Plan Review Details - Permit 06040085
Plan Review Stops For Permit 06040085
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2007-12-11 Cont ID  
Sent By mjacobs Date 2007-12-11 Time 07:03 Rev Time 0.00
Received By mjacobs Date 2007-12-11 Time 06:03 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2007-11-28 Cont ID  
Sent By mjacobs Date 2007-11-28 Time 10:32 Rev Time 0.00
Received By mjacobs Date 2007-11-26 Time 14:17 Sent To PC
Notes
2007-11-27 11:58:30BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)EACH UNIT REQUIRES ITS OWN HANDI-CAP BATHROOM WHICH
 SHALL INDICATE THE UNOBSTRUCTED TURNING SPACE COMPLYING
 WITH SECTION 11-4.2.3. UNITS 'A' AND 'B' BATHROOMS ARE
 MISSING THE TURNING RADIS. NOTE: THE LAYOUT OF THE
 BATHROOM AT THE JOB LOCATION SHALL BE REFLECTED ON THE
 PLANS SUBMITTED.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-06-26 Cont ID  
Sent By mjacobs Date 2007-06-26 Time 10:15 Rev Time 0.00
Received By mjacobs Date 2007-06-26 Time 07:04 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-05-11 Cont ID  
Sent By mjacobs Date 2007-05-11 Time 09:36 Rev Time 0.00
Received By mjacobs Date 2007-05-11 Time 07:12 Sent To PC
Notes
2007-05-11 09:36:02BUILDING PLAN REVIEW
 PERMIT: 06040085
 ADD: 2301 N. TAMARIND AVE.
 CONT: JOYCE DIXON
 TEL: (305)766-2055
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: REV.
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)61G15-23.002THE DRAWINGS SUBMITTED SHALL BE
 SIGN,SEAL AND DATED BY THE ENGINEER.
  
 3)THE WALL DETAIL FOR THE 1 HR RATED WALL DOES NOT
 MATCH THE UL DESIGN 419. THE IS NOW WOOD INDICATED IN
 THE UL DESIGN, HOWEVER THE WALL DETAIL SHOWS 2X4 PT
 WOOD. THE WOOD IS NOT PART OF THE UL DESIGN.ALSO
 PROVIDE THE FIRE STOP DETAIL AS REQUESTED BY THE
 BUILDING INSPECTOR.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-07-24 Cont ID  
Sent By mjacobs Date 2006-07-24 Time 09:23 Rev Time 0.00
Received By mjacobs Date 2006-07-21 Time 11:27 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-07-13 Cont ID  
Sent By mjacobs Date 2006-07-13 Time 10:30 Rev Time 0.00
Received By mjacobs Date 2006-07-07 Time 13:45 Sent To PC
Notes
2006-07-13 00:00:00 
  
 1) SUBMIT TWO COMPLETE SETS OF PLANS AND
 ONE OLD SET. FBC. 106.1.
  
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-05-25 Cont ID  
Sent By mjacobs Date 2006-05-25 Time 06:28 Rev Time 0.00
Received By mjacobs Date 2006-05-24 Time 10:26 Sent To  
Notes
2006-05-24 00:00:001) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 2) INDICATE IN DETAIL DRAWINGS HOW THE
 FLOOR RATING WILL COMPLY WITH THE
 SEPERATION BETWEEN THE BUSINESS AND THE
 RESIDENTAL UNITS ABOVE. SEE FBC TABLE
 302.3.2.
  
 3) THE PRESSURES FOR THE WINDOWS ON THE
 NORTH AND WEST ELEVATIONS ARE MISSING.
 PLEASE SHOW THE PRESSURES FOR THESE
 WINDOWS ON THE DRAWINGS.
  
 4 ) WPB ADMIN CODE 106.3.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. EACH
 PRODUCT WHICH IS APPROVED BY THE STATE
 SHOULD HAVE THE STATE COVER SHEET WITH
 THE MATCHING FL#. SEE EXAMPLE IN PACKAGE
 FOR THE CAMERON ASHLEY-GUARDIAN BUILDING
 PRODUCTS.
  
 5) I NOTICE THAT THE VALUE HAS BEEN
 CHANGED, BUT ACCORDING TO THE SQUARE
 FOOTAGE AND THE SCOPE OF WORK DESCRIBED
 IT STILL SEEMS LOW. A FAIR MARKET VALUE
 IS REQUESTED OR WE WILL USE THE MARSHALL
 AND SWIFT MANUAL TO ADJUST THE VALUE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-19 Cont ID  
Sent By mjacobs Date 2006-04-19 Time 16:35 Rev Time 0.00
Received By mjacobs Date 2006-04-19 Time 10:53 Sent To PC
Notes
2006-04-19 00:00:00 
 1) 104.6.5 BUILDING PERMIT VALUATION. IF
 IN THE OPINION OF THE BUILDING OFFICIAL
 THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL,
 GAS,MECHANICAL OR PLUMBING SYSTEMS
 APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED,
 UNLESS THE APPLICANT CAN SHOW DETAILED
 ESTIMATES AND/OR BONA FIDED SIGNED
 CONTRACTS (EX-CLUDING LAND VALUE) TO
 MEET THE APPROVAL OF THE BUILDING
 OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION FOR BUILDINGS AND
 SYSTEMS SHALL BE FOUND IN MARSHALL AND
 SWIFT OR THE SOUTHERN BUILDING CODE
 CONGRESS INTERNATIONAL VALUATION TABLES,
 LATEST EDITION, AND SHALL BE BASED ON
 TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN
 FEES, OVERHEAD AND PROFIT, EXCLUDING
 ONLY LAND VALUE.
  
 2) A DOOR AND WINDOW SCHEDULE IS
 REQUIRED SHOWING THE SIZE AND TYE OF
 EACH DOOR AND WINDOW ETC.FBC 106.3.5
  
 3) EACH PRODUCT APPROVAL IS REQUIRED TO
 HAVE THE UP-DATED STATE COVER SHEET TO
 MATCH THE INSTALLATION INSTRUCTIONS OR
 NOA. THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
 FOR INFORMATION PLEASE SEE THE STATE
 WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE
 REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE.
  
 4) ALL WINDOWS AND GLAZED DOORS WHICH
 ARE NON-INPACT SHALL HAVE HURRICANE
 PROTECTION. 1609.1.4 PROTECTION OF
 OPENINGS. IN WIND-BORNE DEBRIS REGIONS,
 EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M)
 IN BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS: 1
 GLAZED OPENINGS LOCATED WITHIN 30 FEET
 (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30
 FEET (9.1 M) ABOVE GRADE SHALL MEET THE
 PROVISIONS OF THE SMALL MISSILE TEST.
  
 5) THE DISCRIPTION ON THE APPLICATION
 DOES NOT MENTION ANY ROOFING WORK.
 HOWEVER, THERE IS A SET OF PRODUCT
 APPROVAL IN THE PACKAGE FOR A MODIFIED
 ROOF SYSTEM. IF THE ROOF WILL BE
 REPAIRED INDICATE ON THE PERMIT
 APPLICATION THE SQUARE FOOTAGE OF THE
 ROOF. SELECT OR HI-LIGHT THE APPROVED
 SYSTEM WHICH WILL BE USED. SEE ROOFING
 PROCEDURE IN THE PACKAGE. NOTE: A DETAIL
 DEESCRIPTION OF THE WORK IS REQUIRED ON
 THE APPLICATION. THERE IS NO MENTION OF
 THE BUILDING BEING STUCCOED ON THE
 APPLICATION. PLEASE ALTER THE
 DESCRIPTION ON THE APPLICATION TO MATHC
 THE SCOPE OF WORK FOR OUR RECORDS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
 FAX:(561)805-6731
 [email protected].
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-07-05 Cont ID  
Sent By btrobaug Date 2006-07-05 Time 14:46 Rev Time 0.75
Received By btrobaug Date 2006-07-05 Time 13:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-05-22 Cont ID  
Sent By btrobaug Date 2006-05-22 Time 18:22 Rev Time 1.00
Received By btrobaug Date 2006-05-22 Time 16:53 Sent To  
Notes
2006-05-22 00:00:00 
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PER 700.12(E) UNIT EQUIPMENT.
 INDIVIDUAL UNIT EQUIPMENT FOR EMERGENCY
 ILLUMINATION SHALL CONSIST OF THE
 FOLLOWING: "THE BRANCH CIRCUIT FEEDING
 THE UNIT EQUIPMENT SHALL BE THE SAME
 BRANCH CIRCUIT AS THAT SERVING THE
 NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES."
  
 2} THE GEC MUST BE 2/0 MINIMUM PER
 250.66. THE SERVICE CONDUCTORS ARE
 EQUIVALENT.
 NOTE: WHILE NOT A VIOLATION, ALL THE
 EQUIPMENT GROUNDS FROM THE DISCONNECTS
 TO THE PANELS ARE, CONSIDERABLY, TOO
 LARGE. SEE 250.122.
  
 3} THE GROUNDING ELECTRODE SYSTEM IS
 REQUIRED TO HAVE A SUPPLEMENTAL GROUND
 ROD PER 250.53(D)(2).
  
 4} THE APARTMENT UNITS MUST HAVE SMOKE
 DETECTORS INSTALLED INSIDE, AND OUTSIDE
 THE BEDROOMS.
  
 PLEASE CHECK RECEPTACLE SPACING IN THE
 APARTMENT UNITS PER 210.52.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-11 Cont ID  
Sent By btrobaug Date 2006-04-11 Time 13:35 Rev Time 2.00
Received By btrobaug Date 2006-04-10 Time 18:04 Sent To  
Notes
2006-04-11 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE INDICATE THE LOCATION OF THE
 HOUSE PANEL ON THE PLAN.
  
 2} PLEASE LOCATE THE SERVICE EQUIPMENT
 ON THE PLAN.
  
 3} PLEASE SEE THE SERVICE CONDUCTORS AT
 THE SERVICE ENTRANCE HEAD ARE EXPOSED TO
 RAIN AND SHOULD BE TYPE THHN. SEE
 310.8(C).
  
 4} THE FEEDERS MUST CONTAIN AN EQUIPMENT
 GROUND FROM THE FIRST MEANS OF
 DISCONNECT TO THE PANELS PER 215.6.
  
 5} THE LIGHTING LOADS IN THE OFFICES
 MUST BE CALCULATED AS CONTINUOUS.
  
 6} PLEASE SEE ARTICLE 220 FOR
 RESIDENTIAL CALCULATIONS WHICH MUST BE
 USED FOR THE DWELLING UNITS. A
 COMMERCIAL CALCULATIION IS SHOWN ON THE
 PLAN.
  
 7} THE CODE REFERENCES ON SHEET E0.0
 SHUOLD INDICATE THE ADOPTED VERSION PER
 YEAR. NEC-2002, NFPA-101-2003,
 NFPA-72-2002.
  
 8} THERE IS NO SHEET A1 WITH THE
 SUBMITTED PLANS.
  
 9} AS PER ARTICLE 600.5 BRANCH CIRCUITS.
 (A) REQUIRED BRANCH CIRCUIT. EACH
 COMMERCIAL BUILDING AND EACH COMMERCIAL
 OCCUPANCY ACCESSIBLE TO PEDESTRIANS
 SHALL BE PROVIDED WITH AT LEAST ONE
 OUTLET IN AN ACCESSIBLE LOCATION AT EACH
 ENTRANCE TO EACH TENANT SPACE FOR SIGN
 OR OUTLINE LIGHTING SYSTEM USE. THE
 OUTLET(S) SHALL BE SUPPLIED BY A BRANCH
 CIRCUIT RATED AT LEAST 20 AMPERES THAT
 SUPPLIES NO OTHER LOAD. SERVICE HALLWAYS
 OR CORRIDORS SHALL NOT BE CONSIDERED
 ACCESSIBLE TO PEDESTRIANS. INCLUDE IN
 CALCULATION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-12-10 Cont ID  
Sent By mawillia Date 2007-12-10 Time 14:30 Rev Time 0.00
Received By mawillia Date 2007-12-10 Time 14:00 Sent To B1
Notes
2007-12-10 14:30:20*****REVISION APPROVED*****
  
  
 REVISED PLAN SHEET A-1 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-07-06 Cont ID  
Sent By mwennerg Date 2006-07-06 Time 15:42 Rev Time 0.00
Received By mwennerg Date 2006-07-06 Time 15:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-05-30 Cont ID  
Sent By mwennerg Date 2006-05-30 Time 15:35 Rev Time 0.00
Received By mwennerg Date 2006-05-30 Time 15:35 Sent To  
Notes
2006-05-30 00:00:00***DENIED***
  
 1) PLEASE PROVIDE FURTHER INFORMATION
 REGARDING REQUIREMENTS FOR OUTSIDE
 STAIRS THAT ARE A PART OF MEANS OF
 EGRESS. ARE ALL EXISTING OPENINGS IN
 COMPLIANCE WITH NFPA 101, SECTION
 7.2.2.6.4?
  
 2) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR HANDRAILS AND GUARDS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-04-12 Cont ID  
Sent By mwennerg Date 2006-04-12 Time 10:12 Rev Time 0.00
Received By mwennerg Date 2006-04-12 Time 10:12 Sent To  
Notes
2006-04-12 00:00:00******DENIED******
  
 1) PLEASE NOTE THAT IN ADDITION TO
 APPLICABLE BUILDING CODES, LIFE SAFETY
 SHALL COMPLY WITH NFPA 101, 2003
 EDITION.
  
 2) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 3) PLEASE BE AWARE THAT THE REQUIREMENTS
 OF NFPA 101, SECTION 7.2.2.6.3 REGARDING
 SEPARATION AND PROTECTION OF OUTSIDE
 STAIRS SHALL BE MET. PLEASE INDICATE IF
 BUILDING IS PROTECTED BY AN AUTOMATIC
 FIRE SPRINKLER SYSTEM.
  
 4) PLEASE INDICATE THE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR NEW HANDRAILS
 AND GUARDS.
  
 5) PLEASE SHOW THE LOCATIONS OF REQUIRED
 SMOKE DETECTORS IN RESIDENTIAL UNITS.
  
 6) IF APPLICABLE, SEPARATE SHOP DRAWINGS
 AND PERMITS REQUIRED FOR FIRE
 SPRINKLER/FIRE ALARM SYSTEMS OR REMODEL.
  
 7) PLEASE PROVIDE FURTHER INFORMATION
 REGARDING FIRE RATING OF OPENINGS WITHIN
 10' TO THE OUTSIDE STAIRS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-11-29 Cont ID  
Sent By adarroug Date 2007-11-29 Time 15:03 Rev Time 0.00
Received By adarroug Date 2007-11-29 Time 15:01 Sent To  
Notes
2007-12-03 16:50:16TO "BOB"#13
2007-11-29 15:03:22WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-11-14 Cont ID  
Sent By adarroug Date 2007-11-14 Time 15:51 Rev Time 0.00
Received By adarroug Date 2007-11-14 Time 15:51 Sent To  
Notes
2007-11-19 10:00:38TO "BOB"#7
2007-11-14 15:51:37WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-06-24 Cont ID  
Sent By adarroug Date 2007-06-24 Time 15:17 Rev Time 0.00
Received By adarroug Date 2007-06-24 Time 15:17 Sent To B
Notes
2007-06-24 15:18:00TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-05-10 Cont ID  
Sent By adarroug Date 2007-05-10 Time 15:15 Rev Time 0.00
Received By adarroug Date 2007-05-10 Time 15:15 Sent To B
Notes
2007-05-10 15:16:13TO "MJACOB" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-01-09 Cont ID  
Sent By adarroug Date 2007-01-09 Time 11:04 Rev Time 0.00
Received By adarroug Date 2007-01-09 Time 11:04 Sent To M
Notes
2007-01-09 11:05:15TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-01-04 Cont ID  
Sent By adarroug Date 2007-01-04 Time 12:01 Rev Time 0.00
Received By adarroug Date 2007-01-04 Time 12:01 Sent To M
Notes
2007-01-04 12:05:19TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-12-15 Cont ID  
Sent By adarroug Date 2006-12-15 Time 14:56 Rev Time 0.00
Received By adarroug Date 2006-12-15 Time 14:56 Sent To M
Notes
2006-12-15 14:56:33TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-17 Cont ID  
Sent By adarroug Date 2006-07-17 Time 11:58 Rev Time 0.00
Received By adarroug Date 2006-07-17 Time 11:58 Sent To  
Notes
2006-07-21 00:00:00TO "BOB"#5
2006-07-17 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-21 Cont ID  
Sent By adarroug Date 2006-06-21 Time 11:26 Rev Time 0.00
Received By adarroug Date 2006-06-21 Time 11:26 Sent To  
Notes
2006-06-21 00:00:00TO "BOB"#8

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-22 Cont ID  
Sent By adarroug Date 2006-05-22 Time 10:12 Rev Time 0.00
Received By adarroug Date 2006-05-22 Time 10:12 Sent To  
Notes
2006-05-22 00:00:00TO "BOB"#12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-04-19 Time   Rev Time 0.00
Received By adarroug Date 2006-04-05 Time 16:02 Sent To  
Notes
2006-04-05 00:00:00TO "BOB"#2

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-01-09 Cont ID  
Sent By tgordon Date 2007-01-09 Time 15:37 Rev Time 0.25
Received By tgordon Date 2007-01-09 Time 15:37 Sent To  
Notes
2007-01-09 15:38:31REVISION TO MECH. PLANS PAGE M-0.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2007-01-04 Cont ID  
Sent By tgordon Date 2007-01-04 Time 14:12 Rev Time 0.30
Received By tgordon Date 2007-01-04 Time 14:12 Sent To  
Notes
2007-01-04 14:24:41MECHANICAL REVISION PG. M-0
 *** DENIED ***
 1) RETURN AIR TRANSFER GRILL (CC) 10"X6" NECK SIZE IS
 TO SMALL FOR ANY ROOM WITH OVER 120 CFM'S OF SUPPLY
 AIR, WHICH MOST OF THE ROOMS HAVE MORE CFM'S, PLEASE
 ENLARGE NECK SIZE.
 BALANCED RETURN AIR MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-12-18 Cont ID  
Sent By tgordon Date 2006-12-18 Time 16:51 Rev Time 1.30
Received By tgordon Date 2006-12-18 Time 16:51 Sent To  
Notes
2006-12-18 16:51:55REVISION TO MECH. PLANS PAGE M-1.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-05-31 Cont ID  
Sent By tgordon Date 2006-05-31 Time 10:46 Rev Time 0.00
Received By tgordon Date 2006-05-31 Time 16:43 Sent To  
Notes
2006-05-31 00:00:00REVISION TO MECH. PAGE M-1 .

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-04-06 Cont ID  
Sent By tgordon Date 2006-04-06 Time 09:48 Rev Time 0.40
Received By tgordon Date 2006-04-06 Time 09:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-07-21 Cont ID  
Sent By jleech Date 2006-07-21 Time 13:27 Rev Time 0.00
Received By jleech Date 2006-07-21 Time 13:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-06-29 Cont ID  
Sent By jleech Date 2006-06-29 Time 09:48 Rev Time 0.00
Received By jleech Date 2006-06-29 Time 09:48 Sent To  
Notes
2006-06-29 00:00:00DENIED;
  
 1. (THIRD REQUEST) FLOOR DRAIN IN 2ND
 FLOOR APARTMENT RIGHT SIDE IS STILL
 SHOWN ON THE FLAT DRAWING AND RISER
 DIAGRAM. PLEASE DELETE.
 2. (SECOND REQUEST) DRINKING FOUNTAINS
 ARE REQUIRED PER FBC-2006 PLUMBING SEC.
 410.1. NO BOTTLED WATER.
 3.(SECOND REQUEST) WATER HEATER DETAIL;
 SHUTOFF VALVE FORWATER HEATER IS
 REQUIREDTO BE BEFORE THE EXPANTION TANK
 FOR SERVICE.
 4.(THIRD REQUEST) H/C BATHROOM DOORIN
 SUITE "A" IS REQUIRED TO BE CATTY-CORNER
 TO THE TOILET FBC-2004 SEC. 11-4.17.3.
 5.(SECOND REQUEST)AUTOMATIC CLOTHES
 WASHERS BRANCH DRAINS TO BE 3" PER
 PLUMBING CODE SEC.406.3 WITH A CLEANOUT
 AT 48" ABOVE FINISH FLOOR.
 6.(SECOND REQUEST) PLEASE DELETE WALK IN
 COOLER FROM PAGE P-2.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-06-06 Cont ID  
Sent By jleech Date 2006-06-06 Time 12:32 Rev Time 0.00
Received By jleech Date 2006-06-06 Time 12:32 Sent To  
Notes
2006-06-06 00:00:00DENIED;
 1. (SECOND REQUEST) FLOOR DRAIN IN 2ND
 FLOOR APARTMENT RIGHT SIDE IS STILL
 SHOWN ON FLAT PLUMBING DRAWING AND
 SANITARY RISER DIAGRAM. PLEASE DELETE.
 2.DRINKING FOUNTAINS ARE REQUIRED NOT
 BOTTLE WATER FBC-2004 PLUMBING SECTION
 410.1. THE FIRST DRINK FOUNTAIN MUST BE
 A PLUMBING FIXTURE.
 3.WATER HEATER DETAIL; SHUTOFF VALVE FOR
 HEATER IS REQUIRED TO BE BEFORE
 EXPANSION TANK FOR SEVICEEASY.
 4.(SECOND REQUEST OLD NOTE # 8) H/C
 BATHROOM DOOR IN SUITE "A" IS REQUIRED
 TO BE CATTY-CORNER TO THE W/C FBC-2004
 SEC 11-4.17.3. REVERSE LOCATION OF W/C
 AND LAV.
 5. W/M BRANCH DRAIN TO BE 3" PER
 PLUMBING CODE SEC. 406.3 WITH C.O. AT
 48" AFF.
 6.IF PLANS ARE FOR SHELL ONLY THEN
 PLEASE DELETE FLOOR DRAIN AND NOTE FOR
 WALKIN COOLER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-04-10 Cont ID  
Sent By jleech Date 2006-04-10 Time 10:14 Rev Time 0.00
Received By jleech Date 2006-04-10 Time 10:14 Sent To  
Notes
2006-04-10 00:00:00DENIED;
 1.WATER HEATER DETAIL, PAGE P-O SHOWS
 DRAIN PAN TO OUTSIDE OF BUILDING AS
 REQUIRED BY CODE, SEC 504.7.2. FLOOR
 DRAINS UNDER KITCHEN CABINETS ARE NOT
 REQUIRED. PLEASE DELETE FLOOR DRAINS.
 2.THERMAL EXPANTION CONTROL REQUIRED FOR
 WATER HEATERS IN 2ND FLOOR APPARTMENTS,
 SHOW ON DRAWINGS.
 3.PLUMBING NOTES; #16 FIRE RATED FOAM,
 PLEASE GIVE BRAND NAME AND UL LISTING.
 4.DRINKING FOUNTAINS ARE REQUIRED IN
 RETAIL SPACES. TABLE 403.1.
 5.PAGE P-2 AT WATER SEVICE AND NOTE,
 BACKFLOW REQUIRED.
 6. 2ND FLOOR APARTMENTS; AUTOMATIC
 CLOTHES WASHING FACILITIES ARE REQUIRED
 TABLE 403.1.
 7.WATER RISER DIAGRAM, WATER HAMMER
 ARRESTORS ARE REQUIRED AT ICE MAKER LINE
 AND HOT SIDE OF KITCHEN SINKS. 604.9
 8.PAGE LS-1 FLOOR PLAN, FISH MARKET,
 BATHROOM DOOR SHOUD BE CATTY-CORNER TO
 THE WATER CLOSET FBC-2004 CHAPTER 11 SEC
 11-4.17.3.
 9.BOTH TOILET ROOMS ARE REQUIRED TO BE
 HANDICAP PER SEC. 11-4.22.
 10.SHOW THE SIZE OF HANDICAP BATHROOMS.
 11.PLEASE CONTACT THE DEPT. OF
 AGRICULTURE AND CONSUMER SERVICES AT;
 170 ADMINISTRATION BUILDING
 3125 CONNER BLVD.
 TALLAHASSEE FL. 32399-1650
 PHONE # (904)488-3951
 DR. JOHN REICHNER
 OR(800)435-7352
 OTHER PLUMBING FIXTURES MAY BE REQUIRED,
 HAND SINKS, FLOOR DRAINS, CLEANING
 TABLES, 3 COMPARTMENT SINK AND WATER
 HEATER FOR AN ADEQUATE SUPPLY OF HOT
 WATER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved