Plan Review Details - Permit 06040135
Plan Review Stops For Permit 06040135
Review Stop AD ADDRESSING
Rev No 2 Status F Date 2006-06-16 Cont ID  
Sent By lursu Date 2006-06-16 Time 10:21 Rev Time 0.00
Received By lursu Date 2006-06-16 Time 10:21 Sent To  
Notes
2006-06-16 00:00:00SENT E-MAIL TO DEVELOPER WITH THE
 REQUIREMENTS TO NAME THE PRIVATE STREET
 AS "CORPORATE WAY ".THE STREET NAME MUST
 BE DEPICTED ON THE APPROVED SITE PLAN
 BEFORE RELEASING NEW ADDRESS.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-05-23 Cont ID  
Sent By lursu Date 2006-05-23 Time 14:02 Rev Time 0.00
Received By lursu Date 2006-04-05 Time 15:33 Sent To  
Notes
2006-05-23 00:00:00THE PRIVATE ROADWAY MUST BE NAMED FIRST
 BEFORE ISSUING AN ADDRESS
 E-MAIL WAS SENT TO GEORGE CANTONIS @
 [email protected] ON MAY 19/06
2006-05-19 00:00:00ADDRESS CHANGE FROM 2200 45TH ST TO A
 NEW ADDRESS BASED ON THE PRIVATE ROADWAY
 IS REQUIRED
2006-05-04 00:00:00PROJECT UNDER REVIEW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-10 Cont ID  
Sent By jwitmer Date 2006-05-10 Time 09:50 Rev Time 22.77
Received By jwitmer Date 2006-05-10 Time 09:50 Sent To  
Notes
2006-05-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06040135
 ADD: 2208045TH ST
 CONT:O'CONNORS& TAYLOR, INC.
 TEL: (561)863-7349
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) PLEASE CONTACT LILI URSA MIS
 ADDRESSING TECHNITION FOR THE CORRECT
 ADDRESS. CITY RECORDS INDICATE THE
 CORRECT ADDRESS TO BE 2200 45TH STREET
 FOR THIS PARCEL. CONTACT LILI @ (561)
 805-1239.
  
 THE LETTER FROM THE ARMY CORP OF
 ENGINEERS IS FOR THE PROPERTY LOCATED AT
 2200 45TH ST NOT 2208 45TH STREET.
  
 3) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 4)DLW ARCHITECTS- AA0002714 THE
 CERTIFICATE OF AUTHORIZATION IS NULL &
 VOID SINCE 02/28/2003.
 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 5) ALL A-10 SHEETS (PRODUCT APPROVALS)
 THE DESIGN PROFESSIONAL FAILED TO SIGN
 AND SEAL THESE SHEETS.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 6) THIS STRUCTURE IS CONCIDERED A
 THRESHOLD BUILDING REQUIRING (3) OF ALL
 DOCUMENTS TO BE SUBMITTED TO THE
 BUILDING DEPARTMENT, PLANS, REVISIONS,
 LETTERS,AND OR SUBMITTALS,ETC
  
 7A) WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 7B)FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A
 BUILDING PERMIT FOR THE CONSTRUCTION OF
 A THRESHOLD BUILDING. THE PURPOSE OF
 THE SRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES
 AND SCHEDULES SO THAT THE BUILDING CAN
 BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
 T-0.01INSPECTION PLAN DOESN'T
 INDICATE ANY SHORING OR RESHORING IN THE
 INSPECTION PLAN, NOR LENGTH OF TIME
 SHORING SHOULD BE PLACED THERE.
  
 8) SOILS REPORT SUBMITTED IS A COPY OF
 THE SOILS ENGINEERS' SIGNATURE. NO
 RAISED SEAL.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 9) 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORICSURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED
 SITES.ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 10) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGHWINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 11) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G) NUMBER OF UNITS
 H) NUMBER OF FLOORS
 I) NUMBER OF BEDROOMS
 J) NUMBER OF ROOMS
 K) NUMBER OF BEDROOMS
 L) SQ. FT. LIV SPACE/ FL
 M) SQ. FT. FOOTPRINT
 N) SQ. FT. UNDER ROOF (TOTAL)
 O) OCCUPANT LOAD
 P) FLOOD ZONE
  
 12) 1609.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 13) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 14) THE DESIGNER OF RECORD PRINTING THE
 PRODUCT APPROVALS AS PART OF THE PLAN
 MAKES IT DIFFICULT TO SEE WHAT APPROVALS
 ARE PRESENT AND WHICH AREN'T. ALSO NOTE
 IF THE CONTRACTOR CHANGES OUT PRODUCTS
 ( A REVISION) THE PRODUCT APPROVALS
 PRINTED ON THE ARCHITECTURAL SHEETS WILL
 BE CHARGED A BASE FEE OF $50.00 AND
 $10.00 A PAGE WHERE AS THE PRODUCT
 APPROVAL ITSELF IS CHARGED A TOTAL OF
 $60.00.
  
 15) FL BLD CODE CHAP 13 ENERGY EFFICENCY
 PROVIDE ENERGY CALS/ W MANUAL "J".
 PLEASE USE THE 2004 FORMS. IF A DESIGN
 PROFESSIONAL PRODUCES THE ENERGY CALS,
 MUST BE SIGNED AND SEALED.
  
 16A) PLANS DO NOT SHOW AN ACCESSIBLE
 ENTRANCE, PASSENGER LOADING ZONE,
 11-4.1.2(1). FIGURE 10 ACCESS AISLE AT
 PASSENGER LOADING ZONE.
  
 16B) 11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDINGS OR FACILITY
 ENTRANCES WITH ALL ACCESSIBLE SPACES AND
 ELEMENTS WITHIN THE BUILDING OR
 FACILITY.
  
 17) A-0.1.1 THE PLANS DO NOT SHOW AN
 ACCESSIBLE ROUTE TO 45TH ST.11-4.1.2(1)
 AN ACCESSIBLE SITE SHALL MEET THE
 FOLOWING MINIMUM REQUIREMENTS:
 (1) AT LEAST ONE ACCESSIBLE ROUTE
 COMPLYING WITH SECTION 11-4.3 SHALL BE
 PROVIDED WITHIN THE BOUNDRY OF THE SITE
 FROM PUBLIC TRANSPORTATION STOPS,
 ACCESSIBLE PARKING SPACES, PASSENGER
 LOADING ZONES IF PROVIDED, AND PUBLIC
 STREETS OR SIDEWALKS, AND ACCESSIBLE
 BUILDING ENTRANCE.
  
 18) SHEET A-0.1.1 INDICATES THERE TO BE
 A TOTAL OF 102 PARKING SPACES REQUIRING
 (5) HANDICAPPED PARKING SPACES NOT 4.
 SEE 11-4.1.2(5) 101-150 +5 ACCESSIBLE
 SPACES.
  
 19) SHEET FP-1 PLANS SUBMITTED BY THOMAS
 TOWMEY, PE NOT SEALED,
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 20) SHEET FP-6 INDICATES IN (2) SECTIONS
 THAT THE 4" MAIN IS GOING THE LENGTH OF
 THE ATTIC AREA, A-5.1 AND OTHER CUT
 SHEETS INDICATE THE STRUCTURE IS TO HAVE
 A FLAT ROOF WITH ARCHITECTURAL PEDIMENTS
  
 21A) FIRE SPRINKLER PLANS WERE SUBMITTED
 BUT NO CALCULATIONS?
  
 21B) FP-5INDICATES USE OF A CPVC
 SPRINKLER SYSTEM WHICH IS A R-13(FOUR
 STORIES) WHERE AS THE PLAN CALLS OUT FOR
 A FULL 13 SYSTEM.903.3.1.1 NFPA 13
 SPRINKLER SYSTEMS.
  
 22) THE FIRE PUMP STRUCTURE FOUND ON
 FP-1 DOES NOT SHOW UP ON A-0.1.1, OR
 OTHER SHEETS?
  
 23) S2.03 INDICATES A MECHANICAL ROOM
 FOR THE POOL EQUIPMENT BUT NOT ON THE
 SITE PLAN? NOR DOES THE FIRE PUMP ROOM.
  
 24) EMERGENCY GENERATOR PROVIDE
 ADDITIONAL INFORMATION:
 GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
  
 25) SHEET A-0.03 RAMP COMMENT(2) READS
 THAT LANDING LENGTH SHALL BE A MINIMUM
 OF 60" CLEAR. SHOULD READ: 11-4.8.4(2)
 ALL LANDINGS ON RAMPS SHALL BE NOT LESS
 THAN 60" CLEAR, AND THE BPTTOM OF EACH
 RAMP SHALL HAVE NOT LESS THAN 72" OF
 STRAIGHT AND LEVEL CLEARENCE.
  
 26) SHEET A0.05 4.3.3 WIDTH SEE
 EXEMPTION (44") IF PART OF A MEANS OF
 EGRESS.
  
 27) SHEET A1.1 INDICATES A DETAIL SEE
 A6.2 DETAIL# 3. PLANS INDICATE THAT IT
 IS AN ELEC ROOM# 151, BUT THE DETAIL
 INDICATES A STAIRWELL?
  
 28) SHEET A6.1 UL LISSTING WALL LISTING
 SHEET, THE PRINTING IS TO LIGHT,
 ILLEGIBLE.
  
 29)SHEET A1.1 LAUNDRY CHUTE TERMINATION
 ROOM, WALLS ARE TO BE 1HR RATED, A-3.1
 INDICATES A WALL W8 MO SUCH DETAIL?
  
 30) SAME ENLARGED LAUNDRY DETAIL SHEET
 A-3.1 NOW SHOWS THE LAUNDRY CHUTE ROOM
 IN THE LOWWER RIGHT SIDE OF THE LAUNDRY?
  
 31) ELEVATOR TO THE LAUNDRY AREA DOESN'T
 INDICATE ANY DOOR, 1 1/2 HR PROTECTIVES,
 SHAFT OPENING.
  
 32) SHEET A-3.1 LOWER LEFT INDICATES A
 SECTION 5/A3.2A, MISSING, NO SUCH PAGE.
  
 33) A-1 DOOR# C101 & C102 BOTH APPEAR
 NOT TO HAVE 18" CLEAR ON THE LATCH SIDE.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 34) A-1.1/ A-3.1 ROOM# 122, 124& 125.
 SAME FOR ALL SLEEPING UNITS. SEE:
 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING
 ASSEMBLIES SEPARATING DWELLING UNITS
 FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND
 TRANSMISSION CLASS (STC) OF NOT LESS
 THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90. PENETRATIONS
 OR OPENINGS IN CONSTRUCTION ASSEMBLIES
 FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING,
 VENTILATING OR EXHAUST DUCTS SHALL BE
 SEALED, LINED, INSULATED OR OTHERWISE
 TREATED TO MAINTAIN THE REQUIRED
 RATINGS. THIS REQUIREMENT SHALL NOT
 APPLY TO DWELLING UNIT ENTRANCE DOORS;
 HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 35) 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN
 THE STRUCTURE SHALL HAVE AN IMPACT
 INSULATION CLASS (IIC) RATING OF NOT
 LESS THAN 50 (45 IF FIELD TESTED) WHEN
 TESTED IN ACCORDANCE WITH ASTM E 492.
  
 36) A-1.2- A-1.6.THE 2ND THROUGH THE
 6TH FLOORS, ELEVATOR LOBBIES REQUIRED.
 SEE 2004 CODE COMMENTARY. "EFFECTIVELY,
 THE FOLLOWING BUILDINGS THAT CONTAIN
 ELEVATOR OPENINGS INTO A CORRIDOR WOULD
 RECEIVE ELEVATOR LOBBIES:
 FIVE STORY AND HIGHER FULLY SPRINKLERED
 BUILDINGS OF GROUP H,I-1 AND R.
 ALL GROUPI-3 BUILDINGS.
 NONSPRINKLERD BUILDINGS OF ALL GROUPS
 THAT HAVE REQUIRED FIRE-RESISTANCE-RATED
 CORRIDORS, EXCEPT OFFICE BUILDINGS IN
 COMPLIANCE WITH EXCEPTION # 1.
 707.14.1 ELEVATOR LOBBY.
 ELEVATORS OPENING INTO A
 FIRE-RESISTANCE-RATED CORRIDOR AS
 REQUIRED BY SECTION 1016.1 SHALL BE
 PROVIDED WITH AN ELEVATOR LOBBY AT EACH
 FLOOR CONTAINING SUCH A CORRIDOR. THE
 LOBBY SHALL SEPARATE THE ELEVATORS FROM
 THE CORRIDOR BY FIRE PARTITIONS AND THE
 REQUIRED OPENING PROTECTION. ELEVATOR
 LOBBIES SHALL HAVE AT LEAST ONE MEANS OF
 EGRESS COMPLYING WITH CHAPTER 10 AND
 OTHER PROVISIONS WITHIN THIS CODE.
  
 37) PRODUCT APPROVALS:
 37A) KAWNEER DOORS A10.16, FL 629
 NOA 04-0123.02, PLEASE HIGHLIGHT WHICH
 GLAZING SYSTEM IS TO BE USED.
  
 37B) STANLEY AUTO DOOR A10.18, FL 3627
 REPORT NOT FOUND ON THE STATE WEBSITE
 FBC 2004.FOUND FL 5503 & 6249.
  
 37C)SENTRY GLASS (R) & SAF-GLAS POLY
 CARBONATE 11/32" METRO-DADE NOA NO FL
 LISTING, NEEDS TO BE A TESTED ASSEMBLY
 TAS 201 (LARGE MISSLE).
  
 37D) A10.36 BERRIDGE MANUFACTURING
 REPORT SUBMITTED IS FL 489/ 2001 PLANS
 ARE FILED UNDER FBC 2004.SEE NEW
 LISTINGS. HIGHLIGHT SYSTEMS USED.
  
 37E) A10.48 PGT HORIZONTAL SLIDERS,
 FL 242-R1/ FBC 2001, PLANS FILED UNDER
 FBC 2004.
  
 37F) A10.50 PGT FIXED WINDOWS,
 FL 243-R1/ FBC 2001, PLANS FILED UNDER
 FBC 2004.
  
 37G) SIMPSON STRONG-TIE FL 474 2001 FBC,
 PLANS FILED UNDER FBC2004.
  
 37H) JAMES HARDIE BOARD FL 889 2001 FBC
  
 37I) FLAT ROOF NO REPORT SUBMITTED.
 HIGHLIGHT WHICH SUBSYSTEM TO BE USED.
  
 37J) DRYVIT SYSTEMS, NO REPORT
 SUBMITTED.NOTE SEE SYSTEMS LIMITATIONS
 FOR HORIZONTAL USEAGE!
  
 37K) TRUSS ANCHORS, NO REPORT SUBMITTED
  
 37L) DENSEGLASS GOLD- NO REPORT
 SUBMITTED.
  
 38) SHEET A-3.3 DETAIL #9 A5.5 AND
 DETAIL# 10 BOTH DEAL WITH THE PORTACO
 ROOF SHEATHING, WALL AND ROOF SHEATHING.
 THE PLANS ARE NOT CLEAR AS TO WHAT TYPE
 OF MATERIAL WILL BE USED. TABLE 601 FOR
 TYPE IB ROOF CONSTRUCTION FOOTNOTE "C"
 WILL NOT ALLOW FIRE RETARDANT TREATED
 WOOD SINCE THE BUILDING IS OVER (2)
 STORIES TALL.
  
 39) SAME SHEET A5.5 DETAILS 2 & 3 DEAL
 WITH STEEL EXTERIOR FRAMING, WHERE AS
 S-2.01 INDICATES THE USE OF BLOCK.PLEASE
 PROVIDE MORE INFORMATION.
  
 40) A5.5 PLAN OF PORTACO INDICATES THE
 USE OF STEEL C BEAMS FOR ROOF FRAMING
 MEMBERS.S2.02 DETAIL "B" INDICATES A 2X
 PLATE, (SEE 38) AND SIMPSON TRUSS
 ANCHORS. PLANS DO NOT PROVIDE THE
 VERTICAL, HORIZONTAL OR GRAVITY LOADS TO
 BE RESISTED. NOR WHAT TYPE OF FASTENER
 TOBE USED FOR ANCHORS.
  
 41) A5.6 PLANS INDICATE TO SEE
 STRUCTURAL PLANS FOR FRAMING OF PORTACO,
 WHERE?
  
 42) A5.6 PLANS INDICATE THE USE OF 5/8"
 PLYWOOD SHEATHING, SEE COMMENT38 TYPE IB
 BUILDING.
  
 43) TYPE IB BUILDING TABLE 601 REQUIRES
 VARIOUS FIRE RATINGS DEPENDING ON THE
 STRUCTURAL ELEMENT, PROVIDE INFORMATION
 ON CODE COMPLIANCE?
  
 44) A5.5 & A5.6 BOTH SHOW DETAILS OF
 FOAM TRIM, 1406.2.2ARCHITECTURAL TRIM
 THAT EXCEEDS 40 FEET (12 192 MM) IN
 HEIGHT ABOVE GRADE PLANE SHALL BE
 CONSTRUCTED OF APPROVED NONCOMBUSTIBLE
 MATERIALS AND SHALL BE SECURED TO THE
 WALL WITH METAL OR OTHER APPROVED
 NONCOMBUSTIBLE BRACKETS.
  
 45) A6.2 DETAIL# 4 STAIR HANDRAIL
 MISSING EXTENTION AT THE BOTTOM OF
 STAIR.1009.11.5 HANDRAIL EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD
 OR THE WALKING SURFACE OR SHALL BE
 CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT STAIR FLIGHT. WHERE HANDRAILS
 ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE
 HANDRAILS SHALL EXTEND HORIZONTALLY AT
 LEAST 12 INCHES (305 MM) BEYOND THE TOP
 RISER AND CONTINUE TO SLOPE FOR THE
 DEPTH OF ONE TREAD BEYOND THE BOTTOM
 RISER.
  
 46) HANDRAIL DISCREPANCY, A6.2DETAIL # 5
 INDICATES A ROUND HANDRAIL WHERE AS
 DETAIL# 1 INDICATES USE OF A 1 1/2" SQ
 ALUM TUBE.1009.11.3 HANDRAIL
 GRASPABILITY.
 HANDRAILS WITH A CIRCULAR CROSS SECTION
 SHALL HAVE AN OUTSIDE DIAMETER OF AT
 LEAST 1.25 INCHES (32 MM) AND NOT
 GREATER THAN 2 INCHES (51 MM) OR SHALL
 PROVIDE EQUIVALENT GRASPABILITY. IF THE
 HANDRAIL IS NOT CIRCULAR, IT SHALL HAVE
 A PERIMETER DIMENSION OF AT LEAST 4
 INCHES (102 MM) AND NOT GREATER THAN
 6.25 INCHES (160 MM) WITH A MAXIMUM
 CROSS-SECTION DIMENSION OF 2.25 INCHES
 (57 MM). EDGES SHALL HAVE A MINIMUM
 RADIUS OF 0.01 INCH (0.25 MM).
  
 47) A6.4 WINDOW DETAILS INDICATE BEING
 FLUSH WITH THE EXTERIOR. WITH THE EFIS
 FINISH THE ANCHORING SCREWS OR TAPCONS
 ARE NOT ATTACHING TO ANY FRAMING?
  
 48) SHEET A-6.5.3 PLANS DO NOT SPECIFY
 THE TYPE OF MATERIAL VARIOUS COMPONENTS
 OF TRIM ARE MADE OF.FOAM PLASTICS THAT
 ARE USED AS INTERIOR FINISH SHALL ALSO
 MEET THE FLAME SPREAD INDEX REQUIREMENTS
 FOR INTERIOR FINISH IN ACCORDANCE WITH
 CHAPTER 8 . FOAM PLASTICS INSTALLED AS
 INTERIOR TRIM SHALL COMPLY WITH SECTION
 2604.2 .
  
 2604.2 INTERIOR TRIM.
 FOAM PLASTIC USED AS INTERIOR TRIM SHALL
 COMPLY WITH SECTIONS 2604.2.1 THROUGH
 2604.2.4 .
  
 2604.2.1 DENSITY.
 THE MINIMUM DENSITY OF THE INTERIOR TRIM
 SHALL BE 20 PCF (320 KG/M 3 ).
  
 2604.2.2 THICKNESS.
 THE MAXIMUM THICKNESS OF THE INTERIOR
 TRIM SHALL BE 0.5 INCH (12.7 MM) AND THE
 MAXIMUM WIDTH SHALL BE 8 INCHES (204
 MM).
  
 2604.2.3 AREA LIMITATION.
 THE INTERIOR TRIM SHALL NOT CONSTITUTE
 MORE THAN 10 PERCENT OF THE AGGREGATE
 WALL AND CEILING AREA OF ANY ROOM OR
 SPACE.
  
 2604.2.4 FLAME SPREAD.
 THE FLAME SPREAD INDEX SHALL NOT EXCEED
 75 WHERE TESTED IN ACCORDANCE WITH ASTM
 E 84. THE SMOKE-DEVELOPED INDEX SHALL
 NOT BE LIMITED.
  
 49) A-6.5.6 DETAIL# 11 DEALS WITH THE
 INSWING RESTROOM DOORS VS FIXTURE CLEAR
 FLOOR SPACE. 11-4.19.3 CLEAR FLOOR
 SPACE.
 A CLEAR FLOOR SPACE 30 INCHES BY 48
 INCHES (760 MM BY 1219 MM) COMPLYING
 WITH SECTION 11-4.2.4 SHALL BE PROVIDED
 IN FRONT OF A LAVATORY TO ALLOW FORWARD
 APPROACH. SUCH CLEAR FLOOR SPACE SHALL
 ADJOIN OR OVERLAP AN ACCESSIBLE ROUTE
 AND SHALL EXTEND A MAXIMUM OF 19 INCHES
 (485 MM) UNDERNEATH THE LAVATORY (SEE
 FIGURE 11-32 ). INDICATE A 30"X48" CLEAR
 FLOOR SPACE FOR THE LAV.11-4.22.2 DOORS.
  
 (1)ALL DOORS TO ACCESSIBLE TOILET
 ROOMS SHALL COMPLY WITH SECTION 11-4.13
 . DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE REQUIRED FOR ANY FIXTURE.
  
 50) S-0.01DESIGN CRITERIA WRONG EDITION
 OF THE FBC.
  
 51) S-0.01 WIND LOAD DOES NOT PROVIDE TO
 WHICH EDITION OF ASCE-7 THIS BUILDING
 WAS DESIGNED TOO?
  
 52) S-0.02 WIND DESIGN AGAIN THE WRONG
 CODE EDITION, THE WRONG EDITION OF
 ASCE-7 AND THE WRONG WIND SPEED, SHOULD
 BE 140 MPH ,3 SECOND GUST.
  
 53) S-0.02 OPENING FASTENING CHART
 INDICATES A 130MPH THIS IS A CONVERSION
 FROM 110 MPH FASTEST MILE EQUALS 130MPH
 3 SECOND GUST. PLEASE INDICATE TO WHICH
 METHOD OF TESTING THIS CHART IS IN
 REFRENCE TOO.
  
 54) S-0.03 ROOF END ZONES, THE
 ILLUSTRATON OF THE ROOF IS THE TYPICAL
 SQUARE BOX TAKEN FROM ASCE7-02. PLEASE
 PROVIDE AN ACCURATE DRAWING OF THE
 MULTIPLE END ZONES THAT WILL CONFORM TO
 THIS STRUCTURE.
  
 55) PORTE COCHERE THE T.A.= 50 PLEASE
 REVISIT THIS CALCULATION IF THE LEAST
 DIMENSION OF THE PORT COCHERE IS 30'
 WOULD THE END ZONES BE A TRIBUTARY AREA
 OF 10' NOT 50'?
  
 56) S-1.01 THE ELEVATOR FOUNDATION IS
 NOT SHOWN ON THE FOUNDATION SCHEDULE.
 THERE IS A DETAIL A/ S202 WHICH PROVIDES
 THE WIDTH BUT NOT THE LENGHT OF THE
 FOUNDATION. PLEASE PROVIDE.
  
 57) S-2.03 POOL MECHANICAL ROOM, PART OF
 THIS PERMIT? INDICATE ON APPLICATION AS
 IF ANY OTHER BUILDINGS?
  
 58) S-2.03 POOL MECHANICAL BUILDING
 THERE IS NO INFORMATION AS TO DESIGN?
  
 59) S-2.03 POOL MECH BUILDING, PLAN
 INDICATES ROOF FRAMING MEMBERS 2X4, WHAT
 TYPE OF MATERIAL? SPACING? DECK? LOADS
 TO BE IMPOSED? TYPE OF ROOFING
 ASSEMBLIES?
  
 60) ELEVATOR VENTS:
 3004.2 LOCATION OF VENTS.
 VENTS SHALL BE LOCATED BELOW THE FLOOR
 OR FLOORS AT THE TOP OF THE HOISTWAY,
 AND SHALL OPEN EITHER DIRECTLY TO THE
 OUTER AIR OR THROUGH NONCOMBUSTIBLE
 DUCTS TO THE OUTER AIR. NONCOMBUSTIBLE
 DUCTS SHALL BE PERMITTED TO PASS THROUGH
 THE ELEVATOR MACHINE ROOM PROVIDED THAT
 PORTIONS OF THE DUCTS LOCATED OUTSIDE
 THE HOISTWAY OR MACHINE ROOM ARE
 ENCLOSED BY CONSTRUCTION HAVING NOT LESS
 THAN THE FIRE PROTECTION RATING REQUIRED
 FOR THE HOISTWAY. HOLES IN THE MACHINE
 ROOM FLOORS FOR THE PASSAGE OF ROPES,
 CABLES OR OTHER MOVING ELEVATOR
 EQUIPMENT SHALL BE LIMITED SO AS NOT TO
 PROVIDE GREATER THAN 2 INCHES (51 MM) OF
 CLEARANCE ON ALL SIDES.
  
 3004.3 AREA OF VENTS.
 EXCEPT AS PROVIDED FOR IN SECTION
 3004.3.1 , THE AREA OF THE VENTS SHALL
 NOT BE LESS THAN 3? PERCENT OF THE AREA
 OF THE HOISTWAY NOR LESS THAN 3 SQUARE
 FEET (0.28 M 2 ) FOR EACH ELEVATOR CAR,
 AND NOT LESS THAN 3? PERCENT NOR LESS
 THAN 0.5 SQUARE FOOT (0.047 M 2 ) FOR
 EACH DUMBWAITER CAR IN THE HOISTWAY,
 WHICHEVER IS GREATER. OF THE TOTAL
 REQUIRED VENT AREA, NOT LESS THAN
 ONE-THIRD SHALL BE OF THE PERMANENTLY
 OPEN TYPE UNLESS ALL VENTS ACTIVATE UPON
 DETECTION OF SMOKE FROM ANY OF THE
 ELEVATOR LOBBY SMOKE DETECTORS.
  
 61)3006.5 SHUNT TRIP.
 WHERE ELEVATOR HOISTWAYS OR ELEVATOR
 MACHINE ROOMS CONTAINING ELEVATOR
 CONTROL EQUIPMENT ARE PROTECTED WITH
 AUTOMATIC SPRINKLERS, A MEANS INSTALLED
 IN ACCORDANCE WITH NFPA 72, SECTION
 3?9.4, ELEVATOR SHUTDOWN, SHALL BE
 PROVIDED TO DISCONNECT AUTOMATICALLY THE
 MAIN LINE POWER SUPPLY TO THE AFFECTED
 ELEVATOR PRIOR TO THE APPLICATION OF
 WATER. THIS MEANS SHALL NOT BE
 SELF-RESETTING. THE ACTIVATION OF
 SPRINKLERS OUTSIDE THE HOISTWAY OR
 MACHINE ROOM SHALL NOT DISCONNECT THE
 MAIN LINE POWER SUPPLY.
  
 62) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-14 Cont ID  
Sent By dpalmer Date 2006-05-14 Time 13:36 Rev Time 0.00
Received By dpalmer Date 2006-05-14 Time 11:00 Sent To  
Notes
2006-05-14 00:00:00ONE ROLL IN ELEC FOR REVIEW,
 ******** UNSAT 2ND REVIEW *******
  
 **FAIRFIELD INN/SUITES, FIRST REVIEW
 UNDER 2004 FBC.
  
 ** PLEASE KNOW, PLANS ARE NOT COMPLETE
 AT THIS TIME FOR A COMPLETE REVIEW FOR
 CODE COMPLIANCE.
  
  
 ** PLEASE KNOW, PLANS ORIGINALLY CAME IN
 UNDER THE 2001 FBC AND NOW PLANS ARE
 SUBMITTED UNDER THE 2004 FBC. PLEASE SEE
 MOST OF THE COMMENTS ARE NEW, HOWEVER
 SOME ARE FROM PREVIOUS REVIEW.
  
 ** PLEASE BE SURE TO COMPLETELY REMOVE
 ANY OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
  
 1) NOTE: PLEASE SEE ADDRESSING FOR
 PROJECT SHOULD BE ON TITLE BLOCK FOR
 LOCATION OF PROJECT.
 FAC61G1-16.004, 61G15-23.002
  
 2) NOTE: PLEASE CLARIFY TITLE BLOCK ON
 COVER SHEETS AND ALL TRADE SHEETS.
 PLEASE ALSO SEE STUCTURAL, MECHANICAL
 AND PLUMBING SHEETS AS THESE DO NOT
 CONTAIN ANY TITLE BLOCKS FOR THE
 ENGINEERS OR ENGINEERING FIRMS AS LISTED
 ON COVER SHEETS.
 ** PLEASE SEE A PRINT OUT FROM THE
 STATE'S WEBSITE IS NOW ATTACHED TO
 NOTES, AS THE CERTIFICATE OF
 AUTHORIZATION NUMBER AS INDICATE ON
 TITLE BLOCKS FOR ARCHITECTURAL FIRM IS
 "NULL AND VOID" PER DEPARTMENT OF
 BUSINESS AND PROFESSIOAL REGULATION.
 PLEASE SEE ELECTRICAL SHEETS DO NOT
 INDICATE THIS AND LIST THE ENGINEER AS
 AN INDIVIDUAL?
 PLEASE SEE FAC 61G15-23.002, FS 471.023,
 IF ARCHITECTURAL FIRM IS OFFERING
 ENGIEERING SERVICES, PLEASE PROVIDE
 CERTIFICATE OF AUTHORIZATION FOR THIS.
 THE CA # WAS ADDED FOR ARCHITECTURAL
 FIRM AS REQUESTED ON PREVIOUS REVIEW
 HOWEVER AS NOTED ABOVE, SEEMS NOT BE
 ACTIVE.
 ** PLEASE SEE TITLE BLOCKS ARE MISSING
 THE PRINTED NAME AND LICENSE NUMBER THE
 ARCHITECT AS REQUIRED PER FAC
 61G1-16.004
  
 ** PLEASE BE SURE ALL THREE SETS ARE
 SIGNED, DATED AND SEALED AS REQUIRED
 UNDER FS 481.221,471.025, FAC
 61G1-16,61G15-23.002
 PLEASE SEE MANY SHEETS IN SOME SETS ARE
 NOT SIGNED OER SEALED. PLEASE ALSO SEE
 SOME ROLLS SUBMITTED ARE NOT SIGNED AND
 SEALED AT ALL??
 ***************************************
 **THIS IS FOR ALL TRADES AND FOR ALL
 REVIEWS, WHETHER OR NOT COMMENT IS MADE
 BY OTHER REVIEWER(S).
 **************************************
  
 3) NOTE: PLEASE SEE FP SHEETS, AS SOME
 SHEETS IN SOME SETS ARE PHOTO-COPIES OF
 SIGNED AND SEALED PLANS.
  
 4) NOTE: PLEASE KNOW, PLANS ARE NOW
 BEING SUBMITTED UNDER THE 2004 FBC,
 HOWEVER NO CHANGES IN ELECTRICAL DESIGN
 WERE MADE TO THE NEW 2004 CHAPTER 13.
 PLEASE SEE CHAPTER 13, 13-413.1ABC.1,
 PLEASE PROVIDE ALL WORST CASE CALCS, AND
 ADJUST AS NEEDED FOR LONGEST RUNS.
 PLEASE SEE 13-415.1.ABC.1.1, &.2, & .3
 WHICH GREATLY AFFECT ELECTRICAL DESIGN.
 COULD NOT LOCATE ANY INFORMATION FOR
 THIS ON PLANS.?
 PLEASE SEE ALL OTHER CHANGES IN CHAPTER
 13. FIXTURE TYPES, TANDEM WIRING ETC.
  
 5)NOTE: PLEASE PROVIDE COMPLETE
 PHOTO-METRICS FOR ALL EGRESS
 AREAS/PATHS.
 PLEASE SEE NFPA-101 2003, 7.8.1.3,
 7.9.2.2. PLEASE SEE STAIRS FOR EGRESS
 SHALL CONTAIN A MIN OF 10FT CANDLES AVG
 UNDER NORMAL CONDITIONS AND 1FT CANDLE
 AVG UNDER EM POWER.
 PLEASE SEE MIN REQUIRED FOR ALL OTHER
 PATHS SHALL BE 1FT CANDLE.
 PLEASE ALSO KNOW, AN EM BATTERY BACK UP
 FIXTURE OF SOME TYOE WILL BE REQUIRED IN
 THE MAIN ELECTRICAL ROOM.
 ** PLEASE SEE NOTES ON PLANS MENTIONS
 THE 10 FT CANDLES AT "WAIST LEVEL"?
 PLEASE SEE NFPA-101, AS THIS IS MEASURED
 AT THE WALKING SURFACE.
  
 6) NOTE:PLEASE SEE THE FOLLWOING WAS
 ALSO NOTED ON PREVIOUS REVIEW NOTE #15.
 PLEASE SEE NO INFORMATION WAS SUBMITTED
 FOR THE FIRE PUMP, FIRE PUMP CONTROLLER.
 PLEASE KNOW, ALL PLANS AND INFORMATION
 FOR THIS SHALLBE SUBMITTED.
 PLANS NOW INDICATE A FIRE PUMP LOCATED
 IN A DETACHED BUIDLING? WHICH WILL FEED
 TWO DIFFERENT HOTELS.
 PLEASE KNOW, APPROVAL BY THE FIRE
 MARSHAL'S OFFICE SHALL FIRST BE OBTAINED
 FOR THIS SCENERIO. PLEASE ALSO KNOW,
 PERMIT FOR EITHER BUILDING CAN NOT BE
 PASSED FOR PERMITING UNTIL ALL
 INFORMATION, PLANS ETC FOR FIRE PUMP,
 FIRE PUMP CONTROLLER CAN BE REVIEWED. IF
 ELECTRICAL DRIVEN FIRE PUMP, PLEASE
 PROVIDE ALL INFORMATION.
 PLEASE SEE FP SEEMS TO INDICATE
 ELECTRICAL FIRE PUMP.PLEASE SEE THIS
 FIRE PUMP IS STILL BEING SHOWN BEING FED
 FROM THE MSB WHICH IS NOT PERMITTED AS
 STATED IN PREVIOUS NOTES. PLEASE SEE
 695.4 NEC, NFPA-20 2002.
 PLEASE KNOW, THIS INFORMATION WILL BE
 REQUIRED UNDER THIS PERMIT. THE FIRE
 SPRINKLER AND FIRE ALARM ARE ALSO UNDER
 A SEPARATE PERMIT.MININUM INFORMATION IS
 REQUIRED FOR THE PERMIT ISSUANCE OF EACH
 HOTEL.
  
 7) NOTE: PLEASE SEE PLANS ARE NOW
 INDICATING A BACK UP GENERATOR OF SOME
 SORT? IF ANY PART OF THIS SYSTEM IS
 GOING TO BE INSTALLED, PLEASE SUBMIT ALL
 INFORMATION FOR ATS, GENERATOR,
 ELECTRICAL RISER, SUB BASE FUEL ETC.
 PLEASE SEE TWO SEPARATE ATS'S ARE BEING
 SHOWN ON PLANS AT THIS TIME, HOWEVER
 THIS IS NOTBEING SHOWN WIRED INTO
 RISER?
 PLEASE KNOW, IF NO PART OF THIS SYSTEM
 IS GOING TO BE INSTALLED AT THIS TIME,
 PLEASE REMOVE FROM PLANS AS LONG AS ALL
 MIN LIFE SAFETY BACK UP SYSTEMS ARE
 PROVIDED BY OTHER MEANS.
 **
 PLEASE SUBMIT ALL MANUFACTURE CUT
 SHEETS/SPEC FOR GEN, ATS'S, FIRE PUMP,
 FIRE PUMP CONTROLLER, AND ANY FUEL TANKS
 FOR ITEMS BEING INSTALLED.
  
 8) NOTE: PLEASE SEE PANEL "P" ON SHOWS
 MCB AS REQUIRED, YET PANEL SCHEDULE
 SHOWS THIS PANEL AS "MLO". PLEASE KNOW,
 THIS PANEL IS NOT SHOWN ON PLANS AND
 COULD NOT BE LCOATED?? IS THIS IN A
 DETACHED STRUCTURE? PLEASE KNOW A MEANS
 OF DISCONNECT WILL BE REQUIRED PER
 225.31 AND ALL GROUNDING SHALL BE
 INDICATED PER 250.32
  
 9) NOTE: PLEASE SEE GROUNDING ELECTRODE
 CONDUCTOR ON RISER IS SHOWN AS 1/0?
 PLEASE SEE MIN SHALL BE SIZED PER
 250.66. PLEASE SEE GROUNDING DETAIL
 SUBMITTED INDICATE 1/0 AND 3/0??
 PLEASE CORRELATE WITH MIN REQUIRED.
  
 10) NOTE: PLEASE PROVIDE REFERENCES TO
 THE FOLLOWING CODES ON ELECTRICAL PLANS.
 NFPA-101 2003, NFPA-70 2002, NFPA-72
 2002, NFPA-110 2002, NFPA-20 2002.
 ** PLEASE SEE REPSONSE MENTIONS TO SEE
 COVER SHEET FOR CORRECTED CODES, HOWEVER
 PLEASE SEE COVER SHEETS REFERENCE A
 "2003" NEC? PLEASE SEE WE ARE UNDER 2002
 AND A 2003 IS NOT IN ISSUE. (MISPRINT)?
  
 10) NOTE: PLEASE INDICATE ALL ELECTRICAL
 PANELS ON ALL SHEETS FOR POWER.PLEASE
 SEE ELECTRICAL ROOMS ARE BEING SHOWN
 WITH EGRESS THORUGH "MAIDS CLOSETS".
 THIS WILL NOT BE PERMITTED. MAY NOT
 ACCESS ELECTRICAL ROOMS THROUGH STORAGE
 CLAOSETS OF ANY TYPE.
 PLEASE SEE ALL EGRESS SHALL CONTAIN A
 CLEAR AND UN-OBSTRUCTED PATH OF TRAVEL.
 110.26,408.7,240.24 ETC
  
 11) NOTE: PLEASE SEE PLANS FOR "LARGE
 SCALECOMMERCIAL AREA" ARE NOT
 COMPLETE. PLEASE SEE MISSING LAYOUT FOR
 AREAS LOCATED ON THE FIRST FLR.?
 PLEASE COMPLETE SETS AND PLANS. 215.5
  
 12) NOTE: PLEASE SEE 210.8B3 FOR
 KITCHENS, SEE ALL RECEPTS 15/20A 120 V
 SHALL BE GFI/GFI PROTECTED.
 PLEASE SEE MOST AREAS WERE DONE, HOWEVER
 PLEASE SEE ALL AREAS ARE REQUIRED.
 PREVIOUS REVIEW COMMENT.
  
 13) NOTE: PLEASE SEE GUEST RMS WHICH ARE
 BEING NOTED AS SUITES/DWELLINGS AND
 ROOMS.
 PLEASE SEE 210.60,210.52 PLEASE ADJUST
 ALL CIRCUITING AND LOAD CALCULATIONS,
 PANELS ON PLANS.
 215.5
  
 14) NOTE: PLEASE SUBMIT WIND LOAD
 CALCUALTIONS FOR SITE LIGHTING POLES AS
 REQUESTED ON PREVIOUS REVIEW. THIS COULD
 NOT BE LOCATED ON SITE LIGHTING PLANS?
 215.5
  
 15) NOTE: PLEASE SEE A PREVIOUS NOTE
 MENTIONED THE USE OF A SHUNT TRIP
 BREAKER AND THE MCB STILL BEING REQUIRED
 TO HAVE A MANUAL MEANS OF DISCONNECT
 LOCATED ON THE OUTSIDE RATED RATED FOR
 THE LOAD SERVED. 230.76,230.79 ETC.
 PLEASE SEE PLANS SHALL INDICATE A
 MANUALS MEANS, ETC.
 ** PLEASE ALSO SEEPLANS INDICATE A
 "SERVICE MAIN" LOCATED OUTSIDE HOWEVER
 THIS IS NOT INCLUDED IN RISER?
 215.5
  
 16) NOTE: PLEASE INDICATE PANELS AS
 "FEEDE-THRU" AS PANEL BOARDS SHALL NOT
 CONTAIN MORE THE 42 SPACES.408.15
 PLEASE SEE ALL PANELS ON UPPER FLRS.
  
 17) NOTE: PLEASE SEE A/C UNIT IN ROOMS
 CONSIDERED TO MEET DWELLING UNIT BEDRMS
 SHALL ALSO MEET 210.12B NEC. 2002
  
 18) NOTE: PLEASE SEE NOTES ON RISER AS
 THESE WILL BE AFFECTED BY REVISONS ON
 PLANS.
  
 19) NOTE: PLEASE SEE FIRE REVIEW
 COMMENTS FOR STRETCHER ACCESSIBLE ELEV.
  
 20) NOTE: PLEASE SUBMIT HP RATINGS OF
 ELEVATOR MOTORS, UNABLE TO VERIFY AT
 THIS TIME. NO HP RATING SOR SIZES
 SUBMITTED.
 215.5
  
 21) NOTE: PLEASE SEE CIRCUITES FOR
 ELEVATOR EQUIPMENT DOES NOT CORRELATE
 WITH MSB>.
 215.5
  
 22) NOTE: PLEASE ALSO CORRELATE
 SERVICE MAIN.
 PLEASE SEE RISER IDENTIFIES MAIN AS MSB
 AND SCHEDULE SHOWS MDP?
 PLEASE KEEP IN MIND THE PREVIOUS NOTE
 WIH RESPECT TO THE PLANS ALSO INDICATING
 A "MAIN SERVICE DISC" OUTSIDE?
 215.5
  
 23) NOTE: PLEASE SEE A PANEL "EG" IS
 SHOWN ON PANEL SCHEDULES, HOWEVER NOT
 INFORMATION ON RISER FOR THIS?:
 PLEASE SEE THIS IS ALSO ON PLANS,
 HOWEVER THERE IS NOT ENOUGH INFORMATION
 FOR THIS PANEL, ATS ETC.
 215.5
  
 24) NOTE: PLEASE SEE PANEL 1A SHOWS
 CIRCUITED TO MSB W/ 100A OCP, YET
 MSB/MDP LIST THIS WITH 125A OCP?? PLEASE
 CORRELATE.
  
  
 ** PLEASE KNOW, BASED ON THE PLANS AND
 INFORMATION SUBMITTED THERE MAY BE OTHER
 COMMENTS AS A COMPLETE REVIEW FOR CODE
 COMPLIANCE COULD NOT BE DONE AT THIS
 TIME.
 PLEASE BE SURE TO SEE ALL OF THE 2004
 FBC CHAPTER 13 FOR ELECTRICAL CHANGES.
  
 ** PLEASE KNOW, ONE SET OF PLANS ARE
 BEING RETAINED.
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2006-07-14 Cont ID  
Sent By rchokshi Date 2006-07-14 Time 15:26 Rev Time 0.00
Received By rchokshi Date 2006-07-14 Time 15:21 Sent To  
Notes
2006-07-14 00:00:00PLEASE SUBMIT FOR REVIEW DRAINGE PLANS &
 CALCULATIONS TO VERIFY CONSISTENCY WITH
 SFWMD ERP.
  
 ALSO REQUIRES UTILITIES REVIEW OF WATER
 & SANITARY SEWER.
  
 FOR ANY QUESTIONS PLEASE CALL US
 STEVE SARLEY 494-1095 OR RASIK CHOKSHI
 805-6723
 PLEASE IGNORE " THIS IS A TEST./WRT."
2006-07-13 00:00:00THIS IS A TEST./WRT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-06-15 Cont ID  
Sent By mwennerg Date 2006-06-15 Time 15:01 Rev Time 0.00
Received By mwennerg Date 2006-06-15 Time 15:01 Sent To  
Notes
2006-06-15 00:00:00***DENIED***
  
 1) TEMPORARY STANDPIPES REQUIRED WHEN
 BUILDING REACHES (3) STORIES OR 30' IN
 HEIGHT.
  
 2) PLEASE REFER TO NFPA 101, 2003
 EDITION SEC. 28.2.6 REGARDING TRAVEL
 DISTANCE REQUIREMENTS FOR NEW HOTELS.
  
 3) ADDRESS REQUIRED ON BUILDING THAT
 SHALL BE MINIMUM OF 6" IN HEIGHT AND
 CONTRASTING TO THE BACKGROUND. PLEASE
 SHOW ON ELEVATIONS.
  
 4) PLEASE PROVIDE MANUFACTURER SPEC
 SHEETS FOR GENERATOR AND ASSOCIATED
 EQUIPMENT.
  
 5) POOL AREA SHOWS (1) EXIT. DOES THIS
 AREA MEET EXCEPTION FOR SINGLE EXIT?
  
 6) WILL CARD READERS IMACT REQUIRED
 EXITING FROM BUILDING?
  
 7) EMERGENCY INSTRUCTIONS SHALL BE
 POSTED IN COMPLIANCE WITH NFPA 101, SEC.
 28.7.4.
  
 8) ELEVATORS SHALL COMPLY WITH ASME
 17.1.
  
 9) SIGNAGE SHALL BE PROVIDED IN
 STAIRWELLS INDICATING FLOOR
 IDENTIFICATION, TOP, BOTTOM AND
 DIRECTION TO EXIT DISCHARGE.
  
 10) TACTILE SIGNAGE REQUIRED AT EXIT
 STAIRS.
  
 11) SAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 12) HANDRAILS AND GUARDS TO COMPLY WITH
 NFPA 101, CHAPTER 7. INCORRECT EDITION
 REFERENCED ON SHT A-6.2.
  
 13) SEPARATE SHOPDRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
 14) FIRE ALARM SYSTEM SHALL BE UL
 CERTIFIED FOR CENTRAL STATION SERVICE.
  
 15) FIRE SPRINKLER SYSTEM TO COMPLY WITH
 NFPA 13, 2002 EDITION.
  
 16) FIRE DEPARTMENT VALVES SHALL BE 2
 1/2"- 1 1/2" REDUCER WITH CHAIN.
  
 17) NO FIRE SPRINKLER SHOWN IN WOMENS
 ROOM, SHT FP-4.
  
 18) PLEASE SUBMIT MANUFACTURER SPEC
 SHEETS FOR FIRE PUMP AND ASSOCIATED
 EQUIPMENT.
  
 19) LOCKING KNOX CAPS REQUIRED ON FIRE
 DEPARTMENT CONNECTIONS.
  
 20) SOME OF THE GUEST ROOMS SHOW SMOKE
 DETECTORS TIED TO FA. SINGLE STATION
 TYPES ARE REQUIRED AS SHOWN ON SHT
 4.1.1E.
  
 21) ADDITIONAL EXIT SIGNS AND EMERGENCY
 LIGHTS ARE REQUIRED ON SHT 1.1EA.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2006-06-14 Time   Rev Time 0.00
Received By ptjomsto Date 2006-06-14 Time 10:41 Sent To  
Notes
2006-06-14 00:00:00SUB/APPLICATION/COPY GIVEN TO LILI FOR
 VERIFICATION

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-17 Cont ID  
Sent By mmclean Date 2006-07-12 Time 06:59 Rev Time 0.00
Received By mmclean Date 2006-04-06 Time 13:33 Sent To  
Notes
2006-04-25 00:00:00TO "COMM" BD#25

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-15 Cont ID  
Sent By pkrauss Date 2006-06-15 Time 13:32 Rev Time 0.00
Received By pkrauss Date 2006-06-15 Time 12:57 Sent To  
Notes
2006-06-15 00:00:00CCCDENIED:2004 FLORIDA BUILDING CODE
  
 1.PLAN SHEET A-6.1, PARTITION DETAILS
 ARE NOT LEGIBLE ON TYPES W1 THROUGH W7
 AND W9 THROUGH W11.
  
 2.PLAN SHEET M-1.01 PLEASE CLARIFY THE
 SHAFTS LOCATED IN ROOM 181 & 151.
 ACCORDING TO THE PLAN THE SHAFT WILL
 START AT THE SECOND FLOOR AND A FIRE
 DAMPER WILL BE INSTALLED AT THE
 PENETRATION THROUGH THE 1ST FLOOR
 CEILING/2ND FLOOR SLAB, IS THIS CORRECT?
  
 3.PLAN SHEET A-1.1 AHU CLOSET IN ROOM
 159 (MAINT/ENGINEERING) INDICATES A 20
 MINUTE LOUVERED DOOR.WILL THE LOUVER
 HAVE A FIRE DAMPER?PLEASE CLARIFY IF
 THIS WILL BE USED FOR STORAGE?THE DOOR
 SCHEDULE ON PLAN SHEET A-6.3.2 INDICATES
 THIS AS A "JANITOR" ROOM.RETURN AIR IS
 ONLY REQUIRED FROM HABITABLE ROOMS,
 STORAGE & LAUNDRY ROOMS ARE EXCLUDED.
 2004 FMC 601.4 EXCEPTION #3.
  
 4.MECHANICAL CLOSETS SHALL COMPLY WITH
 2004 FMC 603.9.
  
 5.PLEASE PROVIDE ENERGY AND MANUAL N
 CALCULATIONS IN ACCORDANCE WITH
 407.1.ABC.1 & SECTION 3.1 OF APPENDIX
 13-B.
  
 6.PLEASE PROVIDE MANUFACTURE SUBMITTAL
 DATA FOR THE GENERATOR INSTALLATION.
 PLAN SHEET P-3.05 INDICATES NATURAL GAS
 AS THE FUEL TYPE.PLEASE NOTE,
 GENERATOR SHALL BE PROTECTED FROM
 DAMAGE 2004 FMC 303.4.
  
 7.PLEASE PROVIDE DETAIL FOR THE
 VENTING OF THE GAS DRYERS.PLEASE
 INDICATE DUCT SIZE, MATERIAL &
 TERMINATION. SHOW COMPLIANCE WITH 2004
 FFGC 614 & APPENDIX B.PLEASE INDICATE
 IF THE DRYERS WILL BE DUCTED SINGLE
 APPLIANCE OR TWO OR MORE APPLIANCES
 VENTED TOGETHER.PLEASE PROVIDE
 MANUFACTURE SUBMITTAL DATA FOR THE GAS
 DRYERS.
  
 8.PLEASE PROVIDE COMBUSTION AIR
 CALCULATIONS FOR THE LAUNDRY ROOM.
  
 9.PLEASE PROVIDE MANUFACTURE SUBMITTAL
 DATA FOR THE LAUNDRY CHUTE.SHOW
 COMPLIANCE WITH 2004 FBC 903.2.10.2 &
 NFPA 13.15.2.1.1.
  
 10. PLEASE PROVIDE ANCHORING DETAIL FOR
 THE CONDENSING UNITS IN ACCORDANCE WITH
 2004 FMC 301.13 & 301.13.1.
  
 11. PLEASE PROVIDE SUBMITTAL FOR MAU-1 &
 2.
  
 12. PLEASE PROVIDE ANCHORING DETAIL FOR
 THE CURBS LOCATED ON THE ROOF.
  
 13. FAN SHUTDOWN BY DUCT SMOKE DETECTOR.
 PER 2004 FMC 606.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-06-09 Cont ID  
Sent By kstevens Date 2006-06-09 Time 18:47 Rev Time 0.00
Received By kstevens Date 2006-06-03 Time 11:53 Sent To  
Notes
2006-06-09 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 **THIS PLAN HAS BEEN REVIEWED UNDER
 PERMIT NUMBER 05090945 WHICH HAS BEEN
 VOIDED. ORIGINALLY REVIEWED UNDER
 FBC-2001. SINCE A NEW PERMIT HAS BEEN
 APPLIED FOR, THIS REVIEW WILL BE UNDER
 FBC-2004. THE FOLLOWING COMMENTS ARE
 FROM THE PREVIOUS REVIEW. THE COMMENT
 NUMBER WILL REMAIN THE SAME:
  
 (FIRST REVIEW THIS PERMIT NUMBER)
  
 1. PLANS SHALL BE ROUTED TO DBPR HOTEL &
 RESTURANT DIVISION FOR REVIEW PRIOR TO
 RESUBMITTING TO THE CITY WPB FOR REVIEW.
 SUBMIT A MINIMUM OF 3 SETS OF PLANS
 STAMPED BY DBPR WITH THE TWO PAGE "WORK
 SHEETS" TO EACH SET. SECTION 101.4.7.
 ***NO RESPONSE NOTED. NO STAMPED SHEETS
 FROM DBPR FOUND, WORKSHEETS NOT
 ATTACHED. SECTION 102.2.1.
  
 4. SHT 3.1 TOILET ROOMS SHOW CLEAR FLOOR
 SPACE FOR EACH ACCESSIBLE FIXTURE. SHOW
 TURNING AREA IN EACH TOILET ROOM.
 SECTION 11-4.22.3.
 ***RESPONSE NOTED, BUT CLEAR FLOOR SPACE
 PER 11-4.22.3 NOT TUB CONTROLS WAS
 REQUESTED. THE CLEAR FLOOR SPACE FOR THE
 W/C'S ARE NOT SHOWN. SECTION 11-4.22.3.
  
 5. SHTS A-2.01 & A-2.02 SUBMIT
 CALCULATIONS FOR MINIMUM FACILITIES PER
 TABLES 1003.1 & 403.1 FOR ALL COMMON
 AREAS. SHOW THE SQUARE FOOTAGE OF EACH
 COMMON AREA ON THE FLOOR PLAN.
 ***RESPONSE NOTED, (ON COMMENT #6), BUT
 SHEET A-2.02 NOT SUBMITTED, AND SHEET
 A-2.2 IS A BUILDING EXTERIOR ELEVATION.
 INFORMATION REQUESTED NOT FOUND. PLEASE
 CLARIFY. SECTION 106.1.1. (SEE TABLES
 1004.1.2 & 403.1).
  
 6. SHT A-3.1 SINK IN EMPLOYEE BREAK ROOM
 #156 SHALL COMPLY WITH SECTION 11-4.24
 AND ALL SUBSECTIONS.
 ***RESPONSE NOTED, BUT SECTION 11-4.24.4
 SINK DEPTH STILL NOT SHOWN. PLEASE
 INDICATE ON DETAIL FOR SINK.
  
 11. SUBMIT A BUILDING DRAIN SANITARY
 ISOMETRIC SHOWING ALL PIPE SIZES, DFU'S
 AS THEY ACCUMULATE IN THE SYSTEM, AND
 SHOW RISER LOCATIONS WITH RISER
 DESIGNATION NUMBERS. SECTION 104.2.1 AND
 104.3.1.1.
 ***RESPONSE NOTED, BUT RISER SUBMITTED
 ON SHT P-3.03 DOES NOT REFLECT THE FLOOR
 PLAN. BUILDING SANT. DRAIN IS SHOWN
 EXITING THE BUILDING AT RISERS 14 & 15
 ON THE FLOOR PLAN, BUT EXITING AT RISERS
 1 & 2 ON THE RISER ISOMETRIC. RISER #5
 DOES NOT SHOW THE OFFSET ON THE
 ISOMETRIC AS SHOWN ON THE FLOOR PLAN.
 RISER ISO. DOES NOT SHOW UNIT K-125 AS
 SHOWN ON FLOOR PLAN. FS-1 AND RISER S-15
 DO NOT REFLECT THE FLOOR PLAN AT THE
 CONNECTION TO THE BUILD. DRAIN. FS-1
 SHOWN BETWEEN RISER S-1 & S-3 NOT SHOWN
 ON THE FLOOR PLAN. INDICATE WHERE THE
 BUILDING SANT. DRAIN CHANGES FROM 4" TO
 6" AND SHOW DFU'S AT THAT POINT. SECTION
 106.3.5.1.3 AND TABLE 710.1(1).
  
 12. SHT P-3.01 ALL SANT. RISER DIAGRAMS,
 (EXCEPT S-16), DO NOT REFLECT THE FLOOR
 PLAN, NOR DO THEY MEET CODE
 REQUIREMENTS.
 ***RESPONSE NOTED, BUT NOT RISER 15 DOES
 NOT REFLECT THE FLOOR PLAN. SHOWS FLOOR
 DRAIN NOT FLOOR SINK, AND W.B. CONNECTS
 UPSTREAM OF FLOOR DRAIN ON FLOOR PLAN.
 RISER 14 SHOWS A HORIZONTAL DRY VENT AT
 THE BASE OF THE STACK. THIS IS NOT
 APPROVED PER SECTIONS 905.3 & 905.4.
 (VENT SHOULD CONNECT TO THE STACK WITH
 AN UPRIGHT WYE FITTING ON THE VERTICAL
 PORTION OF THE STACK).
  
 13. SUBMIT A WATER RISER DIAGRAM IN
 ISOMETRIC FORM FOR THE LAUNDRY AND ALL
 COMMON AREAS SHOWNING ALL PIPE SIZES,
 VAVLES, AND WATER HAMMER ARRESTORS,
 (WHERE REQUIRED BY SECTION 604.9).
 ***RESPONSE NOTED, BUT NO WATER LINES
 SHOWN TO THE GUEST LAUNDRY EQUIPMENT
 LAYOUT PLAN, SHT A3.2.
  
 14. SUBMIT A WATER RISER DIAGRAM IN
 ISOMETRIC FORM FOR THE WATER
 DISTRIBUTION SYSTEM SHOWING THE LOCATION
 OF THE WATER ENTERING THE BUILDING, ALL
 PIPING NOT SHOWN ON THE RISERS, ALL PIPE
 SIZES, WATER HAMMER ARRESTORS, LOCATION
 OF WATER RISERS CONNECTING TO THE
 DISTRIBUTION LINE WITH RISER DESIGNATION
 NUMBERS ETC. SECTIONS 104.2.1 AND
 104.3.1.1.
 ***RESPONSE NOTED, BUT WATER HAMMER
 ARRESTORS LOCATED AT THE CLOTHES WASHERS
 TO BE LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN. CAN WASH IS INDICATED AS H.B. ON
 THE FLOOR PLAN. PLEASE CORRELATE. NO
 WATER PIPING SHOWN TO 1ST FLOOR UNITS
 122, 124, 125. RISER DOES NOT REFLECT
 THE FLOOR PLAN AT EW-1. SEPARATE LINE
 SHOWN ON THE FLOOR PLAN TO THIS FIXTURE.
 PLEASE CORRELATE FLOOR PLAN AND RISER
 INFORMATION. SECTION 106.1.1, PDI-WH 201
 & MANUF. INSTALLATION INSTRUCTIONS.
  
 16. THE FOLLOWING INFORMATION IS
 REQUIRED FOR A GAS PERMIT:
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING
 USED).
 ***NO RESPONSE NOTED FOR PIPE MATERIAL.
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 ***RESPONSE NOTEE, BUT BTU'S FOR THE GAS
 GENERATOR AND FIREPLACE AND TOTAL BTU'S
 REFLECTING THE ADDITIONAL BUT'S OF THE
 GENERATOR AND FIREPLACEBTU'S NOT SHOWN.
 FBC-2004 FUEL GAS CODE SECTIONS 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 ***RESPONSE NOTED, BUT THE DISTANCE IS
 NOT CORRECT. WHEN ADDING THE DISTANCE TO
 THE GENERATOR AS SHOWN, THE TOTAL
 DEVELOPED LENGTH IS 372.5 FT. PLEASE
 CLARIFY. FBC-2004 FUEL GAS APPENDIX A -
 USE OF CAPACITY TABLES A.3.1(4).
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2.
 ***NO RESPONSE NOTED, AND MANUF.
 SPECIFICATION SHEETS NOT FOUND. FBC-2004
 FUEL GAS CODE SECTION 402.2, NFPA 54, &
 NFPA 58.
  
 19. ALL INFORMATION REQUIRED BY FAC
 61G1-16.004 & FS 481.219 TO BE IN THE
 TITLE BLOCK OF THE ARCHITECT.
 ***RESPONSE NOTED, BUT INFORMATION STILL
 NOT SHOWN ON ALL SHEETS, AND THE FIRM
 LICENSE HAS BEEN NULL & VOID SINCE
 02-28-2003.
  
 **************NEW COMMENTS**************
  
 1B. SHT A-1.7 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS.
 INDICATE THE SQUARE FOOTAGE BEING
 DRAINED BY EACH DOWNSPOUT. SHOW 1/2 AREA
 OF ALL VERTICAL WALLS INCLUDING PARAPETS
 FOR EACH AREA. - SUBMIT A DETAIL FOR THE
 OPENING TO EACH DOWNSPOUT SHOWING HEIGHT
 & WIDTH ETC. - SUBMIT A DETAIL FOR THE
 EMERGENCY OVERFLOW SCUPPERS. INDICATE
 THE SIZE, (LENGHT & WIDTH), AS WELL AS
 THE MEASUREMENT FROM THE ROOF TO THE
 FLOW LINE OF SCUPPER. (2" TO 4") -
 SCUPPERS SHALL BE SIZED PER SECTIONS
 1101.7 & 1107.3 ALONG WITH TABLE 1106.7.
 THE SIZING OF THE SCUPPERS CAN NOT BE
 DETERMINED WITHOUT REFERENC TO THE
 DEFLECTION OF THE ROOF. PLEASE INDICATE
 ON PLANS THE CLACULATIONS FOR THE
 SCUPPERS.
  
 2B. SHT A-3.2 INDICATES A GUEST WASH
 MACHINE & DRYER WITH NO APPARANT ACCESS,
 SANITARY PIPING OR WATER SUPPLY. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 3B. SHT A-3.3 CANOPY. SUBMIT
 CALCULATIONS FOR PRIMARY AND SECONDARY
 ROOF DRAINS. SHOW SF BEING DRAINED BY
 EACH PRIMARY DRAIN. INDICATE DRAIN SIZE,
 RWL SIZE, FOR PRIMARY AND OVERFLOW
 DRAINS. SUBMIT RISER DIAGRAMS FOR BOTH
 SYSTEMS INDICATING PIPE SIZE, OFFSETS
 AND TERMINATION POINTS. SECTIONS 1106 &
 1107 AND TABLE 1106.3.
  
 4B. SHTS A10.62 THRU A10.65 REFERENCE A
 "HEAT N GLO" GAS FIREPLACE. THIS IS
 SHOWN ON THE FLOOR PLAN, BUT NOT THE GAS
 RISER DIAGRAM. PLEASE CLARIFY. SECTION
 106.1.1.
  
 5B. SHT P-1.07 INDICATES A DRAIN FOR THE
 FIRE SPRINKLER SYSTEM IN THE STAIRWELL
 ADJACENT TO RISER W-2. PLEASE INDICATE
 WHAT THE DRAIN WILL DRAIN INTO. SECTION
 106.1.1.
  
 6B. SHT P-2.01 LAUNDRY WATER HEATER,
 THERMAL EXPANSION CONTROL REQUIRED PER
 SECTION 607.3.2.
  
 7B. SHT P-3.04 WATER MAIN PIPE SIZES DO
 NOT REFLECT PIPE SIZES SHOWN ON SHTS
 P-1.07 & P-5.01. PIPE SIZES TO FROM 3"
 TO 2" THEN BACK TO 2-1/2". PLEASE
 CORRELATE WATER DISTRIBUTION RISERS,
 FLOOR PLAN. SECTION 106.1.1.
  
 8B. ALL ARCHITECTURAL SHEETS, ALL PME
 SHEETS: IF THE DESIGN PROFESSIONAL IS AN
 ARCHITECT OR ENGINEER LEGALLY RESISTERED
 UNDER THE LAWS OF THIS STATE REGULATING
 THE PRACTICE OF ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES,
 PART 1, OR ENGINEERING AS PROVIDED FOR
 IN CHAPTER 471, FLORIDA STATUTES, THEN
 HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE SEAL
 IS AFFIXED TO SAID DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA, AS
 REQUIRED BY FLORIDA STATUTES. SECTION
 106.1.
  
 9B. A SEPARATE IRRIGATION PERMIT AND
 PLANS ARE REQUIRED. THIS MAY BE
 SUBMITTED AT A LATER DATE. SECTIONS
 105.1 AND 106.3.5.1.3.
  
 10B. SUBMIT A ROOF PLAN SHOWING THE
 LOCATION OF ALL VENTS FOR THE SANITARY
 SYSTEM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-12 Cont ID  
Sent By eschneid Date 2006-07-12 Time 13:56 Rev Time 0.00
Received By eschneid Date 2006-07-12 Time 13:56 Sent To  
Notes
2006-07-12 00:00:00PER SHIRLEY GRAHAM -
  
 NO LANDSCAPE PLANS INCLUDED.