Plan Review Details - Permit 06031445
Plan Review Stops For Permit 06031445
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-10-18 Cont ID  
Sent By amorse Date 2006-10-18 Time 07:04 Rev Time 0.00
Received By amorse Date 2006-10-18 Time 07:04 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-20 Cont ID  
Sent By amorse Date 2006-06-20 Time 12:12 Rev Time 0.50
Received By amorse Date 2006-06-20 Time 12:12 Sent To PC
Notes
2006-06-20 00:00:00 
  
 DENIED
  
 1) PREVIOUS SUBMITTAL WAS FOR FACE
 CHANGE ONLY NEW DESIGN REQUIRES THE WIND
 DESIGN CRITERIA PER 1603.1.4 TO BE
 STATED ON THE DRAWINGS. THE STAMP
 PROVIDED IS NOT COMPLETE.
  
 2) PLEASE BE AWARE THAT DRAWINGS WITH
 WHITE OUT OR CHANGES MADE AFTER SEALING
 OF THE DOCUMENT WILL NOT BE ACCEPTED
  
 3) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-04-28 Cont ID  
Sent By amorse Date 2006-04-28 Time 07:22 Rev Time 0.50
Received By amorse Date 2006-04-28 Time 07:22 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-10-17 Cont ID  
Sent By dpalmer Date 2006-10-17 Time 07:09 Rev Time 0.00
Received By dpalmer Date 2006-10-17 Time 07:02 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-20 Cont ID  
Sent By dpalmer Date 2006-06-20 Time 10:03 Rev Time 0.00
Received By dpalmer Date 2006-06-20 Time 10:01 Sent To B
Notes
2006-06-20 00:00:00*********** UNSAT **************
  
 1) NOTE: PLEASE SEE PLANS/DRAWING IS NOW
 COMING IN WITH "WHITE-OUT" AND HAND
 DRAWN CHANGES AT NUMEROUS LOCATIONS ON
 PLANS. PLEASE SEE FS 471.025, THIS IS
 NOT PERMITTED.
 ** PLEASE ALSO SEE BUIDLING REVIEW NOTES
 AS ORIGINAL PLANS WERE NOT SUBMITTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-11 Cont ID  
Sent By dpalmer Date 2006-04-11 Time 12:17 Rev Time 0.00
Received By dpalmer Date 2006-04-11 Time 12:17 Sent To B
Notes
2006-04-11 00:00:00********** UNSAT ***********
  
 1) NOTE: PLEASE SEE NO ELECTRICAL DETAIL
 WAS SUBMITTED FOR THE PROPOSED
 ILLUMINATED SIGN.
 BALLAST, TRANSFORMERS, DISCONNECT?
 215.5,600.6,
 PLEASE SEE THE CABINET IS CHANGING AND
 IS NOT ONNLY A FACE CHANGE.
  
 2) NOTE: PLEASE SEE LETTER ATTACHED FOR
 SIGN AUTHORIZATION IS TO BE NOTARIZED
 PER FS 117.05.
 MISSING COUNTY AND STATE INFORMATION.)
  
 3) NOTE: PLEASE SEE VALUE SHALL REFELCT
 ALL LABOR AND MATERIALS FOR THE SIGN,
 EVEN IF SIGN IS OWNER SUPPLIED.
 FBC , ADMINISTRATIVE SEC 108.3.
  
 4) NOTE: PLEASE OBTAIN AND BRING IN
 INFORMATION FOR OWNERSHIP OF PROPERTY AS
 THE PBC PROPERTY APPR OFFICE INDICATES A
 MR. WILLIAM LEWIS AND APPLICATION SHOWS
 "FOREST HILL STATION INC"
 PLEASE SEE PRINT OUT FROM PBC PROP APPR.
 WHICH IS ATTACHED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-11-16 Cont ID  
Sent By adarroug Date 2006-11-16 Time 11:21 Rev Time 0.00
Received By adarroug Date 2006-11-16 Time 11:21 Sent To Z
Notes
2006-11-16 11:21:45TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-10-16 Cont ID  
Sent By adarroug Date 2006-10-16 Time 11:42 Rev Time 0.00
Received By adarroug Date 2006-10-16 Time 11:42 Sent To E
Notes
2006-10-16 11:42:17TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-10-10 Cont ID  
Sent By adarroug Date 2006-10-10 Time 19:11 Rev Time 0.00
Received By adarroug Date 2006-10-10 Time 19:11 Sent To Z
Notes
2006-10-10 19:11:46TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-06-20 Cont ID  
Sent By adarroug Date 2006-06-20 Time 08:56 Rev Time 0.00
Received By adarroug Date 2006-06-20 Time 08:56 Sent To E
Notes
2006-06-20 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-14 Cont ID  
Sent By adarroug Date 2006-06-14 Time 14:09 Rev Time 0.00
Received By adarroug Date 2006-06-14 Time 14:09 Sent To Z
Notes
2006-06-14 00:00:00TO "Z" BOX/RESUB--NEW SHEETS--

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-06 Cont ID  
Sent By adarroug Date 2006-04-06 Time 10:12 Rev Time 0.00
Received By adarroug Date 2006-04-06 Time 10:12 Sent To E
Notes
2006-04-06 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-04-28 Time   Rev Time 0.00
Received By adarroug Date 2006-03-30 Time 16:40 Sent To  
Notes
2006-03-30 00:00:00TO "Z" BOX

Review Stop Z ZONING
Rev No 4 Status P Date 2006-11-21 Cont ID  
Sent By mmclean Date 2006-11-21 Time 16:24 Rev Time 0.00
Received By mmclean Date 2006-11-21 Time 16:24 Sent To I
Notes
2006-11-21 16:28:43NOTE: THE POLE SIGN MUST NOT EXCEED 10FT IN HEIGHT.
  
 PROVISO: PLEASE CHANGE PERMIT APPLICATION AND COMPUTER
 SCREEN TO REFLECT REPLACE POLE SIGN, SUNCO SIGN IS
 REMOVED.

Review Stop Z ZONING
Rev No 3 Status F Date 2006-10-13 Cont ID  
Sent By eschneid Date 2006-10-13 Time 11:12 Rev Time 0.00
Received By eschneid Date 2006-10-13 Time 11:12 Sent To  
Notes
2006-10-13 13:36:25FAILED
  
 1) SUNOCO SIGN HAS BEEN REMOVED FROM THE POLE, SO THIS
 IS NO LONGER A FACE CHANGE.
  
 2) NO NEW PORTIONS OF THE SIGN MAY EXCEED 10 FEET IN
 HEIGHT OVERALL.THIS SHALL BE VERIFIED BY PROVIDING AN
 ELEVATION DETAIL OF THE ENTIRE SIGN.
  
 CONTACT ERIC SCHNEIDER (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-06-18 Cont ID  
Sent By mmclean Date 2006-06-18 Time 19:00 Rev Time 0.00
Received By mmclean Date 2006-06-18 Time 19:00 Sent To I
Notes
2006-06-18 00:00:00DENIED,
 1. MUST PROVIDE TWO COPY OF WHAT THE
 EXISTING SIGN WAS ON THE I.D. CABINET.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status P Date 2006-04-05 Cont ID  
Sent By mmclean Date 2006-04-05 Time 16:52 Rev Time 0.00
Received By mmclean Date 2006-04-05 Time 16:52 Sent To I
Notes
2006-04-05 00:00:00REPLACING I.D. CABINET