Plan Review Details - Permit 06040141
Plan Review Stops For Permit 06040141
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-10-13 Cont ID  
Sent By alange Date 2006-10-13 Time 11:04 Rev Time 0.00
Received By alange Date 2006-10-13 Time 10:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-09-17 Cont ID  
Sent By amorse Date 2006-09-17 Time 15:42 Rev Time 0.00
Received By amorse Date 2006-09-17 Time 15:42 Sent To PC
Notes
2006-09-17 00:00:00 
  
 DENIED
  
 REVIEW PERFORMED BY ADRIAN MORSE FOR ART
 LANGE WHILE ON LEAVE PER INSTRUCTIONS
 FROM LUIS MARTINEZ
  
 1) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
 ***** PLEASE SEE THAT THEIR ARE LINKS TO
 THE PRODUCT NOA OR EVALUATION REPORT ON
 THE COVER PAGE OF THE PARTICULAR PRODUCT
 THAT IS CHOSEN(SEE THE CIRCLED LINK ON
 THE GAF SHINGLE COVER SHEET)
  
 2) THE NOA'S OR EVALUATION REPORTS ARE
 MISSING FROM THE ROOFING,SINGLE HUNG
 WINDOWS, SWINGING DOORS AND THE FLORIDA
 COVER SHEETS ARE MISSING FROM THE CAST
 CRETE LINTELS
  
 3) PER 106.1.3 FBC* THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS
 AND SPECIFICATIONS "NO WHITE OUT, PENCIL
 OR INK"( PLEASE SUBMIT NEW SIGNED AND
 SEALED SHEETS OF DRAWING FOR PAGES 1/5
 AND2/5 ) THE OLD SHEETS SHALL ALSO BE
 RESUBMITTED BECAUSE OF THE COUNTY STAMP
  
 4) THE SIGNED AND SEALED ENGINEERING OF
 TRUSS COMPONENTS WAS SUBMITTED BUT
 THETRUSS PLACEMENT PLAN IS NOT THE FINAL
 SIGNED AND SEALED SET PLEASE SUBMIT THEM
 TOGETHER, THEY SHALL ALSO BE REVIEWED
 AND APPROVED BY THE DESIGNER OF RECOERD
 (YOUR ARCHITECT)
  
 5) PER 713.13(2) F.S. IF THE IMPROVEMENT
 DISCRIBED IN THE NOTICE OF COMMENCEMENT
 HAS NOT COMMENCED WITHIN 90 DAYS OF
 RECORDING, THENSUCH NOTICE IS VOID AND
 NO LONGER IN EFFECT. PLEASE RE-RECORD
  
 ADRIAN MORSE
 BLDG PLAN REVIEW
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-08-22 Cont ID  
Sent By alange Date 2006-08-22 Time 08:39 Rev Time 1.00
Received By alange Date 2006-08-22 Time 08:39 Sent To  
Notes
2006-08-22 00:00:00DENIED
  
  
 4.SIGN OWNER/ AGENT ON ENERGY CALCS.
  
 5.PRODUCT APPROVALS REQUIRED FOR
 STRAPS TIE-DOWNS AND LINTELS,
  
 PRODUCT APPROVALS SUBMITTED ARE
 INCOMPLETE. SUBMIT TWO COMPLETE SETS.
 ALL NOA'S SHALL HAVE THE STATE PRODUCT
 APPROVAL ATTACHED.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 9.HAND DRAWN CHANGES NOT PERMITTED.
 A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 11.SAFTY GLAZING REQUIRED AT TUB
 LOCATION, R-308.4
  
 NEW COMMENT:
 A.SUBMIT TWO COMPLETE SETS OF PLANS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-20 Cont ID  
Sent By alange Date 2006-07-20 Time 09:06 Rev Time 1.00
Received By alange Date 2006-07-20 Time 09:06 Sent To  
Notes
2006-07-20 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 3.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUE HAS BEEN REVISED TO
 $65,705.
 ADDITIONAL PERMIT FEES ARE DUE.
  
  
 4.SIGN OWNER/ AGENT ON ENERGY CALCS.
  
 5.PRODUCT APPROVALS REQUIRED FOR
 ROOFING, STRAPS TIE-DOWNS, LINTELS,
 EXTERIOR DOORS, WINDOWS AND IMPACT
 PROTECTION.
 PRODUCT APPROVALS SUBMITTED ARE
 INCOMPLETE. SUBMIT TWO COMPLETE SETS.
 ALL NOA'S SHALL HAVEW THE STATE PRODUCT
 APPROVAL ATTACHED.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.SUBMIT TWO SETS OF ORIGONAL SEALED
 TRUSS DRAWINGS FOR REVIEW PER 2004 FBC
 R-802.10.1
  
 9.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 11.SAFTY GLAZING REQUIRED AT TUB
 LOCATION, R-308.4
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-12 Cont ID  
Sent By alange Date 2006-05-12 Time 09:35 Rev Time 1.00
Received By alange Date 2006-05-12 Time 09:35 Sent To  
Notes
2006-05-12 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUE HAS BEEN REVISED TO
 $65,705.
 ADDITIONAL PERMIT FEES ARE DUE.
  
  
 4.SIGN OWNER/ AGENT ON ENERGY CALCS.
  
 5.PRODUCT APPROVALS REQUIRED FOR
 ROOFING, STRAPS TIE-DOWNS, LINTELS,
 EXTERIOR DOORS, WINDOWS AND IMPACT
 PROTECTION.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
  
 9.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 10.SUBMIT 2 ORIGONAL SIGNED AND SEALED
 SURVEYS. FS 472.025
  
 11.SAFTY GLAZING REQUIRED AT TUB
 LOCATION, R-308.4
  
 12.BUILDING ADDRESS NOT ON PLANS.
  
 13. PLANS SHALL BE SIGNED AND SEAL BY
 THE ARCHITECT OF RECORD.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-10-13 Cont ID  
Sent By btrobaug Date 2006-10-13 Time 09:19 Rev Time 0.50
Received By btrobaug Date 2006-10-13 Time 07:55 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-09-12 Cont ID  
Sent By btrobaug Date 2006-09-12 Time 12:29 Rev Time 0.33
Received By btrobaug Date 2006-09-12 Time 12:12 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-08-15 Cont ID  
Sent By btrobaug Date 2006-08-15 Time 10:33 Rev Time 0.33
Received By btrobaug Date 2006-08-15 Time 10:33 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-04-14 Cont ID  
Sent By btrobaug Date 2006-04-14 Time 14:28 Rev Time 0.50
Received By btrobaug Date 2006-04-14 Time 14:15 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-10-10 Cont ID  
Sent By adarroug Date 2006-10-10 Time 10:51 Rev Time 0.00
Received By adarroug Date 2006-10-10 Time 10:51 Sent To E
Notes
2006-10-10 10:51:45TO "BTROBAUGH" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-09-08 Cont ID  
Sent By adarroug Date 2006-09-08 Time 14:03 Rev Time 0.00
Received By adarroug Date 2006-09-08 Time 14:03 Sent To E
Notes
2006-09-08 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-15 Cont ID  
Sent By adarroug Date 2006-08-15 Time 10:06 Rev Time 0.00
Received By adarroug Date 2006-08-15 Time 10:06 Sent To E
Notes
2006-08-15 00:00:00TO "BTROBAUG" DESK/RESUB--ONLY ONE COPY
 OF SHEETS STAMPED

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-19 Cont ID  
Sent By adarroug Date 2006-07-19 Time 13:21 Rev Time 0.00
Received By adarroug Date 2006-07-19 Time 13:21 Sent To B
Notes
2006-07-19 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-13 Cont ID  
Sent By adarroug Date 2006-07-13 Time 16:22 Rev Time 0.00
Received By adarroug Date 2006-07-13 Time 16:22 Sent To Z
Notes
2006-07-13 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-14 Cont ID  
Sent By adarroug Date 2006-04-14 Time 10:26 Rev Time 0.00
Received By adarroug Date 2006-04-14 Time 10:26 Sent To E
Notes
2006-04-14 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-12 Cont ID  
Sent By alange Date 2006-05-12 Time 10:02 Rev Time 0.00
Received By alange Date 2006-04-06 Time 12:07 Sent To  
Notes
2006-04-06 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-04-14 Cont ID  
Sent By tgordon Date 2006-04-14 Time 16:26 Rev Time 0.15
Received By tgordon Date 2006-04-14 Time 16:26 Sent To B
Notes
2006-04-14 00:00:00NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-08-16 Cont ID  
Sent By jleech Date 2006-08-16 Time 07:04 Rev Time 0.00
Received By jleech Date 2006-08-16 Time 07:04 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-04-14 Cont ID  
Sent By jleech Date 2006-04-14 Time 15:10 Rev Time 0.00
Received By jleech Date 2006-04-14 Time 15:10 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2006-11-20 Cont ID  
Sent By mmclean Date 2006-11-20 Time 15:51 Rev Time 0.00
Received By mmclean Date 2006-11-20 Time 15:51 Sent To  
Notes
2006-11-20 15:52:06REVISON: SETBACK CHANGE FROM 9.60 TO 9.07 NORTH/EAST
 SIDE.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-07-18 Cont ID  
Sent By mmclean Date 2006-07-18 Time 14:36 Rev Time 0.00
Received By mmclean Date 2006-07-18 Time 14:36 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-04-13 Cont ID  
Sent By mmclean Date 2006-04-13 Time 09:46 Rev Time 0.00
Received By mmclean Date 2006-04-13 Time 09:46 Sent To I
Notes
2006-04-13 00:00:00DENIED,
 1. MUST PROVIDE TWO CURRENT SURVEY
 (SHOWS THE COMPLETE PROPERTY WITH
 DIMENSION OF LOT).
 2. MUST SHOW ON THE CURRENT SURVEY THE
 PROPOSED ADDITION WITH SETBACKS.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720