| 2006-05-04 00:00:00 | ********* UNSAT ********** |
| | |
| | 1) NOTE: PLEASE SUBMIT INFORMATION ON |
| | EXISTING OR NEW ELECTRICAL CONNECTTIONS. |
| | IS THERE GOING TO BE A NEW FIRE PUMP |
| | CONTROLLER? |
| | PLEASE SUBMIT ELECTRICAL INFORMATION FOR |
| | EITHER TO CORRELATE WITH NEW PUMP FOR |
| | LOCKED ROTOR CURRENT, NEMA 2,ETC. |
| | NFPA-70 695, NFPA-20 CHAPTER 7 |
| | |
| | 2)NOTE: PLEASE SEE LOCATION OF FIRE PUMP |
| | IS BEING NOTED AS BEING LOCATED IN THE |
| | POOL EQUIPMENT ROOM? |
| | PLEASE KNOW, THIS DOES NOT SEEIT WILL |
| | BE PERMITTED TO GO BACK TO LOCATION AS |
| | SHOWN.UNLESS IDENTIFIED FOR USE IN THE |
| | OPERATING ENVIRONMENT, NO CONDUCTORS OR |
| | EQUIPMENT SHALL BE LOCATED IN DAMP OR |
| | WET LOCATIONS; WHERE EXPOSED TO GASES, |
| | FUMES, VAPORS, LIQUIDS, OR OTHER AGENTS |
| | THAT HAVE A DETERIORATING EFFECT ON THE |
| | CONDUCTORS OR EQUIPMENT; OR WHERE |
| | EXPOSED TO EXCESSIVE TEMPERATURES. |
| | PLEASE SEE NFPA-20 CHAPTER 7 FOR |
| | INSTALLATION. NFPA-70 110.11 |
| | PLEASE SEE THERE ARE MANY LOCATIONS IN |
| | CHAPTER 7 WHICH APPLIES. |
| | |
| | 3) NOTE: PLEASE SEE MISSING THE SPECS |
| | FOR THE FIRE PUMP CONTROLLER AND FIRE |
| | PUMP. |
| | IF ONLY THE FIRE PUMP IS BEING CHANGED, |
| | PELASE INDICATE THE FIRE PUMP CONTROLLER |
| | AND IS LISTED WITH THE FIRE PUMP BEING |
| | INSTALLED. PLEAS EKNOW, ALL MUST HAVE |
| | LISTED COMPONENTS AND LISTED FOR THE |
| | USE/ ASSEMBLY.110.3 |
| | |
| | 4) NOTE: PLEASE SEE TITLE BLOCK FOR WHAT |
| | APPEARS TO BE A FIRM AS THE PE IS LISTED |
| | IN THE SAME TITLE BLOCK.? |
| | PLEASE KNOW, IF THIS IS SO, PLEASE |
| | INDICATE THE MISSING CERTIFICATE OF |
| | AUTHORIZATION # AS REQUIRED PER FS |
| | 471.023, FAC 61G15-23.002 |
| | PLEASE KNOW, IF NOT PLEASE INDICATE THE |
| | PE'S TITLE BLCO SEPARATE AND PLEASE BE |
| | SURE ALL INFORMATION ON SAID TITLE BLOCK |
| | IS CLEAR AND VISABLE. |
| | PLEASE SEE TITLE BLOCK IS VERY SMALL AND |
| | INFORMATION ISUNREADABLE. |
| | |
| | 5) NOTE: PLEASE SEE AS PER THE FIRE |
| | SAFETY EVALUATION REPORT AND THE EXECUTE |
| | ORDER AS SO NOTED; ALL STRUCTURAL FIRE |
| | RATED WALL AND COMPONENTS SHALL BE DONE |
| | BY A LICENSED CONTRACTOR AND IS NOT IN |
| | THE SCOPE OF WORK FOR THIE PERMIT |
| | PACKAGE. |
| | PLEASE SEE FBC ADMISTRATIVE SECTION |
| | 105.1 AND 105.2 |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |