| 2006-04-05 00:00:00 | ***********UNSAT ************* |
| | |
| | 1) NOTE:PLEASE ADJUST VALUE FOR |
| | COMPLETE SCOPE OF WORK BEING APPLIED |
| | FOR. PLEASE KNOW, THAT VALUE SHALL BE |
| | ALL LABOR AND MATERIALS EVEN IF |
| | MATERIALS ARE OWNER SUPPLIED. PLEASE SEE |
| | VALUE FOR LABOR AND INSTALLATION IS WAY |
| | LOW FOR SCOPE PF WORK. PLEASE SEE FBC |
| | 2004, ADMINISTRATIVE CODE SECTION 108.3 |
| | AS ADOPTED BY THE CITY OF WEST PALM |
| | BEACH. |
| | |
| | 2) NOTE: PLEASE SEE FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.002 FOR |
| | REQUIRED TITLE BLOCKS REQUIRED ON ALL |
| | SAID SHEETS SIGNED, AND SEALED BY THE |
| | ENGINEER OF RECORD. |
| | TITLE BLOCKS ARE TO BE ON ALL SHEETS. |
| | PLEASE KNOW, THIS COMMENTS IS FOR ALL |
| | TRADES AND FOR ALL REVIEWS WHETHER OR |
| | NOT COMMENT(S) ARE MADE BY OTHER |
| | REVIEWER(S). |
| | |
| | 3) NOTE: PLEASE SEE SPECS SUBMITTED FOR |
| | APS/ ATS DO NOT INDICATE THE REQUIRED |
| | MEANS OF DISCONNECT AS REQUIRED BY |
| | 230.76,230.79,225.31-39. |
| | PLEASE SEE A MANUAL MEANS OF DISCONNECT |
| | COULD NOT BE LOCATED RATED FOR THE LOAD |
| | SERVED ON THE OUTSIDE OF EQUIPMENT |
| | SUBMITTED. |
| | |
| | 4) NOTE: PLEASE CORRELATE SPECS/ |
| | MANUFACTURES CUT SHEETS AND PLANS. |
| | PLEASE SEE ONE SHOWS 3000A AND THE |
| | 3200A'S, ARE THESE THE SAME?AS MANY |
| | LOCATIONS ON PLANS MENTIONS 3000A'S. |
| | 215.5 |
| | |
| | 5) NOTE: PLEASE CLARIFY WHY THE NEW MAIN |
| | AND OCP52 MUT IS MENTIONED AS BEING |
| | SET ABOVE EXISTING MAINS. PLEASE CLARIFY |
| | AS THIS EQUIPMENT IS NOW BECOMING THE |
| | NEW SERVICE MAIN(S) AND SHOULD BE |
| | PROVIDING THE MAX OCP FOR EACH OF THE |
| | EXISTING MAINS AND CONDUCTORS. |
| | 215.5,240.4,,310.16 ETC |
| | |
| | 6) NOTE: PLEASE SEE LOADS PROVIDED ON |
| | LOAD SUMMARY FROM THE 12 MONTH READING |
| | INDICATES A LOAD HIGHER THAN THE MAX |
| | RATING OD SAID GENERATOR. PLEASE PROVIDE |
| | LOAD SHEDDING DETAIL FOR LOADS TO BE |
| | SHEDDED AND THE NEW LOADS INTENDED ONCE |
| | THE MININUM DE-RATING HAS TAKEN PLACE. |
| | 215.5,702.5,220.35 |
| | |
| | 7) NOTE:PLEASE SEE PLANS SHALL |
| | INDICATE THE CURRENT CODES IN EFFECT FOR |
| | INSTALLATION AS FOLLOWS. |
| | 2002 NFPA-70, 2002 NFPA-110. |
| | |
| | 8) NOTE: PLEASE SPECIFY IF GENERATOR IS |
| | A SEPARATELY DERIVED SYSTEM OR NOT. |
| | PLEASE SEE E-2 WHICH LENDS TO THE GEN |
| | WINDINGS BEING TAPPED FOR NEW GROUNDING |
| | ELECTRODE SYSTEM AND GROUNDING DETAIL ON |
| | E-5 DOES NOT INDICATE AS A NEW GROUNDING |
| | ELECTRODE SYSTEM. |
| | THE SPEC FOR THE APS/ ATS DO NOT SEEM TO |
| | INDICATE THE SWITCHING OF THE GROUNDED/ |
| | NEUTRAL CONDUCTOR. |
| | 250.30, 250.24 ETC. |
| | |
| | 9) NOTE: PLEASE SEE THE APS/ATS IS |
| | BECOMING THE NEW FIRST MEANS OF |
| | DISCONNECT HOWEVER THE NEW GROUNDING |
| | ELECTRODE SYSTEMS DOE NOTE SEEM TO |
| | COMPLETE AS PER 250.50. |
| | PLEASE SEE GROUNDING DETAIL MENTIONS NEW |
| | SLAB STEEL WHICH IS OK, HOWEVER DOES NOT |
| | INDICATE A MIN OF 20' IN DIRECT CONTACT |
| | WITH THE EARTH. |
| | PLEASE KNOW, THE SLABS BEING POURED AS |
| | MENTIONED TO THIS OFFICE ARE BEING |
| | INSTALLED OVE RTHE EXISTING SITE |
| | SLAB/CONCRETE PARKING/ BACK OF BLDG |
| | AREA. |
| | THESE NEW SLAB/STEEL ATTACHMENTS DO NOT |
| | MEET THE MIN REQUIREMENTS. PER |
| | 250.50,250.52, 250.104 |
| | IF SLAB STEEL IS ONLY BEING BONDED , |
| | THEN PLEASE INDICATE. |
| | PLEASE COMPLETE GROUNDING ELECTRODE |
| | SYSTEM(S) AND BONDING FOR ALL AS ABOVE. |
| | |
| | 10) NOTE: PLEASE SEE FEEDER CONDUITS, |
| | NEW AND EXISTING. THERE IS NOW A CHANGE |
| | IN CONDUCTOR SIZES FORTHE GROUNDED |
| | NEUTRAL CONDUCTOR. PLEASE PROVIDE LOAD |
| | CALCS FOR NEW DOWN SIZING OR INSTALL AS |
| | SHOWN ON ORIG WITH FULL SIZE NEUTRAL. |
| | 220.22, 215.5 |
| | |
| | 11) NOTE: PLEASE CORRELATE ALL CONDUITS, |
| | FEEDERS AND SERVICE ENTRANCE CONDUITS. |
| | PLEASE SEE THE NUMBER OF CONDUITS FOR 6A |
| | AND 6B ARE DIFFERENET ON MORE THAN ONE |
| | SHEET. PLEASE SEE 6A IS SHOWN AS 5 |
| | SETS,6 SETS AND 7 SETS, AS WELL AS 6B |
| | BEING SHOWN AS 4 SETS AND 6 SETS. |
| | PLEASE VERIFY ALL OF THESE AS IT DOES |
| | SEEM THAT THE NUMBER OF CONDUITS TO THE |
| | EXISTING SERVICE WOULD BE INCREASED. |
| | 215.5 |
| | |
| | 12) NOTE: PLEASE SEE SETS OF CONDUITS |
| | AND FEEDERS DOD NOT SEEM TO INDICATE |
| | THEW NEW REQUIRED "EQUIPMENT GROUNDING |
| | CONDUCTOR" TO TEH EXISITING MAINS. THESE |
| | ARE NO LONGER THE FIRST MENAS OF |
| | DISCONNECT AND THE GROUNDING |
| | DETAIL/RISER ON E-5 MENTIONS THE |
| | DISCONNECT OF THE BONDING JUMPER, |
| | HOWEVER THE CONDUITS/FEEDERS DONOT |
| | SHOW THE EQUIPMENT GROUNDING CONDUCTORS |
| | PER 250.110,250.122,250.24B |
| | 215.5 |
| | |
| | 13) NOTE: PLEASE INDICATE OCP AT |
| | GENERATOR. PLEASE ALSO SEE 445.13 FOR |
| | MIN SIZING WHICH MAY BE AFFECTED. |
| | CONDUCTORS AT 115%? |
| | |
| | 14) NOTE: PLEASE SEE LEGEND ON E-3 WHICH |
| | MENTIONS THE "PINK HIGH-LIGHTED LINES" |
| | AS WIRING BY OTHERS", HOWEVER PLEASE SEE |
| | 4.1 WHICH SHOWS THIS SAME HIGH-LIGHTED |
| | LINE AS A FENCE BY OTHERS? |
| | 215.5 |
| | |
| | 15) NOTE: PLEASE SEE NOTE #4 ON E-1, |
| | WHICH MENTIONS "STANDY" MODE, THIS SEEMS |
| | TO BE A MISPRINT FOR THE INTENDED |
| | "STAND-BY" MODE". |
| | 215.5 |
| | |
| | 16) NOTE:PLEASE SUBMIT A MIN OF TWO |
| | COPIES FOR ALL PLANS SPECS. IF THREE ARE |
| | DESIRED TO BE STAMPED, PLEASE SUBMIT |
| | THREE COMPLETE SETS. |
| | PLEASE BE SURE TO REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO THE COMPLETED SETS FOR |
| | REVIEW AND STAMPING BEFORE RESUBMITTING. |
| | PLANS. |
| | |
| | 17) NOTE: PLEASE KNOW, IT IS KNOWN TO |
| | THIS OFFICE THAT THERE IS AN EXISTING |
| | GENERATOR AT THIS STORE LOCATION, |
| | HOWEVER NO INFORMATION FOR THIS IS |
| | INDICATED. PLEASE SHOW LOCATION AND HOW |
| | THIS SYSTEM IS OR IS NOT TIED INTO THE |
| | NEW SERVICE. |
| | 215.5 |
| | |
| | 18) NOTE: PLEASE PROVIDE THE GPH USEAGE |
| | OF GENERATOR FOR LOADS INTENDED. PLEASE |
| | KNOW, A 1000 GAL TANK IS BEING SHOWN, |
| | WHICH LENDS TO LESS THAN 24HRS OF |
| | OPERTATION? IS THIS CORRECT? |
| | THIS IS ONLY A NOTE,AS AN OPTIONAL |
| | STAND-BY LEVEL 2 SYSTEMS DOES NOT |
| | REQUIRED ANY MIN HRS OF OPERATION. |
| | |
| | |
| | *** PLEASE SEE ANY COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |