Plan Review Details - Permit 06031567
Plan Review Stops For Permit 06031567
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-09-26 Cont ID  
Sent By alange Date 2006-09-26 Time 10:23 Rev Time 0.00
Received By alange Date 2006-09-26 Time 10:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-06-08 Cont ID  
Sent By alange Date 2006-06-08 Time 08:05 Rev Time 0.50
Received By alange Date 2006-06-08 Time 08:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-05-11 Cont ID  
Sent By alange Date 2006-05-11 Time 11:20 Rev Time 0.50
Received By alange Date 2006-05-11 Time 11:20 Sent To  
Notes
2006-05-11 00:00:00DENIED
 SECOND REVIEW:
  
 SHOW SLAB DETAIL AND METHOD OF GENERATOR
 ATTACHMENT TO SLAB.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-14 Cont ID  
Sent By alange Date 2006-04-14 Time 16:23 Rev Time 0.25
Received By alange Date 2006-04-14 Time 16:23 Sent To  
Notes
2006-04-14 00:00:00DENIED
  
 SHOW SLAB DETAIL AND METHOD OF GENERATOR
 ATTACHMENT TO SLAB.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2006-09-17 Cont ID  
Sent By dpalmer Date 2006-09-17 Time 11:29 Rev Time 0.00
Received By dpalmer Date 2006-09-17 Time 11:28 Sent To B
Notes
2006-09-17 00:00:00REVISION SUBMITTED FOR SLAB, NOT FOR
 ELECTRICAL REVIEW, SENT TO BUILDING
 REVIEWER.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-06-02 Cont ID  
Sent By dpalmer Date 2006-06-02 Time 15:43 Rev Time 0.00
Received By dpalmer Date 2006-06-02 Time 15:43 Sent To B
Notes
2006-06-02 00:00:00REDLINED, 100A DISC FOR FEEDERS FROM
 GEN GROUPED WITH EXISTING MAIN
 DISCONNECT PER 225.31-225.39

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-05-09 Cont ID  
Sent By dpalmer Date 2006-05-09 Time 18:53 Rev Time 0.00
Received By dpalmer Date 2006-05-09 Time 18:27 Sent To M
Notes
2006-05-09 00:00:00******** UNSAT ***********
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED ALONG
 WITH SOME NEW COMMENTS DUE TO CHANGES IN
 PLANS MADE.
  
 1) NOTE: NOTE #1, PLEASE SEE A SCHEDULE
 WAS PROVIDED ,
 PLEASE SEE LOAD FOR AHU/ CU ON PANEL
 SCHEDULE, PLEASE CLARIFY WHERE HEAT LOAD
 IS ? WHEN THIS IS UNDER NORMAL POWER
 HEAT IS BEING FED FROM SOMEWHERE? OR IS
 HEAT NOW BEING COMPLETELY REMOVED.?
 PLEASE SEE OCP FOR DRYER IS SHOWN AT
 40A'S FOR 5KW?
 PLEASE KNOW, GEN LT, APPL, RECEPTS MAY
 BE DERATED, ONLY THE HEAT MUST BE
 FIGURED AT 100%, UNLESS LOAD SHEDDING IS
 USED.
  
 ** PREVIOUS REVIEW **
 PLEASE SEE PLEASE PROVIDE A SCHEDULE FOR
 THE TRANSFER PANEL FOR INTENDED LOADS
 AND PLEASE CLARIFY AHU LOAD. UNLESS
 AUTOMATIC LOAD SHEDDING IS DETAILED AND
 PROVIDED, AHU HEAT SHALL BE FIGURED AT
 100%.
 220, 702.5
 PLEASE KNOW, MANY OF THE PRE-WIRED
 PANELS DO NOT CONTAIN THE OCP WHICH MAY
 BE NEEDED FOR THE INTENDED LOADS AND
 ALTERATION OF LISTED EQUIPMENT IS NOT
 PERMITTED.
  
 2) NOTE: NOTE #2 NO, PLEASE SEE PLANS
 ARE RE-DRAWN AND ARE OK, HOWEVER PLEASE
 SEE RISER DOES NOT INDICATE A
 DISCONNECT?
 SOMETHING IS SHOWN, BUT NOT CLEAR WHAT
 THIS IS?
  
 ** PREVIOUS REVIEW **
 PLEASE RE-DRAWN RISER WITH OUT
 HAND DRAWN AND WHITE-OUT CHANGES. PLEASE
 INCLUDE DISCONNECTING MEANS FROM
 GENERATOR TO MAIN HOUSE AND THIS
 DISCONNECTING MEANS SHALL BE GROUPED
 WITH THE EXISTING MAIN.
 225.31-225.39.
  
 3) NOTE:OK.P
  
 4) NOTE:NOTE #4, PLEASE SEE SPECS
 SUBMITTED FOR PANEL/ ATS DOES NOT
 CORRELATE WITH PLANS AND UNIT BEING
 INSTALLED.
  
 ** PREVIOUS NOTE **
 PLEASE SUBMIT SPECS FOR ATS/
 PANEL BEING INSTALLED.
 PLEASE INDICATE THE AIC RAITNG FOR ATS.
 NFPA-110, 6.5.2, NEC 110.9
 215.5
  
 5) NOTE: NOTE #5 OK, BE SURE ALL REVISED
 ARE SIGNED ALSO.
  
 ** PREVIOUS NOTE **
 PLEASE BE SURE ALL SHEETS
 CONTAIN THE PRINTED NAME AND THE
 SIGNATURE OF THE PERSON TAKING
 RESPONSIBILITY FOR PLANS AND DESIGN.
  
 ** NEW NOTE **
 1)NOTE: PLEASE SEE CALCS SHOW CITY OF
 "PALM BEACH GARDENS"? PLEASE ADJUST.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW., IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-12 Cont ID  
Sent By dpalmer Date 2006-04-12 Time 18:11 Rev Time 0.00
Received By dpalmer Date 2006-04-12 Time 18:11 Sent To M
Notes
2006-04-12 00:00:00******** UNSAT ***********
  
 1) NOTE: PLEASE PROVIDE A SCHEDULE FOR
 THE TRANSFER PANEL FOR INTENDED LOADS
 AND PLEASE CLARIFY AHU LOAD. UNLESS
 AUTOMATIC LOAD SHEDDING IS DETAILED AND
 PROVIDED, AHU HEAT SHALL BE FIGURED AT
 100%.
 220, 702.5
 PLEASE KNOW, MANY OF THE PRE-WIRED
 PANELS DO NOT CONTAIN THE OCP WHICH MAY
 BE NEEDED FOR THE INTENDED LOADS AND
 ALTERATION OF LISTED EQUIPMENT IS NOT
 PERMITTED.
  
 2) NOTE: PLEASE RE-DRAWN RISER WITH OUT
 HAND DRAWN AND WHITE-OUT CHANGES. PLEASE
 INCLUDE DISCONNECTING MEANS FROM
 GENERATOR TO MAIN HOUSE AND THIS
 DISCONNECTING MEANS SHALL BE GROUPED
 WITH THE EXISTING MAIN.
 225.31-225.39.
  
 3) NOTE: PLEASE INCLUDE LOCATIONS OF ALL
 SERVICE EQUIPMENT AS SHOWN ON RISER ON
 THE PROVIDED SITE LAYOUT. PLEASE SEE
 PLANS, AT CURRENT TIME ONLY INDICATE THE
 ATS ON THE OUTSIDE OF DWELLING.
 215.5
  
 4) NOTE: PLEASE SUBMIT SPECS FOR ATS/
 PANEL BEING INSTALLED.
 PLEASE INDICATE THE AIC RAITNG FOR ATS.
 NFPA-110, 6.5.2, NEC 110.9
 215.5
  
 5) NOTE: PLEASE BE SURE ALL SHEETS
 CONTAIN THE PRINTED NAME AND THE
 SIGNATURE OF THE PERSON TAKING
 RESPONSIBILITY FOR PLANS AND DESIGN.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW., IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-04-13 Cont ID  
Sent By mperson Date 2006-04-13 Time 14:25 Rev Time 0.15
Received By mperson Date 2006-04-13 Time 14:25 Sent To B
Notes
2006-04-13 00:00:00NOTE: GAS PERMIT REQUIRED. GAS
 CONTRACTOR TO SUBMIT PLANS WITH PERMIT
 APPLICATION. ALL GAS INSPECTIONS TO BE
 COMPLETE BEFORE FINAL GEN/RES
 INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-09-09 Cont ID  
Sent By adarroug Date 2006-09-09 Time 19:08 Rev Time 0.00
Received By adarroug Date 2006-09-09 Time 19:08 Sent To E
Notes
2006-09-09 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-05-23 Cont ID  
Sent By adarroug Date 2006-05-23 Time 14:38 Rev Time 0.00
Received By adarroug Date 2006-05-23 Time 14:38 Sent To E
Notes
2006-05-23 00:00:00TO "E" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-02 Cont ID  
Sent By adarroug Date 2006-05-02 Time 10:50 Rev Time 0.00
Received By adarroug Date 2006-05-02 Time 10:50 Sent To E
Notes
2006-05-02 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-26 Cont ID  
Sent By adarroug Date 2006-04-26 Time 12:35 Rev Time 0.00
Received By adarroug Date 2006-04-26 Time 12:35 Sent To Z
Notes
2006-04-26 00:00:00TO "Z" BOX/RESUB-NEW SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-10 Cont ID  
Sent By adarroug Date 2006-04-10 Time 16:35 Rev Time 0.00
Received By adarroug Date 2006-04-10 Time 16:35 Sent To E
Notes
2006-04-10 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-14 Cont ID  
Sent By alange Date 2006-04-14 Time 16:24 Rev Time 0.00
Received By alange Date 2006-04-06 Time 09:36 Sent To  
Notes
2006-04-06 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2006-05-10 Cont ID  
Sent By tgordon Date 2006-05-10 Time 10:53 Rev Time 0.10
Received By tgordon Date 2006-05-10 Time 10:53 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-04-13 Cont ID  
Sent By tgordon Date 2006-04-13 Time 08:25 Rev Time 0.15
Received By tgordon Date 2006-04-13 Time 08:25 Sent To P
Notes
2006-04-13 00:00:00*** PROVISO ***
 1)GENERATOR EXHUST MUST BE TEN FEET AWAY
 FROM ANY BUILDING OPENINGS (WINDOWS,
 DOORS, ROOF & EAVE VENTS), AND TEN FEET
 AWAY FROM ADJECENT BUILDING OPENS. PER
 2004 FBC/M 401.5.1 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-04-13 Cont ID  
Sent By mperson Date 2006-04-13 Time 14:25 Rev Time 0.00
Received By mperson Date 2006-04-13 Time 14:25 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-04-30 Cont ID  
Sent By mmclean Date 2006-04-30 Time 17:25 Rev Time 0.00
Received By mmclean Date 2006-04-30 Time 17:25 Sent To I
Notes
2006-04-30 00:00:00NOTE: GENERATOR CAN ONLY ENCROACH 4FT
 INTO A SETBACK.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-04-10 Cont ID  
Sent By mmclean Date 2006-04-10 Time 08:17 Rev Time 0.00
Received By mmclean Date 2006-04-10 Time 08:17 Sent To I
Notes
***NONE***