Plan Review Details - Permit 06031563
Plan Review Stops For Permit 06031563
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-08 Cont ID  
Sent By alange Date 2006-05-08 Time 08:05 Rev Time 3.00
Received By alange Date 2006-05-08 Time 08:05 Sent To  
Notes
2006-05-08 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUE HAS BEEN REVISED TO
 $348,309.ADDITIONAL PERMIT FEES ARE
 DUE.
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 5.PRODUCT APPROVALS REQUIRED FOR ALL
 PRODUCTS LISTED IN RULE 9B-72.SUBMIT
 TWO COMPLETE SETS WITH THE FOLLOWING
 STATE PRODUCT APPROVAL ATTACHED.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
  
 9.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 10.SUBMIT TWO ORIGONAL SURVEYS. FS
 472.025
  
 11.SUBMIT TWO COPIES OF ENERGY CALCS
 FOR THE 2004 FBC.
  
 12.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2005 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.CHECK ALL CODE
 REFERENCES USED.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-11 Cont ID  
Sent By dpalmer Date 2006-04-11 Time 19:30 Rev Time 0.00
Received By dpalmer Date 2006-04-11 Time 17:45 Sent To M
Notes
2006-04-11 00:00:00************ UNSAT ***************
  
 1) NOTE: PLEASE SUBMIT COMPLETE PANEL
 SCHEDULES WITH ALL MININNUM REQUIRED
 DEDICATED CIRCUITS AND ALL CIRCUITS
 SHOWN ON PLANS WITH MIN OCP, AWG PER
 240.4,310.16,215.5
 THERE ARE MANY ITEMS MISSING AT THIS
 TIME TO LIST ALL.
  
 2) NOTE: PLEASE SUBMIT LOAD CALCUALTIONS
 WHICH MEET THE MININUM NEC COMPLIANCE TO
 2002 NEC 220.31B.
 PLEASE KNOW, THE LOADS AS SHOWN ARE NOT
 COMPLIANT.
  
 3) NOTE: PLEASE SHOW AND INDICATE ALL
 AREA AND ROOM DESIGNATIONS ON ELECTRICAL
 PLANS.
 THISWILL AFFECT REVIEW FOR CODE
 COMPLIANCE OF AREAS.
 215.5
  
 4) NOTE: PLEASE SEE NUMEROUS MISSING
 RECEPTS PER 210.52
  
 5) NOTE: PLEASE SEE MISSING RECEPTS FOR
 HALLWAYS PER 210.52H
  
 6) NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52E
  
 7) NOTE: PLEASE SEE NOTE WHICH MENTIONS
 RECEPTS W/IN 15' OF POOL TO BE GFI DOES
 NOT MEET 680.22
  
 8) NOTE: PLEASE SEE NOET WHICH MENTIONS
 RECEPTS W/ IN 6' OF KITCHEN SINK TO BE
 GFI IS FROM THE "1993" NEC.PLEASE
 KNOW, THE REQUIREMENTS FOR KITCHEN
 COUNTERSPACE RECEPTS CHANGED IN 1996.
 PLEASE SEE 210.8A6, 2002
  
 9) NOTE: PLEASE SEE MISSING DISCONNECTS
 FOR ALL A/C EQUIPMENT, CU'S AND AHU'S
 NEW AND EXISTING ARE TO BE SHOWN WITH
 MIN CLEARENCES.
 440.11,110.26, 215.5
  
 10) NOTE: PLEASE CLARIFY GFI RECEPT
 BEHIND EACH CU AND GEN? THIS IS OK,
 HOWEVER UNCLEAR?
  
 11) NOTE: PLEASE SEE GENERATOR SHOWN ON
 PLANS CAN NOT BE PART OF THIS PERMIT AS
 NO INFORMATION WAS SUBMITTED FOR UNIT
 NOR IS IT SHOWN IN THE ELECTRICAL RISER
 DIAGRAM.
 PLEASE REMOVE FROM PLANS, OR SUBMIT ALL
 INFORMATION AND COMPLETE PLANS FOR
 INSTALLATION.
 215.5
  
 12) NOTE: PLEASE SEE THAT ALL CURRENT
 APPLICABLE CODES ARE NOTED ON ELECTRICAL
 PLANS.
 2002 NFPA-70 ( NEC ) , 2002 NFPA-72
  
 13) NOTE: PLEASE SEE NFPA-72 11.5.1.1
 FOR ALL MIN LOCATIONS REQUIRED FOR SD'S.
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS,
 LOCATED IN THE IMMEDIATE VICINITY OF
 BEDRM DOORS AND LOCATED ON EACH LEVEL OF
 A MULTI-LEVEL RESIDENCE IN CLOSE
 PROXIMITY LEADING TO THE FLR ABOVE AND
 ON 2DN FLR LEVEL AT THE TOP OF STAIRS.
 PLEASE ALSO SEE 11.8.3.5 FOR OTHER
 LOCATIONS PERMITTED AND LOCATIONS NOT
 PERMITTED.
  
 14) NOTE: PLEASE SHOW THE LOCATION OF
 THE METER/SERVICE.
 215.5
  
 15) NOTE: PLEASE SEE PLANS INDICATE A
 TANKLESS WH, YET THIS IS NOT ON PANEL
 SCHEDUL, LOADSETC?
 215.5
  
 16) NOTE: PLEASE SEE THAT THE PLANS
 SHALL CONTAINTHE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 PLANS AND DESIGN.
 FBC ADMINISTRATIVE CODE.
 106.3.4.3
 PLANS SHALL CONTAIN ALL INFORMATION FOR
 CODE COMPLIANCE AS SET FORTH BY THE FBC
 2004, AND NATIONAL ELECTRICAL CODE.
 PLANS MAY BE REQUIRED TO BE DONE BY A
 LICENSED DESIGN PROFESSIONAL FOR
 COMPLIANCE. 106.1.2, 106.3.5.4
  
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT THE NEW REVISEDSHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONE COPY OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE ONLY.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-10 Cont ID  
Sent By adarroug Date 2006-04-10 Time 16:39 Rev Time 0.00
Received By adarroug Date 2006-04-10 Time 16:39 Sent To E
Notes
2006-04-10 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-08 Cont ID  
Sent By alange Date 2006-05-08 Time 08:11 Rev Time 0.00
Received By alange Date 2006-04-03 Time 15:13 Sent To  
Notes
2006-04-03 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-04-12 Cont ID  
Sent By tgordon Date 2006-04-12 Time 16:51 Rev Time 0.30
Received By tgordon Date 2006-04-12 Time 16:51 Sent To P
Notes
2006-04-12 00:00:00*** DENIED ***
 1) NO MECHANICAL PLANS WERE SUBMITTED
 FOR REVIEW. PLEASE SUBMIT MECHANICAL
 PLANS FOR REVIEW, OR YOU MAY WISH TO
 VOID YOUR MECHANICAL PERMIT NUMBER
 06040008 SO YOUR BUILDING PLANS MAY
 BY-PASS A MECHANICAL REVIEW.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-04-13 Cont ID  
Sent By jleech Date 2006-04-13 Time 10:19 Rev Time 0.00
Received By jleech Date 2006-04-13 Time 10:19 Sent To B
Notes
2006-04-13 00:00:00DENIED;
 1.PAGE 4 SIZE ROOF SCUPPER AND EMERGENCY
 SCUPPERS USING FBC-2004 PLUMBING TABLE
 1106.7. SHOW CAULK'S.
 2.EMERGENCY SCUPPERS TO BE 2" TO 4"
 ABOVE FINISH ROOF. IN SOME ELEVATION
 VIEWS EMERGENCY SCUPPERS ARE THE SAME
 HIGHT AS SCUPPERS. SHOW TOTAL SQ.INS. OF
 OPEN AREA.
 3.SANITARY RISER DIAGRAM DOES NOT MATCH
 FLOOR PLAN, AND CODE VIOLATIONS EXIST.
 4.SECOND FLOOR FIXTURES CANNOT DUMP INTO
 THE VENT OF THE FIRST FLOOR FIXTURES.
 5.SHOWERS ARE NOT VENTED (WHERE
 HIGHLIGHTED)
 6.C.O. REQUIRED ON WASHER STACK 48"
 AFF.
 7.PRINTED AND SIGNATURE OF PERSON
 RESPONSIBLE FOR PLANS IS REQUIRED BY
 FBC-2004 CHAPTER 1 ADMINISTRATION CODE
 SEC.106.3.4.3
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status F Date 2006-04-10 Cont ID  
Sent By mmclean Date 2006-04-10 Time 07:46 Rev Time 0.00
Received By mmclean Date 2006-04-10 Time 07:46 Sent To I
Notes
2006-04-10 00:00:00DENIED,
 1. MUST PROVIDE THE TWO CURRENT COPY OF
 SURVEY SHOWING THE PROPOSED ADDITION &
 REMODEL.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720