Plan Review Details - Permit 06040045
Plan Review Stops For Permit 06040045
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-07-13 Cont ID  
Sent By lmartine Date 2006-07-13 Time 13:36 Rev Time 0.00
Received By lmartine Date 2006-07-13 Time 13:36 Sent To  
Notes
2006-07-13 00:00:002 HR WALL SEPERATING POOL EQUIPMENT FROM
 PUMP ROOM
  
  
 OK LM

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-07-26 Cont ID  
Sent By dpalmer Date 2006-07-26 Time 17:59 Rev Time 0.00
Received By dpalmer Date 2006-07-26 Time 16:50 Sent To FIRE
Notes
2006-07-26 00:00:00OK TO ISSUE PERMIT ONCE FIRE REVIEWS.
 WILL REQUIRE A SEPARATE ELELCTRICAL
 PERMIT FOR ANY ELECTRICAL WORK FOR
 CHANGE OUT OF FPC AND/OR FP.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-16 Cont ID  
Sent By dpalmer Date 2006-06-16 Time 12:49 Rev Time 0.00
Received By dpalmer Date 2006-06-16 Time 10:45 Sent To FIRE
Notes
2006-06-16 00:00:00**** UNSAT 2ND REVIEW *****
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES DUE TO PLANS
 SUBMITTED.
  
 1) NOTE:PLEASE SEE NOTE WITH RESPECT
 LISITNG OF CONTROLLER AS IT APPEARS
 EXISTING CONTROLLER WILL NEED TO BE
 CHANGED AND THE INFORMATION AS STATED IN
 NOTE ONE BELOEW FROM PREVIOUS REVIEW
 WILL BE IN NEED OF BEING ADDRESS.
 215.5
  
 ** PREVIOUS NOTE **
 PLEASE SUBMIT INFORMATION ON
 EXISTING OR NEW ELECTRICAL CONNECTTIONS.
 IS THERE GOING TO BE A NEW FIRE PUMP
 CONTROLLER?
 PLEASE SUBMIT ELECTRICAL INFORMATION FOR
 EITHER TO CORRELATE WITH NEW PUMP FOR
 LOCKED ROTOR CURRENT, NEMA 2,ETC.
 NFPA-70 695, NFPA-20 CHAPTER 7
  
 2)NOTE: PLEAS KNOW, THE PLAN SUBMITTED
 FOR NEW SEPARATION WILL BE REVIEWED BY
 THE BUIDLIG REVIEWER.
  
 3) NOTE: PLEASE SEE RESPONSE MENTIONS A
 NEW FIRE PUMP AND THE SPECS SUBMITTED
 WERE FOR AN EXISTING FIRE PUMP
 CONTROLLER WHICH IS NOT LISTED FOR USE
 WITH THE NEW PUMP. PLEASE SEE IT MAY BE
 LISTED FOR A 50HP PUMP, HOWEVER THESE
 ARE LISTED COMPONETS AND SHALL BE A
 LISTED ASSMENBLEY AS LOCKED ROTOR OCP,
 CURRENT RATIGS ETC FROM A FIRE PUMP
 CONTROLLER IS BASED ON THE MOTOR WHICH
 IT IS LISTED WITH . IE: CODE LETTER, EFF
 RATINGS ETC.
  
 ** PREVIOUS NOTE **
 PLEASE SEE MISSING THE SPECS
 FOR THE FIRE PUMP CONTROLLER AND FIRE
 PUMP.
 IF ONLY THE FIRE PUMP IS BEING CHANGED,
 PELASE INDICATE THE FIRE PUMP CONTROLLER
 AND IS LISTED WITH THE FIRE PUMP BEING
 INSTALLED. PLEAS EKNOW, ALL MUST HAVE
 LISTED COMPONENTS AND LISTED FOR THE
 USE/ ASSEMBLY.110.3
  
 4) NOTE:OK.
  
 5) NOTE: OK, CONTRACTOR WILL BE REQUIRED
 TO APPLY FOR THE PERMIT FOR WALL.
  
 ** NEW NOTES **
  
 6) NOTE: PLEASE SUBMIT TWO COMPLETE NEW
 SETS FOR REVIEW AND STAMPING. PLEASE SEE
 OF THE SETS SUBMITTED, ONE SET IS OLD
 AND ONE SET IS NEW. PLEASE SUBMIT TWO
 COMPLETE NEW SETS FOR REVIEW AND
 STAMPING.
 FBC ADMIN SECT 106.1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-04 Cont ID  
Sent By dpalmer Date 2006-05-04 Time 19:57 Rev Time 0.00
Received By dpalmer Date 2006-05-04 Time 19:29 Sent To FIRE
Notes
2006-05-04 00:00:00********* UNSAT **********
  
 1) NOTE: PLEASE SUBMIT INFORMATION ON
 EXISTING OR NEW ELECTRICAL CONNECTTIONS.
 IS THERE GOING TO BE A NEW FIRE PUMP
 CONTROLLER?
 PLEASE SUBMIT ELECTRICAL INFORMATION FOR
 EITHER TO CORRELATE WITH NEW PUMP FOR
 LOCKED ROTOR CURRENT, NEMA 2,ETC.
 NFPA-70 695, NFPA-20 CHAPTER 7
  
 2)NOTE: PLEASE SEE LOCATION OF FIRE PUMP
 IS BEING NOTED AS BEING LOCATED IN THE
 POOL EQUIPMENT ROOM?
 PLEASE KNOW, THIS DOES NOT SEEIT WILL
 BE PERMITTED TO GO BACK TO LOCATION AS
 SHOWN.UNLESS IDENTIFIED FOR USE IN THE
 OPERATING ENVIRONMENT, NO CONDUCTORS OR
 EQUIPMENT SHALL BE LOCATED IN DAMP OR
 WET LOCATIONS; WHERE EXPOSED TO GASES,
 FUMES, VAPORS, LIQUIDS, OR OTHER AGENTS
 THAT HAVE A DETERIORATING EFFECT ON THE
 CONDUCTORS OR EQUIPMENT; OR WHERE
 EXPOSED TO EXCESSIVE TEMPERATURES.
 PLEASE SEE NFPA-20 CHAPTER 7 FOR
 INSTALLATION. NFPA-70 110.11
 PLEASE SEE THERE ARE MANY LOCATIONS IN
 CHAPTER 7 WHICH APPLIES.
  
 3) NOTE: PLEASE SEE MISSING THE SPECS
 FOR THE FIRE PUMP CONTROLLER AND FIRE
 PUMP.
 IF ONLY THE FIRE PUMP IS BEING CHANGED,
 PELASE INDICATE THE FIRE PUMP CONTROLLER
 AND IS LISTED WITH THE FIRE PUMP BEING
 INSTALLED. PLEAS EKNOW, ALL MUST HAVE
 LISTED COMPONENTS AND LISTED FOR THE
 USE/ ASSEMBLY.110.3
  
 4) NOTE: PLEASE SEE TITLE BLOCK FOR WHAT
 APPEARS TO BE A FIRM AS THE PE IS LISTED
 IN THE SAME TITLE BLOCK.?
 PLEASE KNOW, IF THIS IS SO, PLEASE
 INDICATE THE MISSING CERTIFICATE OF
 AUTHORIZATION # AS REQUIRED PER FS
 471.023, FAC 61G15-23.002
 PLEASE KNOW, IF NOT PLEASE INDICATE THE
 PE'S TITLE BLCO SEPARATE AND PLEASE BE
 SURE ALL INFORMATION ON SAID TITLE BLOCK
 IS CLEAR AND VISABLE.
 PLEASE SEE TITLE BLOCK IS VERY SMALL AND
 INFORMATION ISUNREADABLE.
  
 5) NOTE: PLEASE SEE AS PER THE FIRE
 SAFETY EVALUATION REPORT AND THE EXECUTE
 ORDER AS SO NOTED; ALL STRUCTURAL FIRE
 RATED WALL AND COMPONENTS SHALL BE DONE
 BY A LICENSED CONTRACTOR AND IS NOT IN
 THE SCOPE OF WORK FOR THIE PERMIT
 PACKAGE.
 PLEASE SEE FBC ADMISTRATIVE SECTION
 105.1 AND 105.2
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-08-04 Cont ID  
Sent By mawillia Date 2006-08-04 Time 10:54 Rev Time 0.00
Received By mawillia Date 2006-08-04 Time 09:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-07-13 Cont ID  
Sent By mwennerg Date 2006-07-13 Time 09:44 Rev Time 0.00
Received By mwennerg Date 2006-07-13 Time 09:44 Sent To B
Notes
2006-07-13 00:00:00***DENIED***
  
 PLEASE SEE NOTES FROM LAST FIRE REVIEW.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-05-05 Cont ID  
Sent By mwennerg Date 2006-05-05 Time 13:55 Rev Time 0.00
Received By mwennerg Date 2006-05-05 Time 13:55 Sent To  
Notes
2006-05-05 00:00:00******PROVISO******
  
 1) FIRE SPRINKLER LAYOUT OK. PLEASE SEE
 ELECTRICAL REVIEW COMMENTS AND PROVIDE
 AS NECESSARY.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-24 Cont ID  
Sent By adarroug Date 2006-07-24 Time 10:52 Rev Time 0.00
Received By adarroug Date 2006-07-24 Time 10:52 Sent To E
Notes
2006-07-24 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-08 Cont ID  
Sent By adarroug Date 2006-06-08 Time 17:43 Rev Time 0.00
Received By adarroug Date 2006-06-08 Time 17:43 Sent To E
Notes
2006-06-08 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-08 Cont ID  
Sent By adarroug Date 2006-05-05 Time 17:42 Rev Time 0.00
Received By adarroug Date 2006-04-04 Time 13:12 Sent To  
Notes
2006-04-04 00:00:00TO "F" BOX