Plan Review Details - Permit 06040067
Plan Review Stops For Permit 06040067
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-10-26 Cont ID  
Sent By jwitmer Date 2006-10-26 Time 08:09 Rev Time 0.77
Received By jwitmer Date 2006-10-26 Time 08:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-09-19 Cont ID  
Sent By dpalmer Date 2006-10-17 Time 17:55 Rev Time 0.77
Received By jwitmer Date 2006-09-19 Time 12:41 Sent To  
Notes
2006-09-19 00:00:00ADD: 700 S. ROSEMARY AV #130
 CONT:PLAN REVIEW
 TEL: (561)213-6975 STEVE
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) COMPLIED.
  
 3) SECOND REQUEST, THE ARCHITECT PLACED
 HIS OWN PROFESSIONAL LICENSE NUMBER AS
 THE FIRMS LICENSE NUMBER.
 ZAG ZAMPERELLI ARCHITECTURAL GROUP,
 MISSING THEIR CERTIFICATE OF
 AUTHORIZATION.481.219 F.S.CERTIFICATE
 OF AUTHORIZATION.THE TITLE BLOCK FOR
 ANY SHEET BEARING THE NAME OF AN
 ARCHITECT PRACTICING UNDER A FICTITIOUS
 NAME, A CORPORATION, OR A PARTNERSHIP,
 OFFERING ARCHITECTURAL SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
  
 4) COMPLIED.
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7A) COMPLIED
  
 7B) COMPLIED
  
 7C)COMPLIED.
 7D) COMPLIED
  
 7E) COMPLIED.
  
 8) NOTE: THE NEW PLANS WILL NEED
 TO BE RESTAMPED FOR APPROVAL BY CITY
 PLACE BEFORE SUBMITTAL TO CITY FOR
 REVIEW.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-19 Cont ID  
Sent By jwitmer Date 2006-07-19 Time 12:48 Rev Time 1.11
Received By jwitmer Date 2006-07-19 Time 12:09 Sent To  
Notes
2006-07-19 00:00:00PERMIT: 06040067
 ADD: 700 S. ROSEMARY AV #130
 CONT:PLAN REVIEW
 TEL: (561)213-6975 STEVE
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) COMPLIED.
  
 3) SECOND REQUEST, THE ARCHITECT PLACED
 HIS OWN PROFESSIONAL LICENSE NUMBER AS
 THE FIRMS LICENSE NUMBER.
 ZAG ZAMPERELLI ARCHITECTURAL GROUP,
 MISSING THEIR CERTIFICATE OF
 AUTHORIZATION.481.219 F.S.CERTIFICATE
 OF AUTHORIZATION.THE TITLE BLOCK FOR
 ANY SHEET BEARING THE NAME OF AN
 ARCHITECT PRACTICING UNDER A FICTITIOUS
 NAME, A CORPORATION, OR A PARTNERSHIP,
 OFFERING ARCHITECTURAL SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
  
 4) COMPLIED.
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7A) COMPLIED
  
 7B) COMPLIED
  
 7C) 2ND REQUEST BUILDING TYPE, NOTE TAKE
 THE SIZE OF THE BUILDING INTO ACCOUNT,
 ALSO NOTE THE PARKING GARAGE IS PART OF
 THE SAME BUILDING!!!!
  
 7D) COMPLIED
  
 7E) COMPLIED.
  
 8) NEW COMMENT, THE NEW PLANS WILL NEED
 TO BE RESTAMPED FOR APPROVAL BY CITY
 PLACE BEFORE SUBMITTAL TO CITY FOR
 REVIEW.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-09 Cont ID  
Sent By jwitmer Date 2006-05-09 Time 12:28 Rev Time 2.22
Received By jwitmer Date 2006-05-09 Time 12:24 Sent To  
Notes
2006-05-09 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06040067
 ADD: 700 S. ROSEMARY AV #130
 CONT:PLAN REVIEW
 TEL: (561)213-6975 STEVE
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) A-0 BUILDING DEPARTMENT DATA FOR
 HANDICAPPED CODE, THE ONLY CODE ADOPTED
 BY FLORIDA IS THE FLORIDA ACCESSIBILITY
 CODE, CHAPTER 11 OF 2004 FBC. DELETE THE
 OTHER REFRENCES, PLEASE.
  
 3) ZAG ZAMPERELLI ARCHITECTURAL GROUP,
 MISSING THEIR CERTIFICATE OF
 AUTHORIZATION.481.219 F.S.CERTIFICATE
 OF AUTHORIZATION.THE TITLE BLOCK FOR
 ANY SHEET BEARING THE NAME OF AN
 ARCHITECT PRACTICING UNDER A FICTITIOUS
 NAME, A CORPORATION, OR A PARTNERSHIP,
 OFFERING ARCHITECTURAL SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 4) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5) 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 6) FL BLD CODE 1609.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STOREFRONT WINDOWS
 B) MULLIONS
 C) STOREFRONT DOORS
  
 7) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2006-12-26 Cont ID  
Sent By dpalmer Date 2006-12-26 Time 15:40 Rev Time 0.00
Received By dpalmer Date 2006-12-26 Time 14:56 Sent To PC
Notes
2006-12-26 15:42:35PLANS REDLINED:
  
 ONLY FIXTURES CONTAINING THE "NL" DESIGNATIONS ARE TO
 REMAIN "ON" AS NIGHT LIGHTS, NOT ALL FIXTURES ON THAT
 CIRCUIT.
 PLEASE ALSO SEE NOTES HIGHLIGHTED AS THE PER CIRCUITING
 OF EM / EXT LTS. 700.12E.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2006-12-06 Cont ID  
Sent By dpalmer Date 2006-12-06 Time 20:36 Rev Time 0.00
Received By dpalmer Date 2006-12-06 Time 20:25 Sent To PC
Notes
2006-12-06 20:37:07*** UNSAT ***
  
 1) NOTE:PLEASE UPDATE PLANS AND CORRELATE REVISIONS
 ON PLANS WITH THE TITLE BLOCKS. PLEASE SEE PLANS ARE
 BEING SUBMITTED WITH REV #4, WHERE PLANS ON FILE
 ALREADY CONTAIN REVISIONS 5 AND 6. PLEASE SEE THAT ALL
 CORRELATE.
 FBC 106.1.2, 106.1.3.5.1
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-11-02 Cont ID  
Sent By dpalmer Date 2006-11-02 Time 14:16 Rev Time 0.00
Received By dpalmer Date 2006-11-02 Time 13:37 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-10-15 Cont ID  
Sent By dpalmer Date 2006-10-15 Time 15:40 Rev Time 0.00
Received By dpalmer Date 2006-10-15 Time 17:57 Sent To  
Notes
2006-10-15 15:40:27*** UNSAT4THREVIEW *****
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF COMPPLIANCE.
  
  
 1) NOTE: PLEASE SEE AS STATED IN PREVIOUS REVIEWS, ALL
 SEPARATE SPACES REQUIRE OVER-RIDE DEVICE(S) .
 PLEASE SEE PREVIOUS NOTES FOR SCHEDULING.
 PLEASE SEE PREVIOUS NOTES FOR MAX WATTAGE PERMITTED.
 BASED ON THE WATTAGE ON FIXTURES ON PLANS, THIS EXCEEDS
 THE "PROPOSED WATTAGE" WHICH IS STATED ON PLANS. PLEASE
 PROVIDE A COMPLETE SUMMARY OF AREAS FOR LIGHTING POWER
 DENSITIES AS ALLOWED PER CODE. PLEASE SEE TABLES AS
 PERVIOUSLY NOTED.
 PLEASE SEE SOME FIXTURES AND EM LTS ARE SHOWN BEING
 CIRCUITED THROUGH TIMER WHICH IS OK, HOWEVER THESE ARE
 NOTEDBEING WIRED AHEAD OF CONTROLS, HOWEVER SHOULD BE
 SHOWN ON LIGHTING DETAIL SO THIS ALLEAVIATES ANY
 CONFUSION. THIS ITEM IS NOT REQUIRED , HOWEVER
 RECOMMENDED. IT IS CLEAR TO THE DESIGNER AND REVIEWER
 OF THE INTENT, HOWEVER THE TIME CONTROL PANEL DOES NOT
 INDICATE THIS AND HOW THIS WILL TAKE PLACE.
 PLEASE ALSO CORRELATE WITHTHE WATTAGE BEING SHOWN ON
 PANEL SCHEDULES, AS THIS WATTAGE EXCEED ACTUAL SHOWN
 AND PROPOSED DESIGN WATTAGE.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE 13-415..ABC.1. , PLEASE SEE WHERE TRADES
 OFFS ARE NOT PERMITTED UNDER CERTAINS CIRCUMSTANCES.
 PLEASE SEE TABLES 415.2.C.1, 415.2.B.1
 IT APPERS A WATTAGEAS SHOWN IS COMING FROM THE SPACE
 BY SPACE TABLES AT 2.1, HOWEVER PLEASE SEE FBCAS
 NOTED.
  
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEWS WITH RESPECT
 RELEVANT CODES NOT CURRENT. PLEASE SEE PREVIOUS NOTES
 WHICH ALSO MENTIONED "A" SHEET(S). STILL SHOW 1999
 NEC.
  
  
 3) NOTE: PLEASE SEE FEES FOR FS 553.80(2)(B) HAS NOW
 BEEN ASSESSED AND MUST BE PAID BEFORE PLANS ARE
 RESUBMITTED ON NEXT REVIEW.
 THIS FEE IS $3132.00
 PLANS WILL RETAINED BY THIS OFFICE FOR POSSIBLE REVIEW
 FROM THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-08-25 Cont ID  
Sent By dpalmer Date 2006-08-25 Time 17:47 Rev Time 0.00
Received By dpalmer Date 2006-08-25 Time 11:27 Sent To  
Notes
2006-08-25 00:00:00******* UNSAT 3RD REVIEW *****
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEWS STILL NEED TO BE
 ADDRESSED.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
  
  
  
 1) NOTE:NO. SEE PREVIOUS NOTE.
  
 ** PREVIOUS REVIEW NOTE 2ND REVIEW **
 NO, PLEASE SEE THERE ARE
 PLACES ON PLANS WHICH STILL REFLECT
 OLDER CODES. PLEASE SEE "A" SHEETS, AND
 E-SHEETS. PLEASE SEE NOW THE CHANGES
 MADE ON E-3 NOW CONTAIN BOTH THE
 PREVIOUS AND CURRENT ELECTRICAL CODE.
 PLEASE SEE E-4 WHICH STILL REFLECTS
 SBCCI, SFBC, 1997 LS 101 ETC.
  
 ** PREVIOUS REVIEW 1ST REVIEW NOTE**
 PLEASE ADJUST AND REFLECT ALL
 CURRENT CODES IN AFFECT.
 PLEASE SEE WE ARE UNDER THE 2002
 NFPA-70( NEC), 2003 NFPA-101, 2002
 NFPA-72.
 PLEASE KNOW THESE CODES AT A MINIMUM
 SHALL BE REFERENCED ON ARCHITECTURAL AND
 ELECTRICAL/ FIRE PLANS.
 PLEASE SEE PLANS REFLECT 1999 NEC, 1997
 SBC, AND THE SBCCI ETC.
 PLEASE SE COMMENTS FROM OTHER TRADES
 WITH RESPECT TO CODES. (BUILDING).
  
 2) NOTE: NO. IT IS BEING NOTED THAT ONE
 FIRM LICENSE NUMBER IS NOW BEING SHOWN,
 HOWEVERPLEASE KNOW WE HAVE BEEN IN
 CONTACT WITH THE STATE'S LEGAL COUNSEL
 TO THE BOARD OF ARCHITECTS AS THE FIRM
 LICENSE NUMBER PROVIDED IS LISTED ON THE
 STATE'S WEBSITE FOR V.Z.AARCHITECT'S
 P.A. AND THERE IS NO LISTING FOR
 "ZAMPARELLI ARCHITECTURAL GROUP" AKA
 "ZAG".
 PLEASE KNOW THIS HAS BEEN CONFIRMED WITH
 DWIGHT CHASTANE FROM THE FIRM WHICH
 REPRESENTSTHE STATE BOARD OF
 ARCHITECTURE'S LEGAL COUNSEL. IT IS
 MENTIONED THAT BOTH COMPANIES AS LISTED
 ON TITLE BLOCKSWHICH ARE REGIESTERED
 WITH THE STATEWOULD EACH REQUIRE A
 CERTIFICATE OF AUTHORIZATION NUMBER.
  
 ** PREVIOUS REVIEW NOTE 2ND REVIEW**
 NO, PLEASE SEE ONLY THE
 PRINTED NAME AND LICENSE # OF THE
 ARCHITECT WAS ADDED. PLEASE SEE THE FIRM
 TITLE BLOCK IS STILL MISSING THE
 REQUIRED FIRM LICENSE NUMBER WHICH IS
 ALSO KNOWN AS THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
 FS 481.219, FAC 61G1-16.004
  
 ** PREVIOUS REVIEW NOTE 1ST REVIEW **
 PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCKS FOR ARCHITECT AND
 ARCHITECTURAL FIRM. PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004 AND
 FLORIDA STATUES 481.219.
 MISSING THE PRINTED NAME AND LICENSE #
 OF THE ARCHITECT, MISSING THE FIRM
 LICENSE # FOR THE ARCHITECTURAL FIRM.
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE: OK.
  
 6) NOTE: OK.
  
 7) NOTE: OK
  
 ******** NEW NOTES 2ND REVIEW ******
  
 8) NOTE:NO, PLEASE SEE CONDUCTORS
 STILL DO NOT CORRELATE.
  
 ** PREVIOUS REVIEW NOTE 2ND REVIEW**
 PLEASE SEE RISER AND PANEL "A"
 AS THE OCP FOR THE AHU WAS ADJUSTED AND
 INCREASED TO 30A?S. PLEASE SEE THAT THE
 CONDUCTOR SIZE WAS CHANGED ON THE PANEL
 SCHEDULE, HOWEVER PLEASE SEE RISER
  
 9) NOTE: NO, PLEASE SEE CONTROLS FOR
 SEPARATE SPACES IS NOT BEING SHOWN.
 PLEASE SEE LOCATIONS AT INGRESS/EGRESS
 FOR OVER-RIDES ARE NOT SHOWN ON PLANS AT
 LOCATION WHERE OCCUPANT ENTERS AND EXITS
 AND CAN VISUALLY SEE LIGHTING BEING
 CONTROLLED BY OVER RIDES.
 PLEASE SEE LIGHTING POWER DENSITIES ON
 PLANS/SEPARATLY COULD NOT BE LOCATED.
 PLEASE SEE EACH DEVICE SHOULD BE LISTED
 AND SHOWN ON SYMBOL LEGEND FOR TYPE AND
 AMOUNT OF OVER RIDES TIME.
  
 ** PREVIOUS REVIEW NOTE 2ND REVIEW**
 PLEASE SEE A LIGHTING CONTROL
 PANEL IS BEING SHOWN TO MEET FBC CHAPTER
 13-415.1.ABC.1.1, .1.2, .1.3, HOWEVER
 PLEASE PROVIDE THE OVER-RIDE DEVICES AT
 THIS TIME AND LOCATED IN THE SPACES AS
 REQUIRED.
 PLEASE INDICATE THE DEVICE AND KNOW,
 WHEN USING A TIMED OVER-RIDE (4HRS MAX)
 AND OCCUPANCY SENSOR TYPE DEVICE (30MINS
 MAX). PLEASE SEE AREAS WITH SEPARATE
 SPACES.
 PLEASE ALSO SEE 13-415.1.AB.1, AND
 13-415.2.ABC.1 FOR MAX LIGHTING
 DENSITIES PERMITTED.
 PLEASE SEE BOTH TABLES AND INDICATE.
 PLEASE PROVIDE ALL CONTROLLED CIRCUITING
 ON TIME/PANEL SCHEDULE. PLEASE ALSO
 PROVIDE THE SCHEDULING TIMES.
  
 ** NEW NOTE **
 10) NOTE: PLEASE SEE FS 553.80(2)(B)
 WITH RESPECT TO REPEAT COMMENTS. PLEASE
 KNOW AS PLANS ONLY CMAE IN FOR "PLAN
 REVIEW" FOR THE FIRST REVIEW, PLEASE
 KNOW THE FEE IS NOT ASSESSED AT THIS
 TIME. PLEASE BE SURE ALL COMMENTS ARE
 ADDRESSED AND IF THERE ARE ANY
 QUESTIONS, ONCE AGAIN PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
 ONE SET OF PLANS ARE BEING RETAINED BY
 THIS OFFICE.
  
  
 ** WHEN RESUBMITTING PLANS, PLEASE
 COMPLETELY REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 DPALMER@WPB.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-27 Cont ID  
Sent By dpalmer Date 2006-06-27 Time 09:30 Rev Time 0.00
Received By dpalmer Date 2006-06-27 Time 07:25 Sent To  
Notes
2006-06-27 00:00:00**** PLANS REMOVED FROMHOLD,****
  
 PLEASE SEE PERMIT FEES WERE NOT PAID AND
 REVIEWS ARE ON HOLD.
 CALLED PERMIT PROVIDERS, TO PAY W/IN
 24HRS. SPOKE TO STEVE.
  
 NO REVIEWS WILL BE DONE.
 ******* UNSAT2ND REVIEW *****
  
  
  
 ** PLEASE SEE PLANS ARE NOW SUBMITTED
 FOR PERMIT. PLEASE SEE SOME COMMENTS
 FROM PREVIOUS REVIEW AND SOME NEW
 COMMENTS.
  
 1) NOTE:NO, PLEASE SEE THERE ARE
 PLACES ON PLANS WHICH STILL REFLECT
 OLDER CODES. PLEASE SEE "A" SHEETS, AND
 E-SHEETS. PLEASE SEE NOW THE CHANGES
 MADE ON E-3 NOW CONTAIN BOTH THE
 PREVIOUS AND CURRENT ELECTRICAL CODE.
 PLEASE SEE E-4 WHICH STILL REFLECTS
 SBCCI, SFBC, 1997 LS 101 ETC.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE ADJUST AND REFLECT ALL
 CURRENT CODES IN AFFECT.
 PLEASE SEE WE ARE UNDER THE 2002
 NFPA-70( NEC), 2003 NFPA-101, 2002
 NFPA-72.
 PLEASE KNOW THESE CODES AT A MINIMUM
 SHALL BE REFERENCED ON ARCHITECTURAL AND
 ELECTRICAL/ FIRE PLANS.
 PLEASE SEE PLANS REFLECT 1999 NEC, 1997
 SBC, AND THE SBCCI ETC.
 PLEASE SE COMMENTS FROM OTHER TRADES
 WITH RESPECT TO CODES. (BUILDING).
  
 2) NOTE:NO, PLEASE SEE ONLY THE
 PRINTED NAME AND LICENSE # OF THE
 ARCHITECT WAS ADDED. PLEASE SEE THE FIRM
 TITLE BLOCK IS STILL MISSING THE
 REQUIRED FIRM LICENSE NUMBER WHICH IS
 ALSO KNOWN AS THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
 FS 481.219, FAC 61G1-16.004
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCKS FOR ARCHITECT AND
 ARCHITECTURAL FIRM. PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004 AND
 FLORIDA STATUES 481.219.
 MISSING THE PRINTED NAME AND LICENSE #
 OF THE ARCHITECT, MISSING THE FIRM
 LICENSE # FOR THE ARCHITECTURAL FIRM.
  
 3) NOTE: OK.
  
 4) NOTE:OK, HOWEVER SEE NEW NOTES.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE MINIMUM OCP FOR AHU,
 HEAT. PLEASE SEE MIN OCP IS 125%.
 PLEASE ADJUST.
  
 5) NOTE: OK.
  
 6) NOTE: OK.
  
 7) NOTE: OK
  
 ******** NEW NOTES ******
  
 8) NOTE: PLEASE SEE RISER AND PANEL "A"
 AS THE OCP FOR THE AHU WAS ADJUSTED AND
 INCREASED TO 30A?S. PLEASE SEE THAT THE
 CONDUCTOR SIZE WAS CHANGED ON THE PANEL
 SCHEDULE, HOWEVER PLEASE SEE RISER
  
 9) NOTE: PLEASE SEE A LIGHTING CONTROL
 PANEL IS BEING SHOWN TO MEET FBC CHAPTER
 13-415.1.ABC.1.1, .1.2, .1.3, HOWEVER
 PLEASE PROVIDE THE OVER-RIDE DEVICES AT
 THIS TIME AND LOCATED IN THE SPACES AS
 REQUIRED.
 PLEASE INDICATE THE DEVICE AND KNOW,
 WHEN USING A TIMED OVER-RIDE (4HRS MAX)
 AND OCCUPANCY SENSOR TYPE DEVICE (30MINS
 MAX). PLEASE SEE AREAS WITH SEPARATE
 SPACES.
 PLEASE ALSO SEE 13-415.1.AB.1, AND
 13-415.2.ABC.1 FOR MAX LIGHTING
 DENSITIES PERMITTED.
 PLEASE SEE BOTH TABLES AND INDICATE.
 PLEASE PROVIDE ALL CONTROLLED CIRCUITING
 ON TIME/PANEL SCHEDULE. PLEASE ALSO
 PROVIDE THE SCHEDULING TIMES.
  
 ** WHEN RESUBMITTING PLANS, PLEASE
 COMPLETELY REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 DPALMER@WPB.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-04 Cont ID  
Sent By dpalmer Date 2006-05-04 Time 19:19 Rev Time 0.00
Received By dpalmer Date 2006-05-04 Time 18:03 Sent To  
Notes
2006-05-04 00:00:00IN ELEC FOR REVIEW
 ******** UNSAT **********
  
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW" AND HAVE NOT
 BEEN SUBMITTED FOR PERMIT.
  
 1) NOTE: PLEASE ADJUST AND REFLECT ALL
 CURRENT CODES IN AFFECT.
 PLEASE SEE WE ARE UNDER THE 2002
 NFPA-70( NEC), 2003 NFPA-101, 2002
 NFPA-72.
 PLEASE KNOW,THESE CODES AT A MININUM
 SHALL BE REFERENCED ON ARCHITECTURALS
 AND ELECTRICAL/ FIRE PLANS.
 PLEASE SEE PLANS REFLECT 1999 NEC, 1997
 SBC, THE SBCCI ETC.
 PLEASE SE COMMENTS FROM OTHER TRADES
 WITH RESPECT TO CODES. (BUILDING).
  
 2) NOTE: PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCKS FOR ARCHITECT AND
 ARCHITECTURAL FIRM. PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004 ANF
 FLORIDA STATUES 481.219.
 MISSING THE PRINTED NAME AND LICENSE #
 OF THE ARCHITECT, MISSING THE FIRM
 LICENSE # FOR THE ARCHITECTURAL FIRM.
  
 3) NOTE: PLEASE VERIFY ELECTRICAL PLANS
 WHICH ARE NOTED AS BEING DONE BY A
 PROFESSIONAL ENGINEER, HOWEVER TITLE
 BLOCK REFLECT "MECHANICAL" . PLEASE SEE
 FS 471 FOR WORKING WITHIN SCOPE OF
 LICENSURE. PLEASE CLARIFY.
  
 4) NOTE: PLEASE SEE MININUM OCP FOR AHU,
 HEAT. PLEASE SEE MIN OCP IS 125%.
 PLEASE ADJUST.
  
 5)NOTE: PLEASE SEE 700.12E, WHICH
 REQUIRES THE EM/EXT LTS TO BE CIRCUITED
 TO THE LOCAL LIGHTING BRNACH CIRCUIT IN
 ANY ONE AREA.
 PLEASE SEE AS INDICATED ON PLANS FOR
 LAYOUT, CIRCUITS ETC. IT DOES NOT SEEM,
 PLANS MEET THE EXCEPTION TO USE A
 "LOCK-OFF" DEVICES.
 **PLEASE ALSO KNOW, ANY PROPOSED
 "LOCK-OFF DEVICES" MUST BE APPROVED BY
 THE AHJ. MANY OF THESE DEVICES ARE NOT
 ACCEPTABLE TO THIS AHJ.
  
 6) NOTE: PLEASE LABEL/NOTE COLOR CODING
 FOR 277/480V PER LOCAL AHJ AS BROWN ,
 PURPLE , YELLOW.
  
 7) NOTE: PLEASE SEE MISSIG EQUIPMENT
 GROUNDING CONDUCTOR FROMNEW PANEL "A"
 TO TRANSFORMER.
 250.122,250.110 ETC.
  
 ** WHEN RESUBMITTING PLANS, PLEASE
 COMPLETELY REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2006-10-24 Cont ID  
Sent By rchokshi Date 2006-10-24 Time 08:37 Rev Time 0.00
Received By rchokshi Date 2006-10-24 Time 08:21 Sent To  
Notes
2006-10-24 08:25:18SINCE IT IS ONLY INTERIOR CHANGES, NO ENGINEERING
 REVIEW REQUIRED.RVC

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2006-10-24 Cont ID  
Sent By rchokshi Date 2006-10-23 Time 16:05 Rev Time 0.00
Received By rchokshi Date 2006-10-23 Time 15:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-10-23 Cont ID  
Sent By mwennerg Date 2006-10-23 Time 14:34 Rev Time 0.00
Received By mwennerg Date 2006-10-23 Time 14:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-09-05 Cont ID  
Sent By mwennerg Date 2006-09-05 Time 13:12 Rev Time 0.00
Received By mwennerg Date 2006-09-05 Time 13:12 Sent To  
Notes
2006-09-05 00:00:00***PROVISO***
  
 1) FIRE REVIEW IS OK FOR CODE
 COMPLIANCE. PLEASE SEE ELECTRICAL
 COMMENT (2).
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-07-10 Cont ID  
Sent By mcarsill Date 2006-07-10 Time 15:19 Rev Time 0.00
Received By mcarsill Date 2006-07-10 Time 15:04 Sent To  
Notes
2006-07-10 00:00:001. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 3. SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER OR FIRE ALARM SYSTEM
 REMODEL.
  
 4. NO SOFFITS SHALL INTERFERE WITH THE
 OPERATION OF ANY FIRE SPRINKLER HEADS.
  
 5. INTERIOR FINISH CLASSIFICATIONS SHALL
 COMPLY WITH MINIMUM CODE REQUIREMENTS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-05-31 Cont ID  
Sent By mwennerg Date 2006-05-31 Time 11:06 Rev Time 0.00
Received By mwennerg Date 2006-05-31 Time 11:06 Sent To  
Notes
2006-05-31 00:00:00***DENIED***
  
 1) NOTE REGARDING ADDRESS AT REAR DOOR
 ACKNOWLEDGED. ADDRESS REQUIRED NEAR
 FRONT ENTRANCE DOOR, AND SHALL MEET CODE
 REQUIREMENTS FOR SIZE AND CONTRASTING TO
 BACKGROUND FOR VISIBILITY.
  
 2) DUCT SMOKE DETECTORS WHERE PROVIDED,
 ARE REQUIRED IN SUPPLY DUCT IN SYSTEMS
 GREATER THAN 2000CFM'S AND SHALL
 INITIATE A GENERAL FIRE ALARM IN
 ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 3) IN ADDITION TO FLORIDA FIRE
 PREVENTION CODE, LIFE SAFETY TO COMPLY
 WITH NFPA 101, 2003 EDITION.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL. ANY NEW SOFFITS SHALL NOT
 INTERFERE WITH FIRE SPRINKLER COVERAGE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-12-22 Cont ID  
Sent By adarroug Date 2006-12-22 Time 08:57 Rev Time 0.00
Received By adarroug Date 2006-12-22 Time 08:57 Sent To E
Notes
2006-12-22 08:57:29TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-11-30 Cont ID  
Sent By adarroug Date 2006-11-30 Time 13:25 Rev Time 0.00
Received By adarroug Date 2006-11-30 Time 13:25 Sent To E
Notes
2006-11-30 13:25:52TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status   Date 2006-11-29 Cont ID  
Sent By mmiller Date 2006-11-29 Time 19:47 Rev Time 0.00
Received By mmiller Date 2006-11-29 Time 19:47 Sent To B
Notes
2006-11-29 19:48:06SENT TO JIM'S WITMER DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-09-29 Cont ID  
Sent By adarroug Date 2006-09-29 Time 08:42 Rev Time 0.00
Received By adarroug Date 2006-09-29 Time 08:42 Sent To  
Notes
2006-10-12 17:30:36TO "COMM" BD#54
2006-09-29 00:00:00WAITING FOR "COMM" BD-NEW SHEETS
 SUBMITTED FOR "MECH" AND "F"

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-18 Cont ID  
Sent By adarroug Date 2006-08-18 Time 08:36 Rev Time 0.00
Received By adarroug Date 2006-08-18 Time 08:36 Sent To  
Notes
2006-08-23 00:00:00TO "COMM" BD#40
2006-08-18 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-15 Cont ID  
Sent By adarroug Date 2006-06-15 Time 16:39 Rev Time 0.00
Received By adarroug Date 2006-06-15 Time 16:39 Sent To  
Notes
2006-06-26 00:00:00TO "COMM" BD#21
2006-06-15 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-30 Cont ID  
Sent By adarroug Date 2006-05-30 Time 10:07 Rev Time 0.00
Received By adarroug Date 2006-05-30 Time 10:07 Sent To  
Notes
2006-05-30 00:00:00TO "COMM" BD#23 W/APPL.--CHANGE FROM
 PLAN REV. TO PERMIT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-15 Cont ID  
Sent By adarroug Date 2006-05-30 Time 16:37 Rev Time 0.00
Received By adarroug Date 2006-04-05 Time 14:51 Sent To  
Notes
2006-04-19 00:00:00TO "COMM" BD#23
2006-04-05 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-10-17 Cont ID  
Sent By tgordon Date 2006-10-17 Time 11:17 Rev Time 0.30
Received By tgordon Date 2006-10-17 Time 11:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-08-24 Cont ID  
Sent By tgordon Date 2006-08-24 Time 14:35 Rev Time 0.45
Received By tgordon Date 2006-08-24 Time 14:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-07-18 Cont ID  
Sent By tgordon Date 2006-07-18 Time 11:39 Rev Time 0.20
Received By tgordon Date 2006-07-18 Time 11:39 Sent To  
Notes
2006-07-18 00:00:00*** DENIED ***
 1) PLEASE SEE ELECTRICAL REVIEW NOTE #2
 AND CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-05-10 Cont ID  
Sent By tgordon Date 2006-05-10 Time 12:13 Rev Time 0.30
Received By tgordon Date 2006-05-10 Time 12:13 Sent To  
Notes
2006-05-10 00:00:00** FOR PLAN REVIEW ONLY NOT FOR PERMIT *
 1) SEE ELECTRICAL REVIEW NOTES #1&2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-10-30 Cont ID  
Sent By kstevens Date 2006-10-30 Time 13:45 Rev Time 0.00
Received By kstevens Date 2006-10-30 Time 13:45 Sent To E
Notes
2006-10-30 13:46:33PASSED/PROVISO
  
 SHT P-1 AIR CHAMBERS ARE NOT APPROVED. SECTION 604.9

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-09-05 Cont ID  
Sent By kstevens Date 2006-09-05 Time 09:20 Rev Time 0.00
Received By kstevens Date 2006-09-05 Time 09:20 Sent To  
Notes
2006-09-05 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 **PLUMBING PLANS ACCEPTABLE AT THIS
 TIME. AS SOON AS COMMENT #1 IS RESOLVED,
 THEN PLUMBING WILL BE PASSED.
  
 A. FROM PREVIOUS REVIEW. COMMENT NUMBERS
 TO REMAIN THE SAME FOR CLARITY:
  
 1. ALL SHEETS, THE TITLE BLOCK FOR THE
 ARCHITECT MUST, AT A MINIMUM, CONTAIN
 THE FOLLOWING INFORMATION:
 61G1-16.004(2)(5). THE FIRM LICENSE
 NUMBER, AND A SPACE FOR THE PRINTED NAME
 OF THE PERSON SEALING THE DOCUMENT. FS
 481.219 481.2055.
 ***RESPONSE NOTED, BUT THE CERTIFICATE
 OF AUTHORIZATION, (BUSINESS NUMBER), IS
 NOT SHOWN ON THE TITLE BLOCK.
 ******RESPONSE NOTED, BUT THE
 CERTIFICATE OF AUTHORIZATION FOR "ZAG"
 IS NOT SHOWN.
  
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-07-26 Cont ID  
Sent By kstevens Date 2006-07-26 Time 11:29 Rev Time 0.00
Received By kstevens Date 2006-07-26 Time 11:29 Sent To  
Notes
2006-07-26 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A. FROM PREVIOUS REVIEW. COMMENT NUMBERS
 TO REMAIN THE SAME FOR CLARITY:
  
 1. ALL SHEETS, THE TITLE BLOCK FOR THE
 ARCHITECT MUST, AT A MINIMUM, CONTAIN
 THE FOLLOWING INFORMATION:
 61G1-16.004(2)(5). THE FIRM LICENSE
 NUMBER, AND A SPACE FOR THE PRINTED NAME
 OF THE PERSON SEALING THE DOCUMENT. FS
 481.219 481.2055.
 ***RESPONSE NOTED, BUT THE CERTIFICATE
 OF AUTHORIZATION, (BUSINESS NUMBER), IS
 NOT SHOWN ON THE TITLE BLOCK.
  
 2. SHT A-0 ACCESSIBILITY CODE TO READ
 FBC-2001 CHAPTER 11.
 ***RESPONSE NOTED, BUT MY FAULT, THIS
 SHOULD READ FBC-2004 CHAPTER 11. (SORRY)
  
 3. OK
  
 4. OK
  
 5. OK
  
 6. SUBMIT A DETAIL FOR THE DRINKING
 FOUNTAIN SHOWING COMPLIANCE WITH 11-4.15
 AND ALL SUBSECTIONS, AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING. -
 WALL MOUNTED OR CANTILEVERED UNITS SHALL
 HAVE FORWARD APPROACH CLEAR FLOOR SPACE.
 ***RESPONSE NOTED, BUT PARALLEL APPROACH
 STILL SHOWN AT DETAIL 4. FORWARD
 APPROACH REQUIRED.
  
 7. OK
  
 8. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-05-27 Cont ID  
Sent By kstevens Date 2006-05-27 Time 10:47 Rev Time 0.00
Received By kstevens Date 2006-05-27 Time 11:29 Sent To  
Notes
2006-05-27 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS, THE TITLE BLOCK FOR THE
 ARCHITECT MUST, AT A MINIMUM, CONTAIN
 THE FOLLOWING INFORMATION:
 61G1-16.004(2)(5). THE FIRM LICENSE
 NUMBER, AND A SPACE FOR THE PRINTED NAME
 OF THE PERSON SEALING THE DOCUMENT. FS
 481.219 481.2055.
  
 2. SHT A-0 ACCESSIBILITY CODE TO READ
 FBC-2001 CHAPTER 11.
  
 3. SHT A-3 FINISH PLAN. PLEASE EXPLAIN
 HOW PAINTED WALLS MEETS THE CODE
 REQUIREMENT FOR NONABSORBENT MATERIAL
 PER SECTION 1210.2
  
 4. SHT AC-1 DETAIL 6 - W/C DETAIL. SHOW
 HEIGHT PER SECTION 11-4.16.3.
  
 5. SHT AC-1 DETAIL 3 - LAV CLEARANCE.
 SHOW REQUIREMENTS FOR EXPOSED PIPES AND
 SURFACES PER 11-4.19.4 AND FAUCETS PER
 11-4.19.5.
  
 6. SUBMIT A DETAIL FOR THE DRINKING
 FOUNTAIN SHOWING COMPLIANCE WITH 11-4.15
 AND ALL SUBSECTIONS, AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING. -
 WALL MOUNTED OR CANTILEVERED UNITS SHALL
 HAVE FORWARD APPROACH CLEAR FLOOR SPACE.
  
 7. SHT P-1 SUBMIT MANUF. SPECIFICATIONS
 FOR THE INSTANTANEOUS WATER HEATER.
 LISTING REQUIRED. SECTION 303.4
  
 8. SHT P-1 DETAIL #3 TOILET ROOM WATER
 RISER DIAGRAM. RPZV BACKFLOW SHALL BE
 LOCATED A MAXIMUM 4' ABOVE THE FLOOR FOR
 SERVICING AND CERTIFICATION. INDIRECT
 WASTE RECEPTOR SHALL RECIEVE DISCHARGE
 FROM BACKFLOW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]