Plan Review Details - Permit 06031518
Plan Review Stops For Permit 06031518
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-12-27 Cont ID  
Sent By lmartine Date 2006-12-27 Time 17:25 Rev Time 0.00
Received By lmartine Date 2006-12-27 Time 17:25 Sent To  
Notes
2006-12-27 17:25:45RESTAMP PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-04-14 Cont ID  
Sent By alange Date 2006-04-14 Time 16:00 Rev Time 0.33
Received By alange Date 2006-04-14 Time 16:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-05-31 Cont ID  
Sent By btrobaug Date 2006-05-31 Time 07:00 Rev Time 0.66
Received By btrobaug Date 2006-05-31 Time 06:30 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-05-14 Cont ID  
Sent By dpalmer Date 2006-05-14 Time 15:09 Rev Time 0.00
Received By dpalmer Date 2006-05-14 Time 15:09 Sent To P
Notes
2006-05-14 00:00:00********* UNSAT **********
  
 PLANS NOW SUBMITTED FOR REVIEW. PLEASE
 SEE COMMENTS BELOW.
  
 ** PLEASE SEE SUBMITTED PACKAGE AHS NOW
 COME BACK WITH OUT THE 2ND COPY OF SLAB
 PLANS/DETAIL. PLEASE SUBMIT BOTH COPIES,
 ONE IS NEED FOR FILE SET AND THEN ONE IS
 PROVIDED BACK TO CONTRACTOR ONCE PERMIT
 IS ISSUED AND DATE STAMPED.
  
 1)NOTE: PLEASE PROVIDE LAYOUT ON
 SITE/ELECTRICAL FOR LOCATION OF ALL
 SERVICE EQUIPMENT.
 PLEASE SEE PLANS DO NOT INDICATE
 LOCATION OF EXISTING MAIN(S).
 PLEASE INDICATE ROOM THE ATS PANEL IS
 LOCATED.
 PLEASE SEE RISER AND PLANS DO NOT
 INDICATE ANY DISCONNECTING MEANS FOR
 FEEDERS COMING FROM THE GEN. THE
 DISCONNECT MEANS DOES NOT REQUIRE OCP,
 HOWEVER IS REQUIRED TO BE RATED FOR THE
 LOAD SERVED, GROUPED WITH EXISTING
 MAINS.
 PLEASE NOTE, THE BRKR LOCATED INSIDE THE
 GEN IS NOT ACCCEPTED AS THE MEANS OF
 DISCONNECT.110.27,225.31-225.39.
 PLEASE SEE THIS WAS NOTED ON PREVIOUS
 REVIEW.
  
 2) NOTE: PLEASE CORRELATE RISER DIAGRAM
 SUBMITTED WITH SPECS.
 ATS/PANEL IS SHOWN AS 100A'S AND 60A'S.
  
  
 3) NOTE: PLEASE KNOW, ALL PLANS SHALL
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR
 DESIGN/PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-12 Cont ID  
Sent By dpalmer Date 2006-04-12 Time 18:25 Rev Time 0.00
Received By dpalmer Date 2006-04-12 Time 18:25 Sent To M
Notes
2006-04-12 00:00:00************ UNSAT **************
  
 1) NOTE: PLEASE SUBMIT TWO COPIES OF
 PLANSS/ RISER DIAGRAM ON GENERATOR, ATS,
 DISCONNECTING MEANS ETC TO BE INSTALLED.
 NO PLANS SUBMITTED.
 PLEASE INDICATE ALL SERVICE EQUIPMENT ON
 A SITE LAYOUT.
 PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT
 SHEETS FOR GEN/ ATS.
 215.5, 225.31-225.39, 702.5, 220
  
 2) NOTE: PLEASE BE SURE PERMIT
 APPLICATION DESCRIBES PROJECT IN DETAIL
 AS MENTIONED ON APPLICATION. PLEASE
 MENTIONS, SIZE OF GEN ETC.
  
 3) NOTE: PLEASE PROVIDE PANEL
 SCHEDULE(S), FOR INTENDED LOADS AND LOAD
 CALCUALTIONS FOR INTENDED LOADS. THIS
 WILL DEPEND ON HOW SYSTEM IS BEING
 INSTALLED.
  
 ** PLEASE KNOW, THERE WILL BE COMMENTS
 FROM OTHER TRADES FOR GAS AND MECH AT A
 MIN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-05-15 Cont ID  
Sent By mperson Date 2006-05-15 Time 13:29 Rev Time 0.33
Received By mperson Date 2006-05-15 Time 13:29 Sent To PC
Notes
2006-05-15 00:00:00 
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 2,000 CUBIC FEET REQUIRED.

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-04-13 Cont ID  
Sent By mperson Date 2006-04-13 Time 14:05 Rev Time 0.15
Received By mperson Date 2006-04-13 Time 14:04 Sent To B
Notes
2006-04-13 00:00:00NOTE: GAS PERMIT REQUIRED. GAS
 CONTRACTOR TO SUBMIT PLANS WITH PERMIT
 APPLICATION. ALL GAS INSPECTIONS TO BE
 COMPLETE BEFORE FINAL GEN/RES
 INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-22 Cont ID  
Sent By adarroug Date 2006-05-22 Time 15:08 Rev Time 0.00
Received By adarroug Date 2006-05-22 Time 15:08 Sent To E
Notes
2006-05-22 00:00:00TO "E" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-12 Cont ID  
Sent By adarroug Date 2006-05-12 Time 10:31 Rev Time 0.00
Received By adarroug Date 2006-05-12 Time 10:31 Sent To E
Notes
2006-05-12 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-04 Cont ID  
Sent By adarroug Date 2006-04-04 Time 11:01 Rev Time 0.00
Received By adarroug Date 2006-04-04 Time 11:01 Sent To E
Notes
2006-04-04 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-14 Cont ID  
Sent By alange Date 2006-04-14 Time 16:00 Rev Time 0.00
Received By alange Date 2006-03-31 Time 13:10 Sent To  
Notes
2006-03-31 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-04-13 Cont ID  
Sent By tgordon Date 2006-04-13 Time 09:10 Rev Time 0.20
Received By tgordon Date 2006-04-13 Time 09:10 Sent To P
Notes
2006-04-13 00:00:00*** PROVISO ***
 1)GENERATOR EXHUST MUST BE TEN FEET AWAY
 FROM ANY BUILDING OPENINGS (WINDOWS,
 DOORS, ROOF & EAVE VENTS), AND TEN FEET
 AWAY FROM ADJECENT BUILDING OPENS. PER
 2004 FBC/M 401.5.1 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-04-13 Cont ID  
Sent By mperson Date 2006-04-13 Time 14:04 Rev Time 0.00
Received By mperson Date 2006-04-13 Time 14:04 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-04-01 Cont ID  
Sent By mmclean Date 2006-04-01 Time 12:53 Rev Time 0.00
Received By mmclean Date 2006-04-01 Time 12:53 Sent To I
Notes
2006-04-01 00:00:00NOTE: GENERATOR CAN ONLY ENCROACH 4FT
 INTO A SETBACK.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved