15-23.002.
  
 THIRD REVIEW - THE INDEX SHEET HAS BEEN
 REVISED BUT IS NOT SEALED.EITHER SIGN,
 SEAL, AND DATE THE INDEX SHEET OR SIGN,
 SEAL, AND DATE EVERY SHEET IN THE
 SPECIFICAITON.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-05-03 Cont ID  
Sent By shill Date 2006-05-03 Time 14:08 Rev Time 0.00
Received By shill Date 2006-05-03 Time 14:08 Sent To  
Notes
2006-05-04 00:00:00****CORRECTIONS****
  
 ****REVISED CORRECTION LIST AFTER
 TELEPHONE CONVERSATION WITH DAVID
 COLSTON, PE
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LISTS
  
 2.)THE CERTIFICATE OF AUTHORIZATION
 NUMBER FOR THE ENGINEERING FIRM IS
 REQUIRED TO BE ON THE PLAN,
 FAC61G15-23.002.
  
 THE ENGINEER HAS ADDED IT TO THE
 CLUBHOUSE SOFFIT DETAILS SHEET, BUT THAT
 REVISED SHEET HAS NOT BEEN INCLUDED IN
 THE BOUND PERMIT PACKAGE.THE CA NUMBER
 IS NOT ON THE RAS CALCULATIONS.ALSO
 THERE IS ONLY ONE RAS CALCULATION
 ORIGINAL, THE OTHERS ARE PHOTOCOPIES.
 THE CA NUMBER ALSO DOES NOT APPEAR ON
 OTHER SHEETS IN THE PERMIT PACKASGE.I
 HAVE LEFT A MESSAGE WITH FBPE TO CLARIFY
 REQUIREMENTS.
  
 THE INDEX SHEET, WHICH YOU REFER TO AS
 TABLE OF CONTENTS, IS TO CLEARLY
 IDENTIFY EACH SHEET AND IS TO BE SEALED.
 THE INDEX (TABLE OF CONTENTS) NUMBERING
 IS NOT CONSISTENT WITH THE CONTENTS OF
 THE PACKAGE.SEE FAC61G15-23.002.
  
 14.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED IN ADDITION TO THE
 NOAS SUBMITTED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 STATE PRODUCT APPROVAL WAS SUBMTITED FOR
 THE ROOF.PLEASE SUBMIT FOR THE
 DENSGLASS OR ADVISE IF ONE IS NOT
 AVAILABLE AND A LOCAL PA WILL BE ISSUED
 WITH THE NOA.
  
 NEW COMMENT:
  
 REMOVE OLD SHEETS FROM THE BOUND
 ENGINEERING SPECIFICATION.INSERT NEW
 SHEETS INTO THE ENGINEERING
 SPECIFICATION.SUBMIT OLD SHEETS
 SEPARATELY AND MARK "VOID".
  
 YOUR NEW PACKAGE SHOULD INCLUDE THE RAS
 CALCULATIONS, NEW SPECIFICATION SHEETS,
 A NEW INDEX SHEET (SIGNED, SEALED,
 DATED), FLORIDA STATE PRODUCT APPROVALS,
 AND THE MEMO FROM MIAMI DADE REGARDING
 THE ERROR ON THE PRODUCT APPROVAL.
  
  
  
  
  
2006-05-03 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LISTS
  
 2.)THE CERTIFICATE OF AUTHORIZATION
 NUMBER FOR THE ENGINEERING FIRM IS
 REQUIRED TO BE ON THE PLAN,
 FAC61G15-23.002.
  
 NOT ADDRESSED.
  
 14.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED IN ADDITION TO THE
 NOAS SUBMITTED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 IF A STATE PRODUCT APPROVAL IS NOT
 AVAILABLE, PLEASE ADVISE AND A LOCAL
 PRODUCT APPROVAL WILL BE ISSUED.
  
 NOT ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-21 Cont ID  
Sent By shill Date 2006-04-21 Time 19:49 Rev Time 0.00
Received By shill Date 2006-04-21 Time 19:49 Sent To  
Notes
2006-04-21 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.PLEASE KEEP THE
 NOC PROVIDED IN THE PACKAGE.
  
 2.)THE CERTIFICATE OF AUTHORIZATION
 NUMBER FOR THE ENGINEERING FIRM IS
 REQUIRED TO BE ON THE PLAN,
 FAC61G15-23.002.
  
 NOT ADDRESSED.
  
 3.)THE ENGINEER'S SEAL IS EXPIRED.IT
 IS TO STATE "LICENSE", NOT
 "CERTIFICATE", FAC61G15-23.ALSO SEE
 THE FPBE WEBSITE, WWW.FBPE.ORG.
  
 4-7.)ADDRESSED.
  
 8.)THE ENGINEER HAS SPECIFIED 110PSF
 AS THE DESIGN PRESSURE.HE HAS
 SPECIFIED METAL ROOFING PANELS WHICH
 HAVE A DESIGN PRESSURE LIMITATION OF
 -41.5PSF, ENHANCED FASTENING NOT ALLOWED
 FOR FIELD OR PERMETER ZONES ACCORDING TO
 PRODUCT LIMITATION #1 OF THE NOA.
 ADDRESS.
  
 KEEP THE EMAIL FROM MIAMIDADE IN THE
 PACKAGE.WIND DESIGN INFORMATION SHOULD
 BE A PART OF THE PROJECT SPECIFICATION,
 INCLUDING DESIGN PRESSURES FOR
 COMPONENTS AND CLADDING FBC1603.1.4.
  
 9-13.)ADDRESSED.PLEASE INCLUDE THE
 WIND DESIGN INFORMATION INCLUDED WITH
 THE RAS 137 IN THE PROJECT
 SPECIFICATION, SEE #8.
  
 THE CALCULATIONS FOR RAS137 ARE TO BE
 SIGNED, SEALED, DATED.INCLUDE ALL
 INFORMATION REQUIRED BY FAC61G15-23.002.
  
  
 14.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED IN ADDITION TO THE
 NOAS SUBMITTED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 IF A STATE PRODUCT APPROVAL IS NOT
 AVAILABLE, PLEASE ADVISE AND A LOCAL
 PRODUCT APPROVAL WILL BE ISSUED.
  
 NOT ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-07 Cont ID  
Sent By shill Date 2006-04-07 Time 09:59 Rev Time 0.00
Received By shill Date 2006-04-07 Time 09:59 Sent To  
Notes
2006-04-07 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.PLEASE KEEP THE
 NOC PROVIDED IN THE PACKAGE.
  
 2.)THE CERTIFICATE OF AUTHORIZATION
 NUMBER FOR THE ENGINEERING FIRM IS
 REQUIRED TO BE ON THE PLAN,
 FAC61G15-23.002.
  
 3.)THE ENGINEER'S SEAL IS EXPIRED.IT
 IS TO STATE "LICENSE", NOT
 "CERTIFICATE", FAC61G15-23.ALSO SEE
 THE FPBE WEBSITE, WWW.FBPE.ORG.
  
 4.) REVISE THE PROJECT DESCRIPTION ON
 THE APPLICATION.REFERRING TO ANOTHER
 DOCUMENT IS NOT A DESCRIPTION OF THE
 PROJECT.
  
 5.)SEE ATTACHED POLICY IN REGARDS TO
 INFORMATION REQUIRED FOR REROOF PERMITS.
 INCLUDE ALL REQUIRED INFORMATION ON THE
 PROJECT DESCRIPTION.
  
 6.)YOUR PROJECT DESCRIPTION REFERS TO
 SPECIFICATIONS, THE SPECIFICATION REFERS
 TO THE CONDO ASSOCIATION AS THE JOB
 LOCATION.THE NOC
 REFERS TO CLUBHOUSE REPAIRS.THERE IS
 NOTHING ON EITHER THE APPLICATION OR THE
 ENGINEERING INDICATING THE BUILDING YOU
 ARE WORKING ON.PLEASE CLARIFY.
  
 7.)PROVIDE INFORMATION IN REGARDS TO
 THE EXISTING CONDITIONS.IS FIRE
 RESISTANCE REQUIRED BASED ON BUILDING
 TYPE?FIRE RESISTANCE INFORMATION WAS
 PROVIDED BUT DESIGN CRITERIA WAS NOT
 GIVEN.CODE COMPLIANCE CANNOT BE
 DETERMINED DUE TO INSUFFICIENT
 INFORMATION.
  
 8.)THE ENGINEER HAS SPECIFIED 110PSF
 AS THE DESIGN PRESSURE.HE HAS
 SPECIFIED METAL ROOFING PANELS WHICH
 HAVE A DESIGN PRESSURE LIMITATION OF
 -41.5PSF, ENHANCED FASTENING NOT ALLOWED
 FOR FIELD OR PERMETER ZONES ACCORDING TO
 PRODUCT LIMITATION #1 OF THE NOA.
 ADDRESS.
  
 9.)THE SPECIFICATION STATES TO REMOVE
 THE DAMAGED WOODEN SOFFIT TRUSS MEMBERS,
 THEN CONSTRUCT NEW METAL TRUSS MEMBERS
 TO SUPPORT THE NEW DENSGLASS SOFFIT.
 YOUR DRAWING SHOWS STEEL STUDS IN THE
 SOFFIT AREA, SIDE ELEVATION.CLARIFY
 SCOPE OF WORK.IT APPEARS THAT YOU ARE
 REMOVING THE EXISTING WOOD SOFFIT
 FRAMING, REBUILDING WITH STEEL FRAMING?
 ARE YOU REPLACING ONLY THE ONES WHICH
 ARE DAMAGED AS STATED, OR REBUILDING
 EVERYTHING?IF YOU ARE REPLACING ONLY
 DAMAGED WOOD (WITH STEEL), PROVIDE A
 SPECIFICATION FOR FASTENING OF THE
 DENSGLASS INTO WOOD.ONLY A STEEL
 DETAIL SHOWN.
  
 10.) THE SPECIFICATION STATES THAT THIS
 IS A WOOD DECK, AND THAT YOU ARE
 REPAIRING ROTTED AREAS OF THE WOOD DECK.
 THERE IS NO MENTION OF USING DENSDECK,
 OR A FASTENING SPECIFICATION, BUT YOU
 HAVE INCLUDED THE SPECIFICATION SHEET
 FOR DENSDECK.CLARIFY SCOPE OF WORK.
  
 11.)SPECIFY DESIGN CRITERIA (WIND) FOR
 THE SOFFIT, FBC16.
  
 12.)THE SIDE SECTION DETAIL DOES NOT
 SHOW A PITCHED ROOF.IT SHOWS A FLAT
 DECK.THE FRONT ELEVATION SHOWS WHAT
 APPEARS TO BE A PITCHED ROOF.NO ROOF
 PITCH IS SPECIFIED ON EITHER THE
 APPLICATION, SPECIFICATIONS, OR THE
 PLAN.YOU ARE REMOVING A BUILT UP ROOF,
 IMPLYING A FLAT DECK, BUT INSTALLING A
 METAL ROOF, IMPLYING A PITCHED ROOF.
 CLARIFY SCOPE OF WORK AND SITE
 CONDITIONS.
  
 13.)THE DETAIL ON THE TOP LEFT IS
 CONFUSING.YOU SPECIFY TWO FASTENERS,
 ONLY ONE IS SHOWN.IT APPEARS TO BE
 SHOWING TWO DIFFERENT ATTACHMENTS,
 SHOWING THEM ADJACENT, BUT THEY ARE NOT
 ADJACENT (ONE AT THE BEAM, THE OTHER AT
 THE END OF THE OVERHANG, 4FT AWAY).IT
 IS NOT CLEAR WHY THIS EXPLODED DETAIL IS
 SHOWN, ESPECIALLY AS IT DIFFERS FROM
 BOTH ATTACHMENTS AND SHOWS ONLY ONE
 FASTENER WHERE THE TEXT AND OTHER
 GRAPHIC SHOWS TWO.
  
 14.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED IN ADDITION TO THE
 NOAS SUBMITTED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 IF A STATE PRODUCT APPROVAL IS NOT
 AVAILABLE, PLEASE ADVISE AND A LOCAL
 PRODUCT APPROVAL WILL BE ISSUED.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-08 Cont ID  
Sent By adarroug Date 2006-05-08 Time 10:58 Rev Time 0.00
Received By adarroug Date 2006-05-08 Time 10:58 Sent To B
Notes
2006-05-08 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-03 Cont ID  
Sent By adarroug Date 2006-05-03 Time 10:47 Rev Time 0.00
Received By adarroug Date 2006-05-03 Time 10:47 Sent To B
Notes
2006-05-03 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-21 Cont ID  
Sent By adarroug Date 2006-04-21 Time 16:17 Rev Time 0.00
Received By adarroug Date 2006-04-21 Time 16:17 Sent To B
Notes
2006-04-21 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-07 Cont ID  
Sent By shill Date 2006-04-07 Time 14:46 Rev Time 0.00
Received By shill Date 2006-04-06 Time 14:51 Sent To  
Notes
2006-04-06 00:00:00TO "SHILL" DESK