Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-07 Cont ID  
Sent By jgomez Date 2006-11-07 Time 15:42 Rev Time  
Received By jgomez Date 2006-11-07 Time 15:20 Sent To  
Notes
2006-11-07 15:46:45ENTER IN THIS PERMIT NUMBER BY MISTAKE.I WAS WORKING
 ON THE RE-ROOF PERMIT 06110075.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-01 Cont ID  
Sent By amorse Date 2006-05-01 Time 16:23 Rev Time 0.00
Received By amorse Date 2006-05-01 Time 16:23 Sent To PC
Notes
2006-05-01 00:00:00 
  
 DENIED
  
 1) WIND DESIGN CRITERIA ON TITLE PAGE
 INCORRECT, SHOULD BE ASCE 7-02
  
 2) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION
  
 3) STAIRS ON A2 SHOW 10 RISERS AT 7" TO
 LANDING. DRAWING STATES LANDING AT 5'-4
 3/16" PLEASE CLARIFY
  
 4) INDICATE MINIMUM ROOF SHEATHING NAIL
 PATTERN AS SPECIFIED IN TABLE 2304.9.1
  
 5) WHEN POSSIBLE FLORIDA PRODUCT
 APPROVAL COVER SHEETS SHALL BE SUBMITTED
 THE ONLY PRODUCT THAT REQUIRES IT IS THE
 ROOF TILES. PLEASE SEE FL# 282-R1
  
 6) PRODUCT APPROVAL FOR CASEMENT WINDOWS
 HAVE A MAXIMUM HEIGHT OF 72", THE NEW
 DINING ROOM WINDOW EXCEEDS THE MAX. HT.
  
 7) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-07 Cont ID  
Sent By dpalmer Date 2006-04-07 Time 13:04 Rev Time 0.00
Received By dpalmer Date 2006-04-07 Time 10:09 Sent To M
Notes
2006-04-07 00:00:00******** UNSAT ************
  
 1) NOTE: PLEASE SEE MECHANICALNOTES AS
 COPIES OF SIGNED, DATED AND SEALED PLANS
 WERE MADE OF THE ELECTRICAL PLANS AND
 MECHANICAL LAYOUT ADDED TO ARCHITECTS
 PLANS WHICH IS NOT PERMITTED.
 ** PLEASE SEE COMMENTS BELOW PERTAINING
 TO CORRELATE OF MECH AND ELEC PLANS.
  
 2) NOTE: PLEASE SEE BLDG REVIEW NOTES,
 AS TRUSS LAYOUT/ENGINEERING, CONTAINS A
 "RUBBER STAMP" FOR THE REQUIRED ORIGINAL
 SIGNATURE FORTHE ENGINEER OF RECORD.
 PLEASE SEE FS 471.025
  
 3) NOTE: PLEASE SEE RISER INDICATES
 "EQUIPMENT GROUNDING CONDUCTORS" FROM
 THE METER TO THE FIRST MEANS OF
 DISCONNECT WHICH IS NOT PERMITTED.
 250.6,250.24B.
  
 4) NOTE: PLEASE SEE MIN SIZE FOR
 GROUNDING ELECTRODE SYSTEM SHALL BE
 SIZED ACCORD TO 250.66. SHOWS #4 WHICH
 IS MOST UNLIKELY FOR A 600A SERVICE AS
 SHOWN.
  
 5) NOTE: PLEASE SEE SEC'S FROM FPL ARE
 SHOWN AS ONE RUN OF COPPER CONDUCTORS
 SIZED AT 4/0'S. PLEASE KNOW, THIS ARE
 NOT LARGE ENOUGH FOR A 600A SERVICE.
 PLEASE SEE 310.16, 240.4 FOR SIZING MIN
 SEC'S TO FPL HANDHOLE.
  
 6) NOTE: PLEASE CORRLELATE ALL A/C
 EQUIPMENT FOR CU'S AND AHU'S.
 PLEASE SEE PLANS INDICATE 5 CU'S, YET
 PANELS, LOADS AND MECH PLANS DO NOT
 CORRELATE WITH THIS.
 215.5
  
 7) NOTE: PLEASE SEE MIN OCP FOR AHU'S
 HEAT SHALL BE SIZED PER 424.3B EVEN IF
 EXISTING. MIN OCP IS TO BE SIZED @ 125%.
  
 8) NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCULATIONS.
 PLEASE CORRELATE ALL LOADS ON PANEL
 SCHEDULES WITH LOAD CALCS. (SMALL APPL
 ETC).
 PLEASE PROVIDE PANEL SCHEDULES AND LOAD
 CALCS FOR OTHER PANELS NOT SUBMITTED.
 PLEASE BE SURE ADJUST LOAD CALCS.
 215.5
  
 9) NOTE: PLEASE VERIFY POOL PUMP BEING
 SHOWN ON SCHEDULE "A" WHEN PLANS
 INDICATE A POOL PANEL.
 THIS IS ONLY A NOTE:
  
 10) NOTE: PLEASE SEE PLANS MISSING
 EITHER NEW OR EXISTING FRONT GFI PER
 210.52E,210.8A
  
 11) NOTE: PLEASE SEE SOME MISSING
 RECEPTS PER 210.52 REDLINED ON ONE OF
 THE SETS OF PLANS. BEDRM #4(2' OF WALL),
 LIVING/KITCHEN WALL.
 PLEASE SEE DUE TO THE LEVEL OF
 ALTERATION THE RECEPT ON LOWER LEVEL
 ADJACENT TO KITCHEN REMODEL WILL BE
 REQUIRED IF ONE IS NOT EXISTING.
  
 12) NOTE: PLEASE SEE 210.52C1 FOR SOME
 MISSING GFI RECEPTS ALONG KITCHEN
 COUNTER SPACE.
  
 13) NOTE: PLEASE SEE 250.50 WHICH
 REQUIRES ANY NEW FOOTINGS TO BE BONDED
 TO THE EXISITNG GROUNDING ELECTRODE
 SYSTEM.
 PLEASE REVISE AND INDICATE THIS ON
 RISER.
  
 14) NOTE: PLEASE INDICATE THE REQUIRED
 ARC FAULT PROTECTION FOR ALL PER 2002
 NEC 210.12B.
 SD'S, LTS, RECEPTS, FANS ETC IN SLEEPING
 RMS.
  
 15) NOTE: PLEASE SEE 210.52D AS THE GFI
 RECEPTS IN BATHS LOCATED ADJACENT TO
 LAV'S SHALL BE LOCATED WITHIN 3' FROM
 LAV EDGE.
 (PLEASE SEE HIS BATH) MASTER)
  
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** WHEN RE-SUBMITTING PLANS, PLEASE
 COMPLETELY REMOVED ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING. ONE COPY OF ANY OLD/VOIDED
 REMOVED SHEETS SHOULD BE BE SUBMITTED
 FOR REFERENCE AS AN INDIVIDUAL SET.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-06 Cont ID  
Sent By adarroug Date 2006-04-06 Time 10:30 Rev Time 0.00
Received By adarroug Date 2006-04-06 Time 10:30 Sent To E
Notes
2006-04-06 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-05-01 Time   Rev Time 0.00
Received By adarroug Date 2006-03-30 Time 15:21 Sent To  
Notes
2006-03-30 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-04-07 Cont ID  
Sent By tgordon Date 2006-04-07 Time 15:26 Rev Time 0.25
Received By tgordon Date 2006-04-07 Time 15:26 Sent To P
Notes
2006-04-07 00:00:00*** DENIED ***
 1)PLEASE SUBMIT A MANUAL J CALCULATION,
 PER 2004 FBC 13-607.1.ABC.1 .
  
 2) MECHANICAL PLANS HAVE TO MUCH
 ELECTRICAL DETAIL ON THEM AND ARE TO
 DIFFICULT TO READ. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY. PER 2004 FBC 106.1.1 .
  
 3) ARCHITECT'S SEAL MUST APPEAR ON PLANS
 WITH HIS TITLE BLOCK, PER FAC
 61G1-16.003 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-04-11 Cont ID  
Sent By jleech Date 2006-04-11 Time 07:41 Rev Time 0.00
Received By jleech Date 2006-04-11 Time 07:41 Sent To B
Notes
2006-04-11 00:00:00DENIED;
 1.SANITARY RISER DIAGRAM DOES NOT MATCH
 FLOOR PLAN. W/M AND L/T OUT OF PLACE.
 2.L/T DRAIN TO BE 1 1/2".
 3.FIXTURES ON RISER DIAGRAM ARE NOT
 MARKED CORRECTLY.
 4.COVERED PATIO; WHERE DOES ICE MACHINE
 DRAIN TO?
 ONE SET OF PLANS(RISER DIAGRAM) MARKED
 IN RED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status F Date 2006-04-05 Cont ID  
Sent By mmclean Date 2006-04-05 Time 17:24 Rev Time 0.00
Received By mmclean Date 2006-04-05 Time 17:24 Sent To I
Notes
2006-04-05 00:00:00DENIED,
 1. THE PROPOSED HEIGHT FOR FOYER IS OVER
 THEHEIGHT REQIRED, (2 1/2FT). (HEIGHT
 ALLOWED IS 30FT)
 2. THE EXTENED CHIMENY (EXISTING) WILL
 BE OVER THE HEIGHT REQUIREMENT. (HEIGHT
 ALLOWED 30FT FOR STRUCTURE & 10% FOR
 CHIMENY = 33FT)
 3. THE PROPOSED CHIMENY WILL BE OVER THE
 HEIGHT REQUIREMENT (SEE NOTE #2).
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
  
 NOTE: CHIMENY IS MEASURED FROM THE GRADE
 TO TOP (HIGHEST POINT)
 NOTE: THE STRUCTURE IS MEASURED FROM THE
 GRADE TO THE MEAN HEIGHT FOR A HIP ROOF.