Plan Review Details - Permit 06031571
Plan Review Stops For Permit 06031571
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-12-07 Cont ID  
Sent By mjacobs Date 2007-12-07 Time 10:46 Rev Time 0.00
Received By mjacobs Date 2007-12-07 Time 07:48 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-07-11 Cont ID  
Sent By mjacobs Date 2007-07-11 Time 05:53 Rev Time 0.00
Received By mjacobs Date 2007-07-10 Time 12:21 Sent To P
Notes
2007-07-10 13:13:45BUILDING PLAN REVIEW
 PERMIT: 06031571
 ADD: 3008 RIDGEWAY AVE
 CONT: T&S CONSTRUCTION INC.
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:REV.
 ACTION: DENIED
  
 1) THE DRAWINGS SHALL BE SIGNED/DATEDAND SEAL BY THE
 ENGINEER OF RECORD. THE ONLY PERSON WHO CAN MAKE
 CHANGES TO THE DRAWINGS IS THE ENGINEER OF RECORD. THE
 DRAWINGS SUBMITTED ARE NOT SIGNED BY THE ENGINEER OF
 RECORD.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-10-19 Cont ID  
Sent By alange Date 2006-10-19 Time 13:16 Rev Time 0.00
Received By alange Date 2006-10-19 Time 11:26 Sent To  
Notes
2006-10-19 13:20:32SEPERATE PERMIT REQUIRED FOR FLAT ROOF.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-10 Cont ID  
Sent By alange Date 2006-07-10 Time 11:01 Rev Time 1.25
Received By alange Date 2006-07-10 Time 10:53 Sent To  
Notes
2006-07-10 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-18 Cont ID  
Sent By alange Date 2006-04-18 Time 09:47 Rev Time 2.50
Received By alange Date 2006-04-18 Time 09:47 Sent To  
Notes
2006-04-18 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUE HAS BEEN REVISED TO
 $21,765.ADDITIONAL PERMIT FEES ARE
 DUE.
  
 4.SQUARE FOOTAGE ON APPLICATION HAS
 BEEN CORRECTED.
  
 5.SUBMIT TWO COMPLETE SETS OF PRODUCT
 APPROVALS WITH QUALITYA ASSURANCE AND
 THE FOLLOWING STATE PRODUCT APPROVAL
 ATTACHED.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 9.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2005 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.ALSO UPDATE ANY
 CODE SECTIONS SHOWN
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-11-19 Cont ID  
Sent By dpalmer Date 2007-11-19 Time 10:41 Rev Time 0.00
Received By dpalmer Date 2007-11-19 Time 09:48 Sent To M
Notes
2007-11-19 10:43:38REDLINED PLANS.
 SD'S ARE SA FOR SMOKE ALARMS.
 CLOSET LIGHTS ARE TO MEET 410.8

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-07-30 Cont ID  
Sent By dpalmer Date 2007-07-30 Time 11:07 Rev Time 0.00
Received By dpalmer Date 2007-07-30 Time 10:40 Sent To M
Notes
2007-07-30 11:07:16 
 *** UNSAT ***
  
 1) NOTE: PLEASE SEE THAT THE DESIGNER OF RECORD SHALL
 SIGN PLANS. IF THE DESIGNER OF RECORD HAS CHANGED
 PLEASE SUBMIT NOTARIZED LETTERS FOR CHANGE OF
 DESIGNER.
 FBC 106.1.2
 FS 481, 471, 489
  
 2) NOTE: PLEASE SHOW A REVISED ELECTRICAL RISER
 DIAGRAM. PLEASE INCLUDE THE EQUIPMENT GROUNDING
 CONDUCTOR TO NEW SUB PANEL.
 PLEASE SEE 250.122, 250.110 ETC.
  
 3) NOTE: PLEASE SUBMIT A LAYOUT OF THE NEW SMOKE ALARMS
 IN DWELLING INSIDE AND OUTSIDE SLEEPING ROOMS.
 R313, NFPA-72 11.5.1.1, 11.8.3
 PLEASE SHOW LOCATIONS.
  
 4) NOTE: PLEASE SPECIFY NEW LIGHTS IN CLOSET AS THE
 SYMBOL/FIXTURE LEGEND DOES NOT CORRELATE OR INDICATE
 TYPE OF FIXTURE. BASED ON SCALE ON PLANS AND LOCATIONS,
 IT NOT APPEAR 410.8 IS MET?
  
 5) NOTE: PLEASE SEE PLANS NOW INCLUDE THE RELOCATED CU
 YET NOT GFI IS SHOWN FOR THIS AS REQUIRED PER 210.63,
 210.8A
  
 6) NOTE: PLEASE REVISE LOAD CALCULATIONS TO COORDINATE
 WITH PANEL SCHEDULE. SEE KITCHEN SMALL APPLIANCE
 CIRCUITS FOR EXAMPLE.
 PLEASE SEE 210.52B1, 210.11C1, 220.16.
  
 7) NOTE: PLEASE SEE REDLINED PLANS AS OF OCT 06
 REQUIRED THE PANEL SCHEDULE TO BE REVISED TO BE
 SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED.
 *PLEASE SEE 408.4. *SECTION 408.4 WAS REVISED FOR THE
 2005 CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
  
  
 * PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-10-17 Cont ID  
Sent By dpalmer Date 2006-10-17 Time 17:59 Rev Time 0.00
Received By dpalmer Date 2006-10-17 Time 17:59 Sent To B
Notes
2006-10-17 17:59:21**REDLINED FOR PANEL SCHEDULE TO BE UPDATED TO
 CORRELATE OCP / LOADS AND CONDUCTOR SIZES.
 240.4,310.16, 408.4

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-21 Cont ID  
Sent By dpalmer Date 2006-06-21 Time 18:01 Rev Time 0.00
Received By dpalmer Date 2006-06-21 Time 16:53 Sent To M
Notes
2006-06-21 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE THE RECEPT FOR NEW
 WASHER IS NOT SHOWN ON PLANS. PANEL
 SCHEDULE ETC SHOWS NEW , HOWEVER NOT
 SHOWN.
 PLEASE CORRELATE.
 215.5
  
 2) NOTE: PLEASE SEE PANEL SCHEDULE SHOWS
 40A OCP FOR THE RANGE WHICH IS BEING
 SHOWN AS 12KW. PLEASE KNOW, WITH THE
 LOAD SHOWN AS 12KW, THE 40A CIRUIT AS
 SHOWN EXCEEDS SAFE OPERATION AND OCP FOR
 PROTECTION OF BRANCH CIRCUIT.
 240.4,310.16.ETC.
 PLEASE VERIFY AND ADJUST.
  
 3) NOTE: PLEASE SEE BATH RECEPTS SHALL
 BE GFI/ GFI PROTECTED PER 210.8A1
  
 4) NOTE: PLEASE CORRELATE WATER HEATER
 SHOWN ON PANEL SCHEDULE AND KW RATING ON
 LOAD CALCULATIONS.
 PLEASE SEE ONE SHOWS 4.5 KW AND THE
 OTHER SHOWS 3KW?
 PLEASE BE SURE TO SEE IF THE KW IS
 4500VA, THEN PLEASE ADJUST OCP AND AWG
 SIZES. PER 240.4,310.16 ETC
 215.5
  
 5) NOTE: PLEASE VERIFY CIRCUITING AS
 SHOWN. PLEASE SEE MAX VA PERMITTED ON
 #14AWG AND 15A OCP. PLEASE SEE A MAX OF
 1440VA.
 215.5. PLEASE SEE OTHER CIRCUITS.
  
 6) NOTE: PLEASE SEE NEC 2002 FOR CORRECT
 LOAD CALCULATIONS. PLEASE SEE SOME
 APPEAR TO BE SHOWN FOR COMMERCIAL AND
 SOME FOR RESIDENTIAL??
  
 7) NOTE: PLEASE SEE A LIGHTING CONTROL
 SWITCH WILL BE REQUIRED IN THE PATH OF
 EGRESS WHEN ENTERING THE LAUNDRY RM.
 PLEASE SEE A 3-WAY SW MAY BE USED TO ADD
 TO THE OTHER SW AS SHOWN.
 PLEASE KNOW, THE SWITCHING SHOULD BE
 LOCATED IN THE PATH OF EGRESS AND ALWAYS
 WITH THE DIRECTION OF EGRESS TRAVEL.
 210.70, 2002 NEC, NFPA-101 CHAPT 24,
 CHAPT 8 7.8
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER TRADES WHICH MAY AFFETC THE
 ELECTRICAL PLANS.
  
 ** PLEASE BE SURE PLANS REFLECT THE
 CURRENT CODES IN EFFECT 2004 FBC , 2002
 NEC AT A MIN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-11 Cont ID  
Sent By dpalmer Date 2006-04-11 Time 07:49 Rev Time 0.00
Received By dpalmer Date 2006-04-11 Time 07:17 Sent To M
Notes
2006-04-11 00:00:00************ UNSAT *****************
  
 1) NOTE: PLEASE SEE PLAN SETS CONTAIN
 MANY AREAS ON ELECTRICLA AND OTHER
 SHEETS WHICH CONTAIN "HAND-DRAWN" ITEMS
 ON PLANS WHICH ARE SIGNED, DATED AND
 SEALED BY AN ENGINEER. PLEASE SEE FS
 471.025, THIS IS NOT PERMITTED AND WILL
 NOT BE ACCEPTED. PLEASE HAVE SHEETS
 RE-PRINT WITH CHANGES AND ANY
 CORRECTIONS FROM PLAN REVIEW COMMENTS.
 215.5
 ** PLEASE KNOW, THIS COMMENTS IS FOR ALL
 SHEETS AND FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 2) NOTE: PLEASE SEE RISER MENTIONS NEW
 #10 FOR DRYER AND WATER HEATER, HOWEVER
 PLEASE SEE THE "BRIEF" PANEL SCHEDULE
 PROVODED DOES NOT CORRELATE WITH THIS.
 ALL CIRCUITS ON THE 4 CIRCUIT SCHEDULE
 SHOWS ONLY 1-POLE 20A CIRCUITS???
  
 A) PLEASE SEE 220.18 FOR MIN KW AND
 CIRCUIT RATING FOR DRYER.
 240.4,310.16
  
 B) PLEASE SEE 422.13 FOR MIN SIZE AND
 OCP FOR WATER HEATER, 125% FOR
 NAMEPLATE.
  
 PLEAS ADJUST CONDUCTOR AND OCP SIZES.
  
 3) NOTE: PLEASE VERIFY ON PLANS IF NEW
 LOADS ARE TAKING THE PLACE OF THE
 EXISTING WASHER, DRYER, WATER HEATER OR
 ARE THESE NEW ADDTIONAL LOADS.
 PLEASE PROVIDE MIN LOAD CALCUALTIONS FOR
 NEW ADDED LOADS.
 215.5,220
  
 4) NOTE: PLEASE SEE WATER HEATER IS
 BEING SHOWN WITH A RECEPT FOR
 DISCONNECT/PLUG IN OF UNIT. PLEASE SEE
 422.30 AS A DISCONNECTING MEANS IS
 REQUIRED AND MAY NOT PLUG IN UNIT.
  
 5) NOTE: PELASE INCLUDE ANY NEW GFI
 RECEPTS ON PLANS (PRINTED) NOT DRAWN.
 210.52D, 210.8A1,3 ETC.
  
 6) NOTE: PLEASE SEE ELECTRICAL SYMBOL
 LEGEND, SHOWS 125A PANELAND RISER AND
 PLANS MENTIONS 200A PANEL EXISTING?
 PLEASE CORRELATE
  
 7) NOTE: PLEASE SEE FBC R313, FOR SD'S
 TO BE ADDED TO THE EXISTING DWELLING FOR
 THE LEVEL OF ALTERATION TO THE EXISTING
 BUILDING.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-11-08 Cont ID  
Sent By adarroug Date 2007-11-08 Time 14:11 Rev Time 0.00
Received By adarroug Date 2007-11-08 Time 14:11 Sent To Z
Notes
2007-11-08 14:11:36TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-07-05 Cont ID  
Sent By adarroug Date 2007-07-05 Time 14:14 Rev Time 0.00
Received By adarroug Date 2007-07-05 Time 14:14 Sent To E
Notes
2007-07-05 14:15:14TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-10-14 Cont ID  
Sent By adarroug Date 2006-10-14 Time 16:54 Rev Time 0.00
Received By adarroug Date 2006-10-14 Time 16:54 Sent To E
Notes
2006-10-14 16:54:59TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-20 Cont ID  
Sent By adarroug Date 2006-06-20 Time 09:38 Rev Time 0.00
Received By adarroug Date 2006-06-20 Time 09:38 Sent To E
Notes
2006-06-20 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-10 Cont ID  
Sent By adarroug Date 2006-04-10 Time 16:13 Rev Time 0.00
Received By adarroug Date 2006-04-10 Time 16:13 Sent To E
Notes
2006-04-10 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-18 Cont ID  
Sent By alange Date 2006-04-18 Time 09:47 Rev Time 0.00
Received By alange Date 2006-04-03 Time 11:28 Sent To  
Notes
2006-04-03 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-11-26 Cont ID  
Sent By tgordon Date 2007-11-26 Time 09:40 Rev Time 0.30
Received By tgordon Date 2007-11-26 Time 09:40 Sent To P
Notes
2007-11-26 09:43:21MECHANICAL REVISION
  
 *** PROVISO ***
 1) THE CLOTHES DRYER VENT TERMINATION MAY NOT DISCHARGE
 NEAR THE A/C CONDENSER UNIT, SEE 2004 FBC/M 501.2 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-07-30 Cont ID  
Sent By tgordon Date 2007-07-30 Time 11:52 Rev Time 0.30
Received By tgordon Date 2007-07-30 Time 11:52 Sent To  
Notes
2007-07-30 12:05:02*** DENIED ***
 1) THE CLOTHES DRYER VENT MAY NOT DISCHARGE NEAR THE
 A/C CONDENSER UNIT, SEE 2004 FBC/M 501.2 , PLEASE
 CORRECT.
  
 2) SHOW THE RELOCATED A/C CONDENSER UNIT ON THE REVISED
 MECHANICAL PLANS (SEE REVISED ELECTRICAL PLAN), PLEASE
 CORRECT.
  
 3) THE TITLE BLOCK OF THE MECHANICAL REVISION SHOWS THE
 JOB ADDRESS AS BELLE GLADE, PLEASE CORRECT.
  
 4) SEE OTHER TRADE REVIEW NOTES REGARDING THE ENGINEER
 OF RECORD, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-06-22 Cont ID  
Sent By tgordon Date 2006-06-22 Time 08:09 Rev Time 0.20
Received By tgordon Date 2006-06-22 Time 08:09 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-04-11 Cont ID  
Sent By dpalmer Date 2006-06-21 Time 18:01 Rev Time 0.45
Received By tgordon Date 2006-04-11 Time 09:08 Sent To P
Notes
2006-04-11 00:00:00*** DENIED ***
 1) ENGINEER'S PRINTED LICENSE NUMBER
 MUST APPEAR IN THE TITLE BLOCK, PER FAC
 61G15-23.002 .
  
 2) PLEASE SHOW THE SIZE OF THE DUCT FROM
 THE EXISTING TRUNK LINE TO THE MIXING
 BOX (IF FLEX) OR SHOW AS A RIDGE DUCT.
  
 3) PLEASE SHOW BATHROOM EXHAUST FAN ON
 MECHANICAL PLANS.
  
 4) PLEASE SHOW THE CLOTHES DRYER VENT ON
 MECH. PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-12-05 Cont ID  
Sent By jleech Date 2007-12-05 Time 15:12 Rev Time 0.00
Received By jleech Date 2007-12-05 Time 15:07 Sent To B
Notes
2007-12-05 15:13:31REVISED SANITARY RISER DIAGRAM.

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-07-30 Cont ID  
Sent By jleech Date 2007-07-30 Time 07:35 Rev Time 0.00
Received By jleech Date 2007-07-30 Time 07:24 Sent To E
Notes
2007-07-30 07:34:46DENIED;
 1. REVISIONS MUST BE APPROVED, SIGNED AND SEALED BY THE
 DESIGN PROFESSIONAL OF RECORD.
 2. A SANITARY RISER DIAGRAM IS REQUIRED, SEE FBC-2004
 BUILDING CHAPTER 1 ADMIINISTRATION AMENDMENTS SECTION
 106.3.5.4( 9).
 3. AUTOMATIC CLOTHES WASHER BRANCH DRAIN MUST DISCHARGE
 UP OR DOWN STREAM OF THE BATHROOM GROUP. SEE FBC-2004
 PLUMBING SECTION 909.1.
 4. AUTOMATIC CLOTHES WASHER TO BE 3" NOT 2" SEE SECTION
 406.3.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-07-08 Cont ID  
Sent By jleech Date 2006-07-08 Time 09:22 Rev Time 0.00
Received By jleech Date 2006-07-08 Time 09:22 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-04-12 Cont ID  
Sent By jleech Date 2006-04-12 Time 11:29 Rev Time 0.00
Received By jleech Date 2006-04-12 Time 11:29 Sent To B
Notes
2006-04-12 00:00:00DENIED;
 1.ENGINEER'S PRINTED LICENSE NUMBER
 REQUIRED IN TITLE BLOCK PER. FAC
 61G15-23.002.
 2.HAND WRITEN ITEMS ON DRAWINGS ARE NOT
 EXCEPTABLE.
 3.AUTOMATIC CLOTHES WASHER DRAIN TO BE
 3" FBC-2004 SEC. 406.3.
 4.C.O. REQUIRED ON W/M STACK AT 48" AFF.
 5.W/M DISCHARGE SHALL BE DOWN STREAM OF
 THE BATHROOM GROUP. LAVATORY VENT SHOULD
 BE UP STREAM OF SHOWER SO SHOWER IS
 VENTED. SEC. 909.1.
 6.THERMAL EXPANSION CONTROL IS REQUIRED
 PER SEC.607.3 LIST ON PLANS MEANS OF
 CONTROL.
 7.A TWO WAY CLEANOUT IS REQUIRED OUT
 SIDE NEW ADDITION BEFORE BUILDING SEWER
 TIE-IN. SEC.708.3.5

Review Stop Z ZONING
Rev No 2 Status P Date 2007-11-14 Cont ID  
Sent By choops Date 2007-11-14 Time 11:38 Rev Time 0.00
Received By choops Date 2007-11-14 Time 11:38 Sent To E
Notes
2007-11-14 11:39:09***APPROVED - REVISION***
  
 PROVISO:A/C EQUIPMENT MAY NOT PROJECT MORE THAN 4'
 INTO A REQUIRED SETBACK.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-04-10 Cont ID  
Sent By mmclean Date 2006-04-10 Time 13:25 Rev Time 0.00
Received By mmclean Date 2006-04-10 Time 13:25 Sent To I
Notes
***NONE***