Plan Review Details - Permit 06031357
Plan Review Stops For Permit 06031357
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-09-13 Cont ID  
Sent By shill Date 2007-09-13 Time 10:00 Rev Time 0.00
Received By shill Date 2007-09-13 Time 10:00 Sent To  
Notes
2007-09-13 10:00:42REVISED SP2 AND SP3

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-03-28 Cont ID  
Sent By shill Date 2007-03-28 Time 14:15 Rev Time 0.00
Received By shill Date 2007-03-28 Time 14:15 Sent To  
Notes
2007-03-28 14:20:21REVISED A1-3, A1-4, A3-2
 PROVISO REVISE SP2 AND SP3

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-01-02 Cont ID  
Sent By shill Date 2007-01-02 Time 14:14 Rev Time 0.00
Received By shill Date 2007-01-02 Time 11:34 Sent To  
Notes
2007-01-02 14:16:03****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB
 FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)THIS PERMIT WAS ISSUED WITH A PROVISO TO REVISE
 SHEETS SP2 AND SP3.THE ORIGINAL PLAN, SHEET SP3, WAS
 REDLINED PER AGREEMENT WITH ARCHITECT.RAMP SECTION 3
 IS TO COMPLY WITH FBC11-4.8.4(2), THE BOTTOM OF EACH
 RAMP SHALL HAVE NOT LESS THAN 72 INCHES OF STRAIGHT AND
 LEVEL CLEARANCE.PLAN STILL SHOWS 60IN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-09-29 Cont ID  
Sent By shill Date 2006-09-29 Time 09:02 Rev Time 0.00
Received By shill Date 2006-09-27 Time 13:24 Sent To  
Notes
2006-09-29 00:00:00PROVISO - REVISE SP2 AND SP3 (RAMP,
 GRATING)TO COMPY WITH FBC11
  
 NO APPROVED ASSEMBLY FOR ROOF SELECTED;
 ROOF CONTRACTOR TO BRING IN PRODUCT
 APPROVALS WITH SEPARATE FEES

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-11 Cont ID  
Sent By shill Date 2006-08-11 Time 09:54 Rev Time 0.00
Received By shill Date 2006-08-08 Time 09:22 Sent To  
Notes
2006-08-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ITEMS FROM PREVIOUS LIST NEEDING FURTHER
 CLARIFICATION; NUMBERING REMAINING THE
 SAME FOR CONSISTENCY:
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)REGARDING IMPACT FEES, THE PLANS
 WERE STAMPED WITH INTERIOR ALTERATION, 0
 SQUARE FEET.THIS IS IN CONFLICT WITH
 LS1 WHICH SHOWS AN ADDITION OF 1000 SF.
 THIS
 SHOULD STATE WHETHER THIS IS HABITABLE
 SPACE OR NOT.THE LOADING DOCK
 ENCLOSURE AND THE ENTRY ROOFS SHOULD BE
 DECLARED SEPARATELY AS IMPACT FEES WILL
 BE DUE ON THE LOADING DOCK RENOVATION
 BUT NOT ON THE ENTRIES IF THEY ARE NOT
 UNDER AIR.
  
 3.)ADDRESSED.
  
 4.)THE DUMPSTER ENCLOSURES WILL
 REQUIRE A SEPARATE PERMIT.COMPLETE A
 PERMIT APPLICATION.SEPARATE PLANS ARE
 NOT REQUIRED.
  
 5.)SEPARATE PERMIT REQUIRED FOR THE
 FENCES.SUBMIT SEPARATELY WITH PLANS.
 THIS ITEM DOES NOT NEED TO BE ADDRESSED
 PRIOR TO ISSUANCE OF THIS PERMIT, BUT
 MUST BE ADDRESSED PRIOR TO COMMENCEMENT
 OF THE FENCING WORK.INFORMATIONAL
 ONLY.
  
 6-7.)ADDRESSED.
  
 8.)RAMP DETAIL 3-SP2 WAS REVISED TO
 SHOW 72IN, FBC11-4.8.4(2), PLEASE ALSO
 REVISE 01SP2.MY APOLOGIES FOR MISSING
 THIS DETAIL THE FIRST REVIEW.
  
 9.)CATCH BASIN GRATINGS SHOWN ON
 THE NEW RAMP PLAN, 01-SP2 IS TO COMPLY
 WITH FBC11-4.5.4.
  
 10-13.)
  
 14.)THE PLAN SHOWS ACCORDION SHUTTERS
 ON THE SECOND FLOOR.THIS MUST BE
 APPROVED BY THE BUILDING OFFICIAL, ITEM
 #14 OF THE MISSILE IMPACT PROTECTION
 STANDARD, ATTACHED.SUBMIT AN
 INSTALLATION PLAN AS REFERENCED IN ITEM
 #13.
  
 THE PLAN SUBMITTED BY EMAIL IS TO BE
 SUBMITTED AS A SIGNED ORIGINAL FOR
 REVIEW BY THE BUILDING OFFICIAL.THIS
 MUST BE DONE PRIOR TO PERMIT ISSUANCE.
  
 15.)PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DOR, FBC*106.3.3.SOME ARE
 REFERENCED SPECIFICALLY ON THE PLAN
 (SUCH AS ON A8-1), BUT OTHERS (SUCH AS
 THE ROOF PRODUCTS) ARE NOT.FOR
 PRODUCTS NOT REFERENCED BY NOA NUMBER ON
 THE PLAN, PLEASE REVIEW AND SHOW
 COMPLIANCE EITHER BY LETTER OR BY A
 REVIEW STAMP.THE RESPONSE LETTER
 STATED THAT THE PRODUCTS WERE REVIEWED
 BUT PLEASE PROVIDE EITHER A LETTER OR
 REVIEW STAMP.
  
 16.)FROM PREVIOUS LIST, SAME PAPERWORK
 SUBMITTED WITH NO CHANGES:
  
 FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED, FAC9B72.IF A
 FLORIDA STATE PRODUCT APPROVAL IS NOT
 AVAILABLE, AND YOU HAVE SUBMITTED A NOA,
 PLEASE ADVISE AND A LOCAL PRODUCT
 APPROVAL WILL BE ISSUED.
 WWW.FLORIDABUILDING.ORG
  
 STOREFRONT SYSTEM >10',NOA 01-0228.09
 IS EXPIRED.ALSO THIS REQUIRES A
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL.
 THE NOA MUST BE CURRENT FOR A LOCAL TO
 BE ISSUED FROM THE NOA.A LOCAL PRODUCT
 APPROVAL CAN BE ISSUED WITH EITHER A
 TEST OR EVALUATION REPORT, PLEASE READ
 FAC9B72.
  
 STOREFRONT SYSTEM < 10', FLORIDA STATE
 PRODUCT APPROVAL 5844 WAS SUBMITTED.
 SUBMIT THE NOA REFERENCED ON THE STATE
 APPROVAL FOR VERIFICATION OF DESIGN
 PRESSURES AND FOR INSTALLATION
 INSTRUCTIONS IN THE FIELD.NOTE THE
 PRODUCT LIMITATION THAT PRESSURES ARE TO
 BE DIVIDED BY 1.33 OR VERIFIED BY A
 FLORIDA PE.
  
 CECO DOOR, A NOA WAS PROVIDED.A LOCAL
 PRODUCT APPROVAL HAS ALREADY BEEN ISSUED
 FOR THIS PRODUCT.PLEASE HAVE DOR
 REVIEW.
  
 ACCORDION SHUTTER, REQUIRES DOR REVIEW
 AND BACKUP AND NOA REFERENCED IN THE
 FLORIDA STATE PRODUCT APPROVAL.CIRCLE
 THE DETAILS WHICH APPLY TO THIS
 INSTALLATION.SHOW ANCHORING SPACING.
 THIS CAN BE DONE BY EITHER COMPLETING A
 SCHEDULE SUCH AS THE SAMPLE FORM
 ATTACHED OR BY CIRCLING IT ON THE
 PRODUCT APPROVAL.
  
 STOREFRONT DOOR, THE NOA PROVIDED AND
 REFERENCED ON A8-1 IS NON IMPACT.THE
 PLANS STATE IMPACT.ADDRESS.THE SHEET
 PROVIDED IS NOT A FLORIDA STATE PRODUCT
 APPROVAL, IT IS THE SEARCH RESULT.
 PROVIDE THE FLORIDA STATE PRODUCT
 APPROVAL.SEE THE OTHERS SUBMITTED AS
 THE OTHERS WERE PRINTED PROPERLY.
  
 LOUVER, PROVIDE FLORIDA STATE PRODUCT
 APPROVAL.IF ONE IS NOT AVAILABLE, A
 LOCAL WILL BE ISSUED USING THE NOA.
  
 NO PRODUCT APPROVALS FOR THE ROOF WERE
 SUBMITTED.THEY MAY BE SUBMITTED WITH
 THE ROOF PERMIT APPLICATION, BUT
 SEPARATE FEES BASED ON VALUE WILL BE
 CHARGED.
  
 ALL ITEMS APPEAR CODE COMPLIANT, BUT
 PLEASE SUBMIT ALL PAPERWORK AS
 REQUESTED.
  
 17.)FROM PREVIOUS LIST, THE ENERGY
 CALCS DIFFER IN SQUARE
 FOOTAGE, 20550 ON THE ENERGY CALC, 23000
 ON LS1.CLARIFY THE
 DISCREPANCY. YOUR RESPONSE THAT THE
 DISCREPANCY IS DUE TO WHERE THE ROOMS
 WERE MEASURED IS NOTED, BUT THEY SHOULD
 BE MEASURED FROM OUTSIDE WALLS FBC 13-2,
 DEFINITIONS, CONDITIONED FLOOR AREA,
 GROSS FLOOR AREA, FLOOR AREA.
  
 18.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALCS, FBC13-103.1.
  
 19.)ADDITIONAL FEES DUE, SEE ATTACHED
 (RADON, FS404.056, FS166.021.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-12 Cont ID  
Sent By shill Date 2006-05-12 Time 10:09 Rev Time 0.00
Received By shill Date 2006-05-10 Time 10:41 Sent To  
Notes
2006-05-12 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025.THIS APPEARS TO
 BE A CHANGE OF OCCUPANCY, FROM BUSINESS
 TO ASSEMBLY, FOR A PORTION OF THE
 BUILDING.
  
 LS1 SHOWS AN ADDITION OF 1000 SF.THIS
 SHOULD STATE WHETHER THIS IS HABITABLE
 SPACE OR NOT, AND IF IT IS, WHICH
 OCCUPANCY.IT APPEARS THAT THE ADDITION
 IS ROOF AREA ONLY, WHICH WILL NOT BE
 CALCULATED FOR IMPACT FEES BUT WHICH
 MUST BE INCLUDED FOR TABLE 503
 COMPLIANCE.
  
 3.)THE ACCESSIBLE PARKING DETAIL C7 IS
 TO COMPLY WITH CITY OF WEST PALM BEACH
 STANDARDS, SEE ATTACHED.
  
 4.)THE DUMPSTER ENCLOSURES WILL
 REQUIRE A SEPARATE PERMIT.COMPLETE A
 PERMIT APPLICATION.SEPARATE PLANS ARE
 NOT REQUIRED.
  
 5.)SEPARATE PERMIT REQUIRED FOR THE
 FENCES.SUBMIT SEPARATELY WITH PLANS.
 THIS ITEM DOES NOT NEED TO BE ADDRESSED
 PRIOR TO ISSUANCE OF THIS PERMIT, BUT
 MUST BE ADDRESSED PRIOR TO COMMENCEMENT
 OF THE FENCING WORK.INFORMATIONAL
 ONLY.
  
 6.)SP1 REFERS TO MECHANICAL SHEET ???,
 PLEASE REVISE NOTE.
  
 7.)AN EXISTING ACCESSIBLE ROUTE FROM
 THE PUBLIC WAY IS SHOWN.SHOW THE WIDTH
 AND MAX SLOPE, EITHER WITH A NOTE ON THE
 PLAN OR WITH EXISTING ELEVATIONS, TO
 SHOW COMPLIANCE WITH FBC11-4.1.2(1) AND
 (2), FBC11-4.1.6(1)(B).
  
 8.)RAMP DETAIL 3-SP2 SHOWS 5FT AT THE
 BOTTOM OF THE RAMP.SEE FBC11-4.8.4(2),
 72IN REQUIRED.
  
 9.)WHAT IS THE "EXISTING CB" SHOWN ON
 THE NEW RAMP PLAN, 01-SP2?IT IS IN THE
 ACCESS AISLE FOR THE ACCESSIBLE PARKING
 SPACE.A SEARCH OF STANDARD
 ABBREVIATIONS WAS NOT HELPFUL.IF YOU
 USE NONSTANDARD ABBREVIATIONS, PLEASE
 INCLUDE A LEGEND.
  
 10.)LS1, APPLICABLE CODES, 8-A2-3, AND
 OTHER DETAILS REFER TO ASCE7-98.THIS
 SHOULD BE ASCE7-02, FBC35.
  
 11.)LS1 CODE SUMMARY REFERS TO TABLE
 500.THIS IS TABLE 503 IN THE NEW CODE.
  
 12.)LS1, PROVIDE CALCULATIONS FOR
 ALLOWABLE AREA INCREASES TO SHOW HOW YOU
 HAVE ARRIVED AT THE ALLOWABLE AREA.
 PLANS APPEAR CODE COMPLIANT BUT HOW YOU
 HAVE ARRIVED AT CODE COMPLIANCE SHOULD
 BE CLEAR.SEE ALSO FBC302.3.2.
  
 13.)LS3, SOUTH STAIR, DOORS DO NOT
 LEAD TO AN EXIT; ONE DOOR OPENS INTO
 WHAT APPEARS TO BE A CLOSET, AND THE
 OTHER DOOR OPENS INTO THE FIRST FLOOR
 SPACE.TRAVEL DISTANCE FROM SECOND
 FLOOR FOR SECOND MEANS OF EGRESS IS NOT
 CLEAR.
  
 14.)THE PLAN SHOWS ACCORDION SHUTTERS
 ON THE SECOND FLOOR.THIS MUST BE
 APPROVED BY THE BUILDING OFFICIAL, ITEM
 #14 OF THE MISSILE IMPACT PROTECTION
 STANDARD, ATTACHED.SUBMIT AN
 INSTALLATION PLAN AS REFERENCED IN ITEM
 #13.
  
 THE PLAN MAY BE SUBMITTED SEPARATELY
 FROM THE PERMIT APPLICATION RESUBMITTAL.
 FAILURE TO GET A PLAN APPROVED PRIOR TO
 RESUBMITTAL WILL RESULT IN DELAYS IN
 PERMIT ISSUANCE.
  
 THE INSTALLATION PLAN MAY BE SUBMITTED
 VIA EMAIL FOR PRELIMINARY REVIEW TO
 [email protected] PROVIDED ALL DOCUMENTATION
 IS LEGIBLE.A HARD COPY ORIGINAL SIGNED
 BY ALL PARTIES AFTER ALL COMMENTS HAVE
 BEEN ADDRESSED WILL BE REQUIRED FOR
 APPROVAL BY THE BUILDING OFFICIAL.
  
 15.)PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DOR, FBC*106.3.3.SOME ARE
 REFERENCED SPECIFICALLY ON THE PLAN
 (SUCH AS ON A8-1), BUT OTHERS (SUCH AS
 THE ROOF PRODUCTS) ARE NOT.FOR
 PRODUCTS NOT REFERENCED BY NOA NUMBER ON
 THE PLAN, PLEASE REVIEW AND SHOW
 COMPLIANCE EITHER BY LETTER OR BY A
 REVIEW STAMP.
  
 16.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED, FAC9B72.IF A
 FLORIDA STATE PRODUCT APPROVAL IS NOT
 AVAILABLE, AND YOU HAVE SUBMITTED A NOA,
 PLEASE ADVISE AND A LOCAL PRODUCT
 APPROVAL WILL BE ISSUED.
 WWW.FLORIDABUILDING.ORG
  
 STOREFRONT SYSTEM >10',NOA 01-0228.09
 IS EXPIRED.ALSO THIS REQUIRES A
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL.
 THE NOA MUST BE CURRENT FOR A LOCAL TO
 BE ISSUED FROM THE NOA.A LOCAL PRODUCT
 APPROVAL CAN BE ISSUED WITH EITHER A
 TEST OR EVALUATION REPORT, PLEASE READ
 FAC9B72.
  
 STOREFRONT SYSTEM < 10', FLORIDA STATE
 PRODUCT APPROVAL 5844 WAS SUBMITTED.
 SUBMIT THE NOA REFERENCED ON THE STATE
 APPROVAL FOR VERIFICATION OF DESIGN
 PRESSURES AND FOR INSTALLATION
 INSTRUCTIONS IN THE FIELD.NOTE THE
 PRODUCT LIMITATION THAT PRESSURES ARE TO
 BE DIVIDED BY 1.33 OR VERIFIED BY A
 FLORIDA PE.
  
 CECO DOOR, A NOA WAS PROVIDED.A LOCAL
 PRODUCT APPROVAL HAS ALREADY BEEN ISSUED
 FOR THIS PRODUCT.PLEASE HAVE DOR
 REVIEW.
  
 ACCORDION SHUTTER, REQUIRES DOR REVIEW
 AND BACKUP AND NOA REFERENCED IN THE
 FLORIDA STATE PRODUCT APPROVAL.CIRCLE
 THE DETAILS WHICH APPLY TO THIS
 INSTALLATION.SHOW ANCHORING SPACING.
 THIS CAN BE DONE BY EITHER COMPLETING A
 SCHEDULE SUCH AS THE SAMPLE FORM
 ATTACHED OR BY CIRCLING IT ON THE
 PRODUCT APPROVAL.
  
 STOREFRONT DOOR, THE NOA PROVIDED AND
 REFERENCED ON A8-1 IS NON IMPACT.THE
 PLANS STATE IMPACT.ADDRESS.THE SHEET
 PROVIDED IS NOT A FLORIDA STATE PRODUCT
 APPROVAL, IT IS THE SEARCH RESULT.
 PROVIDE THE FLORIDA STATE PRODUCT
 APPROVAL.SEE THE OTHERS SUBMITTED AS
 THE OTHERS WERE PRINTED PROPERLY.
  
 LOUVER, PROVIDE FLORIDA STATE PRODUCT
 APPROVAL.IF ONE IS NOT AVAILABLE, A
 LOCAL WILL BE ISSUED USING THE NOA.
  
 NO PRODUCT APPROVALS FOR THE ROOF WERE
 SUBMITTED.THEY MAY BE SUBMITTED WITH
 THE ROOF PERMIT APPLICATION, BUT
 SEPARATE FEES BASED ON VALUE WILL BE
 CHARGED.
  
 17.)THE ENERGY CALCS DIFFER IN SQUARE
 FOOTAGE, 20550 AND 19375.CLARIFY THE
 DISCREPANCY.
  
 18.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALCS, FBC13-103.1.
  
 19.)ADDITIONAL FEES DUE, SEE ATTACHED
 (RADON, FS404.056, FS166.021.
  
 WHEN RESUBMITTING, PROVIDE A RESPONSE
 LETTER STATING HOW EACH ITEM WAS
 ADDRESSED.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-02-14 Cont ID  
Sent By dpalmer Date 2007-02-14 Time 12:46 Rev Time 0.00
Received By dpalmer Date 2007-02-14 Time 12:13 Sent To PC
Notes
2007-02-14 12:47:22REV FOR 2ND FLR AND PANEL/LCP SCHEDULES

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-12-08 Cont ID  
Sent By dpalmer Date 2006-12-08 Time 21:01 Rev Time 0.00
Received By dpalmer Date 2006-12-08 Time 20:23 Sent To  
Notes
2006-12-08 21:02:39REDLINED NOTES ON LIGHTING PLANS FOR LOUNGE. LIGHTING
 CONTROL REQUIRED WHICH APPEARS TO BE MISSING PER
 13-415.1.ABC.1.2

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-09-29 Cont ID  
Sent By dpalmer Date 2006-09-29 Time 12:26 Rev Time 0.00
Received By dpalmer Date 2006-09-29 Time 12:26 Sent To  
Notes
2006-09-29 00:00:00NEW ENERGY CALCULATIONS SUBMITTED BY
 ENGINEER ON 9/28/06 ALONG WITH SIGNED
 AND SEALED LPD'S. OK
 INFORMED BLDG REVIEWER OF NEW ENERGY
 CALCULATIONS TO BE REVIEWED.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-09-17 Cont ID  
Sent By dpalmer Date 2006-09-17 Time 16:57 Rev Time 0.00
Received By dpalmer Date 2006-09-17 Time 16:23 Sent To  
Notes
2006-09-17 00:00:00*** UNSAT ***
  
 ** PLANS ARE TEMPORARILY FAILED FOR
 ELECTRICAL REVIEW.
  
 1) NOTE: PLEASE TWO DIFFERENT SETS OF
 FLORIDA ENERGY CALCULATIONS WERE
 SUBMITTED. PLEASE SEE EACH SHOW
 DIFFERENT SQ FT?
 PLEASE SEE EACH, ONLY ONE SIGNED, DATED
 AND SEALED BY THE ENGINEER FOR DESIGNS.
 PLEASE SEE CONTROLS FOR LIGHTING ARE
 LISTED AS MANUAL /ON/OFF??
  
 PLEASE SEE AT THIS TIME THE LIGHTING
 POWER USEAGE APPEARS IT MAY BE OK, BUT
 IT IS UNCLEAR AT THIS TIME.
  
 2) NOTE: PLEASE SUBMIT MANUFACTURE'S
 SPEC/CUT SHEETS FOR THE NEW PROPOSED
 LIGHTING CONTROL SYSTEM(S). PLEASE
 SUBMIT A LAYOUT FOR EACH SYSTEM ,AND
 ZONE, FOR FLR AND EACH LEVEL.
  
 ELECTRICAL PLANS ARE OK, AS LONG AS
 FIXTURES REMAINS THE SAME.
  
 **PLEASE AHVE ENGINEER OF RECORD CALL TO
 GO OVER THESE COMMENTS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 DPALMER2WPB.ORG

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-16 Cont ID  
Sent By dpalmer Date 2006-07-16 Time 10:46 Rev Time 0.00
Received By dpalmer Date 2006-07-16 Time 08:41 Sent To  
Notes
2006-07-16 00:00:00********* UNSAT2ND REVIEW *********
  
 ** PLEASE SEE COMMENTS BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
  
  
 1) NOTE: NO, PLEASE SEE RESPONSE
 MENTIONS THIS IS COMPLIED WITH, HOWEVER
 PLANS DO NOT INDICATE ANY SYSTEM FOR THE
 FIRST FLOOR OR 2NF FLR AS EACH FLR SHALL
 BE SEAPARATE. PLEASE SEE MOST ROOMS
 WHICH ARE CONSIDERED "SEPARATE SPCES"
 WITH FLOOR TO CEILING HEIGHT PARTITIONS
 ALSO REQUIRE SEPARATE CONTROLS WHICH
 WOULD OVER RIDE ANY TIME OF DAY
 SCHEDULEING ETC. PLEASE ALSO SEE OVER
 RIDE DEVICE LOCATIONS ARE REQUIRED TO BE
 SHOWN ON PLANS AT LOCATIONS AT THE PINT
 OF ENTRANCE(S) TO SPACE(S)AND HAVE
 VISABILITY OF LIGHTING IN WHICH THE OVER
 RIDE DEVICE CONTROLS.
 COULD NOT LOCATE THE VOLTAGE DROP WORST
 CASE FOR LONGER RUNS, (SITE LIGHTING)?
 PLEASE CLARIFY THE LIGHTING POWER
 DENSITIES (LPD). THE ENERGY CALCS SEEM
 TO INDICATE LIGHTING POWER DESIGN AT
 18,688 AND 23,760 ALLOWED, PLEASE
 CLARIFY THE LPD USED. PLEASE ALSO SEE
 CONTROLS MENTIONS MANUAL ON/OFF??
 PLEASE SEE 13-415.1.ABC.1.1, .1.2,.1.3,
 13-415.1.AB.1,13-415.1.ABC.1
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS ARE COMING IN
 UNDER THE 2004 FBC. PLEASE SEE CHAPTER
 13, 13-413.1ABC.1. FOR VOLTAGE DROP
 CALCS TO BE PROVIDED FOR WORST CASE
 SCENERIO.
 PLEASE SEE 13-415.1.ABC.1.1,
 13-415.1.ABC.1.2, 13-415.1.ABC.1.3,
 PLEASE PROVIDE ALL INFORMATION FOR
 LIGHTING CONTROL SYSTEM, TIME OF DAY,
 TYOE OF DEVICES, SYSTEMS ETC.
 INDICATE THE SECTION(S) AND PLEASE SEE
 MULTIPLE FLOOR REQUIREMENTS FOR
 ADDTIONAL CONTROLS.
 PLEASE SEE 13-413.1.ABC.2.2
 PLESASE SEE 13-415.1.ABC.3
  
  
 2) NOTE: OK.
  
 3) NOTE: NO, PLEASE SEE THIS WAS ONLY
 CHANGED ON "A" SHEETS. PLEAS KNOW, DUE
 TO REVISIONS ON ELECTRICAL SHEETSWHICH
 SOME WERE REVISED AND SOME WERE NOT,
 PLEASE BE SURE TO CHANGE THE DOOR SWING.
  
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MAIN ELECTRICAL ROOM
 DOOR SHALL OPEN OUTWARD AND BE EQUIPPED
 WITH PANIC HARDWARE.
 110.26
  
 4) NOTE: OK, REVISED FIX TYPE.
  
  
 5) NOTE: OK.
  
 6) NOTE: OK.
  
 7) NOTE: NO/YES, PLEASE SEE RISER STILL
 ONLY MENTIONS IN NOTES THAT THE
 GROUNDING ELECTRODE SYSTEM PER NEC AND
 NOTE FOR TRANSFORMER ALSO MENTIONS PER
 NEC. PLEASE SEE THESE NOTES SHOULD
 REFERENCE THE DETAILS ON 7-1. PLEASE
 REVISE NOTES.
 PLEASE ALSO KNOW, EXISTING FOOTER STEEL
 WILL NOT BE REQUIRED TO BE PART OF THE
 GROUNDING ELECTRODE SYSTEM UNLESS A STUB
 OUT IS ALREADY PROVIDED. IT IS NOT THE
 INTENTION TO AFFECT THE STRUCTURAL
 INTEGRITY OF THE EXISTING FOOTER.
 ** PLEASE SEE ORIG PLANS WERE REDLINED
 FOR THE "EQUIPMENT GROUNDING CONDUCTOR"
 SHOWN BEING INSTALLED FROM FPL TO THE
 MSB MAIN, HOWEVER WAS NOT SPECIFICALLY
 TYPE IN NOTES. PLEASE SEE 250.24B,
 250.6, THE "EQUIPMENT GROUNDING
 CONDUCTOR" IS ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISCONNECT.
  
 ** PREVIOUS REVIEW NOTE **
 PLASE SEE NO GROUNDING ELECTRODE SYSTEM
 WAS SHOWN. PLEASE SUBMIT A COMPLETE
 DETAIL PER 250.50, 250.52 ETC.
 PLEASE ALSO INDICATE THE ATTACHMENT
 LOCATIONS FOR THE TRANSFORMER PER
 250.30,250.66
  
 8) NOTE: OK.
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
 11) NOTE:OK.
 ** ONLY A NOTE **
 PLEASE SEE RATINGS ON SUB PANELS/BRNACH
 BRKRS ARE STILL BEING SHOWN 65K, ONLY
 ONE PANEL WAS REVISED FOR A 35K RATING.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE AIC RATING
 FOR ALL SERVICE EQUIPMENT. PLEASE SEE
 TWO DIFFERENT RATINGS ARE SHOWN FOR MSB.
 PLEASE ALSO CLARIFY THE 65K RAITNGS
 INDICATE DFOR PANELS,AS THIS SEEMS HIGH,
 HOWEVER THIS IS PERMITTED. PLEASE
 INDICATE THE RATINGS OF THE BRANCH
 BRKRS.
  
 12) NOTE: OK.
  
  
 ** PLEASE KNOW, A DETAILED RESPONSE TYPE
 WRITTEN LTR FROM THE DESIGN PROFESSIONAL
 WILL HELP IN THE REVIEW PROCESS WHEN
 RESUBMITTING PLANS.
  
 ** PLEASE ALSO KNOW, WHEN RESUBMITTING
 PLANS, ALL OLD/VOIDED SHEETS MUST BE
 COMPLETELY REMOVED FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING. PLEASE
 KNOW, ONE COPY OF THE OLD/VOIDED REMOVED
 SHEETS SHOULD BE SUBMITTED WITH THE
 RESUBMITTED PLANS.
  
 ** PLEASE BE SURE TO SEE ANY OTHER
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THISOFFICE.
  
 DEWEY PALMER
 EELCTRICAL PLAN REVIEW.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-17 Cont ID  
Sent By dpalmer Date 2006-05-17 Time 21:53 Rev Time 0.00
Received By dpalmer Date 2006-05-17 Time 21:07 Sent To  
Notes
2006-05-17 00:00:00IN ELEC FOR REVIEW.
 ********* UNSAT ***********
  
 1) NOTE: PLEASE SEE PLANS ARE COMING IN
 UNDER THE 2004 FBC. PLEASE SEE CHAPTER
 13, 13-413.1ABC.1. FOR VOLTAGE DROP
 CALCS TO BE PROVIDED FOR WORST CASE
 SCENERIO.
 PLEASE SEE 13-415.1.ABC.1.1,
 13-415.1.ABC.1.2, 13-415.1.ABC.1.3,
 PLEASE PROVIDE ALL INFORMATION FOR
 LIGHTING CONTROL SYSTEM, TIME OF DAY,
 TYOE OF DEVICES, SYSTEMS ETC.
 INDICATE THE SECTION(S) AND PLEASE SEE
 MULTIPLE FLOOR REQUIREMENTS FOR
 ADDTIONAL CONTROLS.
 PLEASE SEE 13-413.1.ABC.2.2
 PLESASE SEE 13-415.1.ABC.3
  
  
 2) NOTE: PLEASE CORRELATE EXITING, AND
 EGRESS PATHS LTS WITH FIXTURE SCHEDULE
 AS SOME FIXTURES DO NOT CONTAIN BATTEY
 BACK UP WHERE REQUIRED.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2,
 WHERE STAIRS ARE NOW REQUIRED TO HAVE
 10FT CANDLES UNDER NORMAL AND 1FT CANDLE
 UNDER EM CONDITIONS. PLEASE PROVIDE
 COMPLETE PHOTOMETRICS FOR ALL EGRESS
 PATHS. PLEASEKNOW, THE STAIRS CAN BE A
 "TYPICAL DETAIL". ONE SHWOING NORMAL,
 ONE SHOWING EM.
 PLEASE ALSO SEE FIRE REVIEW COMMENTS AS
 ONE TYPE OF FIXTURE SEEMS TO SHOW ONLY
 30 MIN??
  
 3) NOTE: PLEASE SEE MAIN ELECTRICAL ROOM
 DOOR SHALL OPEN OUTWARD AND BE EQUIPPED
 WITH PANICA HARDWARE.
 110.26
  
 4) NOTE: PLEASE SEE THE MAIN ELECTRICAL
 ROOM WILL BE REQUIRED TO CONTAIN A MIN
 OF ONE BATTERY BACK UP TYPE OF FIXTURE.
 700.16, 7.8,7.8
  
 5) NOTE: PLEASE SEE MISSING RECEPT PER
 210.63, 210.8 FOR A/C EQUIPMENT
  
 6) NOTE: PLEASE SEE 620.23, 620.24, AS
 ELEVATOR EQUIPMENT RMS AND ELEV SHALL
 HAVE DEDICATED CIRCUITS AS REQUIRED.
 PLEASE SEE SOME OF THESE ITEMS ARE SHOWN
 CIRCUITED TO STAIR LTS??
  
 7) NOTE: PELASE SEE NO GROUNDING
 ELECTRODE SYSTEM WAS SHOWN. PLEASE
 SUBMIT A COMPLETE DETAIL PER
 250.50,250.52 ETC.
 PLEASE ALSO INDICATE THE ATTACHMENT
 LOCATIONS FOR THE TRANSFORMER PER
 250.30,250.66
  
 8) NOTE: PLEASE TYPE AND USE OF THE
 TRANSFORMER AS RISER INDICATE THIS BEING
 USED FROM 120/208V 3-PHASE TO 120/208V
 3-PHASE??
  
 9) NOTE: PLEASE SEE MSB IS SHOWN AS
 "GFI" PROTECTED?? PLEASE KNOW, IF
 MEETING THE REQUIREMENTS OF
 230.95,240.13 ETC, THIS WOULD BE GF
 PROTECTED. "GFI" IS FOR PERSONNEL.
 PLEASE CLARIFY THE GF PROTECION AS THIS
 IS SHOWN AS 120/208V??
  
 10) NOTE: PLEASE VERIFY MAIN FOR MSB.
 PLEASE SEE ONE END OF THIS EQUIPMENT IS
 SHOWN AS MLO, INDICATE MORE THAN 6
 SPACES AND 6 MAINS. 230.70,230.71??
 PLEASE SEE THE OTHER SEEMS TO INDICATE A
 MCB BUT THIS IS UNCLEAR. PLEASE NOTE AND
 INDICATE THIS MCB, CONTAINING A MANUAL
 MEANS OF DISCONNECT LOCATED ON THE
 OUTSIDE OF THIS EQUIPMENT, RATED FOR THE
 LOAD SERVED PER 230.76,230.79
  
 11) NOTE: PLEASE SUBMIT THE AIC RATING
 FOR ALL SERVICE EQUIPMENT. PLEASE SEE
 TWO DIFFERENT RATINGS ARE SHOWN FOR MSB.
 PLEASE ALSO CLARIFY THE 65K RAITNGS
 INDICATE DFOR PANELS,AS THIS SEEMS HIGH,
 HOWEVER THIS IS PERMITTED. PLEASE
 INDICATE THE RATINGS OF THE BRANCH
 BRKRS.
  
 12) NOTE: PLEASE SUBMIT WIND LOAD
 CALCULATIONS FOR LT POLES TO MEET FBC
 140.
  
 ** PLEASE KNOW, A DETAILED RESPONSE TYPE
 WRITTEN LTR FROM THE DESIGN PROFESSIONAL
 WILL HELP IN THE REVIEW PROCESS WHEN
 RESUBMITTING PLANS.
  
 ** PLEASE ALSO KNOW, WHEN RESUBMITTING
 PLANS, ALL OLD/VOIDED SHEETS MUST BE
 COMPLETELY REMOVED FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING. PLEASE
 KNOW, ONE COPY OF THE OLD/VOIDED REMOVED
 SHEETS SHOULD BE SUBMITTED WITH THE
 RESUBMITTED PLANS.
  
 ** PLEASE BE SURE TO SEE ANY OTHER
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THISOFFICE.
  
 DEWEY PALMER
 EELCTRICAL PLAN REVIEW.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2007-01-05 Cont ID  
Sent By rchokshi Date 2007-01-05 Time 10:53 Rev Time 0.00
Received By rchokshi Date 2007-01-05 Time 10:51 Sent To  
Notes
2007-01-05 10:52:57NOTHING CHANGED FROM PREVIOUS DRAWINGS WHEN APPROVED.
  
  
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2006-10-17 Cont ID  
Sent By rchokshi Date 2006-10-17 Time 08:22 Rev Time 0.00
Received By rchokshi Date 2006-10-17 Time 08:20 Sent To  
Notes
2006-10-17 08:22:46PASSED ON 10/17/06,MANNY G. COMPLETED UTILITY REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2006-09-20 Cont ID  
Sent By rchokshi Date 2006-09-20 Time 14:44 Rev Time 0.00
Received By rchokshi Date 2006-09-20 Time 14:40 Sent To  
Notes
2006-09-20 00:00:00UTILITY REVIEW IS NOT COMPLETE AS OF
 9/20/06 PER MANNY G.(45TH STREET)
  
 EVERYTHING ELSE IS O.K.
  
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2006-08-08 Cont ID  
Sent By rchokshi Date 2006-08-08 Time 15:28 Rev Time 0.00
Received By rchokshi Date 2006-08-08 Time 15:16 Sent To  
Notes
2006-08-08 00:00:00NEED THE FOLLOWINGS:
 1. POLLUTION PREVENTION PLAN, DETAILS,
 BEFORE,DURING,& AFTER CONSTRUCTION
 2. DUMPSTER ENCLOSURE DETAILS MUST MEET
 CITY OF WPB STANDARDS
 3. STORM/DRAINAGE
 CAL.,PERVIOUS,IMPERVIOUS AREA
 CAL.,RUNOFF WATER CAL., CONTROL
 STUCTURES DETAIL,GEOTECHNICAL ENG.
 REPORT,SFWMD PERMIT,
 4. UTILITY REVIEW FROM 45TH STREET ENG.
 SERVICES, FROM MANNY G.
 5. ALL DETAILS ON SIDEWALK,
 DRIVEWAY,PARKINGS, MUST MEET CITY OF WPB
 STANDARD NOTES ON DRAWINGS.
 6. ALL NEW FLOOR ELEVATION MUST MEET
 FBC.
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-03-27 Cont ID  
Sent By mawillia Date 2007-03-27 Time 15:18 Rev Time 0.00
Received By mawillia Date 2007-03-27 Time 14:36 Sent To B
Notes
2007-03-27 15:12:06*****REVISION APPROVED*****
  
  
 REVIEWED REVISED PLAN SHEETS A1-3, A1-4, AND A3.2;
 PLAN SHEET A-3.2 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-02-07 Cont ID  
Sent By mwennerg Date 2007-02-07 Time 11:38 Rev Time 0.00
Received By mwennerg Date 2007-02-07 Time 11:38 Sent To  
Notes
2007-02-07 11:42:24***APPROVED***
  
 1) PLANS WERE APPROVED PREVIOUSLY, AND STAMPED AT THIS
 TIME. ANY SHEETS SUBMITTED FOR REVIEW FOR ANY FIRE
 PROTECTION SYSTEMS TO BE SUBMITTED UNDER THAT SPECIFIC
 PERMIT.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 (561) 805-6722 OR 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-10-17 Cont ID  
Sent By mawillia Date 2006-10-17 Time 12:29 Rev Time 0.00
Received By mawillia Date 2006-10-17 Time 12:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-07-12 Cont ID  
Sent By mcarsill Date 2006-07-12 Time 12:02 Rev Time 0.00
Received By mcarsill Date 2006-07-12 Time 11:41 Sent To  
Notes
2006-07-12 00:00:001. PROPOSED FIRE HYDRANT SHALL MEET ALL
 REQUIREMENTS WITH REGARDS TO CLEARANCES
 TO THE FRONT, SIDES, AND REAR OF IT.
  
 2. NEW PROPOSED FIRE HYDRANT SHALL MEET
 MINIMUM UTILITY AND FIRE RESCUE
 STANDARDS.
  
 3. ALL WORK SHALL BE SUBJECT TO FIELD
 INSPECTION AND APPROVAL.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-06-07 Cont ID  
Sent By mwennerg Date 2006-06-07 Time 13:15 Rev Time 0.00
Received By mwennerg Date 2006-06-07 Time 13:15 Sent To  
Notes
2006-06-07 00:00:00***DENIED***
  
 1) PLEASE PROVIDE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS IN ACCORDANCE WITH NFPA 101,
 CHAPTER 10.
  
 2) IN ADDITION TO FIRE SPRINKLER,
 SEPARATE SHOP DRAWINGS AND PERMIT
 REQUIRED FOR FIRE ALARM REMODEL.
  
 3) RAMPS TO COMPLY WITH APPLICABLE
 BUILDING CODES, AND NFPA 101, SECTION
 7.2.5.
  
 4) PLEASE CLARIFY THE OCCUPANT LOAD FOR
 LECTURE HALL. USING THE CONCENTRATED
 FACTOR, IT WOULD APPEAR WILL NOT SUPPORT
 THE SEATING ILLUSTRATION.
  
 5) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 6) KNOX BOX APPLICATION CAN BE OBTAINED
 AT THE BUREAU OF FIRE PREVENTION.
  
 7) PLEASE SHOW ADDRESS ON BUILDING, NEW
 OR EXISTING THAT SHALL BE MINIMUM OF 6"
 IN HEIGHT AND CONTRASTING TO BACKGROUND.
  
  
 8) WILL CARD ACCESS SYSTEM IMPACT
 REQUIRED MEANS OF EGRESS?
  
 9) EMERGENCY LIGHT BACK UP SYSTEMS SHALL
 BE MAINTAINED FOR MINIMUM OF 90 MINUTES.
  
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2007-09-28 Cont ID  
Sent By adarroug Date 2007-09-28 Time 11:07 Rev Time 0.00
Received By adarroug Date 2007-09-28 Time 11:07 Sent To Z
Notes
2007-09-28 11:08:16TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2007-09-11 Cont ID  
Sent By adarroug Date 2007-09-11 Time 14:16 Rev Time 0.00
Received By adarroug Date 2007-09-11 Time 14:16 Sent To B
Notes
2007-09-11 14:16:16TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2007-06-29 Cont ID  
Sent By adarroug Date 2007-06-29 Time 09:13 Rev Time 0.00
Received By adarroug Date 2007-06-29 Time 09:13 Sent To M
Notes
2007-06-29 09:13:48TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2007-05-18 Cont ID  
Sent By adarroug Date 2007-05-18 Time 10:31 Rev Time 0.00
Received By adarroug Date 2007-05-18 Time 10:30 Sent To M
Notes
2007-05-18 10:31:26TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-05-15 Cont ID  
Sent By adarroug Date 2007-05-15 Time 14:14 Rev Time 0.00
Received By adarroug Date 2007-05-15 Time 14:14 Sent To P
Notes
2007-05-15 14:14:25TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-04-30 Cont ID  
Sent By adarroug Date 2007-04-30 Time 11:19 Rev Time 0.00
Received By adarroug Date 2007-04-30 Time 11:19 Sent To M
Notes
2007-04-30 11:20:04TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-03-21 Cont ID  
Sent By adarroug Date 2007-03-21 Time 09:36 Rev Time 0.00
Received By adarroug Date 2007-03-21 Time 09:36 Sent To FIRE
Notes
2007-03-21 09:37:41TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-03-14 Cont ID  
Sent By adarroug Date 2007-03-14 Time 09:06 Rev Time 0.00
Received By adarroug Date 2007-03-14 Time 09:06 Sent To B
Notes
2007-03-14 09:07:26TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-03-14 Cont ID  
Sent By adarroug Date 2007-03-14 Time 09:01 Rev Time 0.00
Received By adarroug Date 2007-03-14 Time 09:01 Sent To M
Notes
2007-03-14 09:01:55TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-03-03 Cont ID  
Sent By adarroug Date 2007-03-03 Time 17:46 Rev Time 0.00
Received By adarroug Date 2007-03-03 Time 17:46 Sent To M
Notes
2007-03-03 17:47:10TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-02-12 Cont ID  
Sent By adarroug Date 2007-02-12 Time 08:36 Rev Time 0.00
Received By adarroug Date 2007-02-12 Time 08:36 Sent To E
Notes
2007-02-12 08:36:33TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-01-31 Cont ID  
Sent By adarroug Date 2007-01-31 Time 15:03 Rev Time 0.00
Received By adarroug Date 2007-01-31 Time 15:03 Sent To M
Notes
2007-01-31 15:04:03TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-27 Cont ID  
Sent By adarroug Date 2006-11-27 Time 14:06 Rev Time 0.00
Received By adarroug Date 2006-11-27 Time 14:06 Sent To  
Notes
2006-12-08 15:14:41TO "COMM" BD#33
2006-11-27 14:06:40WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-31 Cont ID  
Sent By adarroug Date 2006-08-31 Time 14:01 Rev Time 0.00
Received By adarroug Date 2006-08-31 Time 14:01 Sent To  
Notes
2006-09-15 00:00:00TO "COMM" BD#3/PLANS ON RACK-4 ROLLS AND
 BINDERS
2006-08-31 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-30 Cont ID  
Sent By adarroug Date 2006-06-29 Time 14:21 Rev Time 0.00
Received By adarroug Date 2006-06-29 Time 14:21 Sent To  
Notes
2006-07-05 00:00:00TO "COMM" BD#59
2006-06-30 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-06-07 Time   Rev Time 0.00
Received By adarroug Date 2006-03-30 Time 16:38 Sent To  
Notes
2006-04-18 00:00:00TO "COMM" BD#39
2006-03-30 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2007-07-03 Cont ID  
Sent By tgordon Date 2007-07-03 Time 10:02 Rev Time 0.25
Received By tgordon Date 2007-07-03 Time 10:02 Sent To  
Notes
2007-07-03 10:03:37REVISION TO MECH. PLANS PAGES M2-1 AND M2-2.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2007-05-18 Cont ID  
Sent By tgordon Date 2007-05-18 Time 14:08 Rev Time 0.40
Received By tgordon Date 2007-05-18 Time 14:08 Sent To  
Notes
2007-05-18 14:09:40REVISION TO MECHANICAL PLANS PAGES M2-1 AND M2-2.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2007-05-01 Cont ID  
Sent By tgordon Date 2007-05-01 Time 08:07 Rev Time 0.45
Received By tgordon Date 2007-05-01 Time 08:07 Sent To  
Notes
2007-05-01 08:09:00REVISION TO MECH. PLANS PAGES M2-1 AND M2-2.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-03-19 Cont ID  
Sent By tgordon Date 2007-03-19 Time 08:07 Rev Time 0.30
Received By tgordon Date 2007-03-19 Time 08:07 Sent To  
Notes
2007-03-19 08:08:18REVISION TO MECH. PLANS PAGE M0-1.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-03-05 Cont ID  
Sent By tgordon Date 2007-03-05 Time 14:31 Rev Time 0.30
Received By tgordon Date 2007-03-05 Time 14:31 Sent To  
Notes
2007-03-05 14:32:33REVISION TO MECHANICAL PLANS PAGE M2-1.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rregueir Date 2007-02-09 Time 10:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-08-17 Cont ID  
Sent By hmoser Date 2006-08-17 Time 10:56 Rev Time 0.00
Received By hmoser Date 2006-08-17 Time 15:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-06 Cont ID  
Sent By hmoser Date 2006-06-06 Time 09:40 Rev Time 0.00
Received By hmoser Date 2006-06-06 Time 09:40 Sent To  
Notes
2006-06-06 00:00:00PLAN DENIED
 1) PLEASE PROVIDE TYPE OF MATERIALS USED
 FOR CHILL WATER PIPING ON THE PLANS.
 2)NEED RETURN AIR FOR ROOMS 119,127 PER
 SECTION 601.4 FBC (M) 2004.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 5 Status P Date 2007-06-07 Cont ID  
Sent By kstevens Date 2007-06-07 Time 12:20 Rev Time 0.00
Received By kstevens Date 2007-06-07 Time 12:09 Sent To  
Notes
2007-06-07 12:29:48REVISION OK --ADDED PIPING DWV AND WATER HOT & COLD
 AND 1 NEW SINK. PIPING FOR 1 FUTURE CONNECTION TO SINK.
 SHTS P2-1, P3-1, P4-1, P4-2

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-01-13 Cont ID  
Sent By kstevens Date 2007-01-13 Time 16:04 Rev Time 0.00
Received By kstevens Date 2007-01-13 Time 16:04 Sent To  
Notes
2007-01-13 16:54:50REVISION OK -SHTS IR-1, IR-2 (NEW SHEET) P2-1, P2-2,
 P3-1, P4-1, P4-2,

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-09-28 Cont ID  
Sent By kstevens Date 2006-09-28 Time 18:52 Rev Time 0.00
Received By kstevens Date 2006-09-28 Time 18:52 Sent To  
Notes
2006-09-28 00:00:00PASSED/PROVISO
  
 SEE SHT A2-1 FOR ROOF DRAIN SIZE AND
 HORIZONTAL STORM PIPE SIZE FOR AREAS
 CHANGED BY UPPER ROOFS AND ADDED
 VERTICAL CONTRIBUTION.

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-08-11 Cont ID  
Sent By kstevens Date 2006-08-11 Time 16:15 Rev Time 0.00
Received By kstevens Date 2006-08-11 Time 16:15 Sent To  
Notes
2006-08-11 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A. FROM PREVIOUS REVIEW:
  
 1. SURVEY SHEET 1 OF 1 PER FS 472.025
 ALL FINAL DRAWINGS, PLANS ETC. PREPARED
 BY THE REGISTRANT SHALL BE SIGNED,
 SEALED, AND DATED BY THE RESISTRANT.
 ****RESPONSE NOTED, BUT SURVEY SUBMITTED
 HAS NOT CHANGED AND IS NOT SIGNED,
 SEALED, AND DATED.
  
 2. OK
  
 3. SHT A2.1 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS AS
 REQUIRED IN SECTIONS 1106 & 1107 WITH
 ALL SUBSECTIONS. SHOW THE SF OF EACH
 AREA BEING DRAINED, ALONG WITH 1/2 THE
 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS, AND SHOW THE AREAS OF ROOFS
 THAT DRAIN ONTO THE ROOF AREAS FROM
 ABOVE IN CLACULATIONS. - IT APPEARS THAT
 NEW AREA WILL BE ADDED TO THE ROOF AREAS
 IN THE FORM OF NEW ROOF/WALL AREAS AT
 ENTRANCES.
 ****RESPONSE NOTED, BUT CALCULATIONS
 WERE NOT FOUND, AND LOCATION OF
 CALCULATIONS NOT INDICATED IN RESPONSE.
  
 4. SHT A2.1 THE NEW OVERFLOW SCUPPERS
 SIZING CAN NOT BE DETERMINED WITHOUT
 REFERENCE TO THE DEFLECTION OF THE ROOF.
 PLEASE INDICATE THAT SCUPPERS WERE SIZED
 TO COMPLY WITH SECTIONS 1101.7, 1107.3 &
 TABLE 1106.7.
 ****RESPONSE NOTED, BUT HEIGHT AND WIDTH
 OF OVERFLOW SCUPPERS ARE REQUIRED TO
 DETERMINE THE AREA OF THE SCUPPER.
  
 5. SHT A6-1 THE FOLLOWING INFORMATION IS
 REQUIRED TO SHOW COMPLIANCE WITH
 ACCESSIBILITY:
 FOR DRINKING FOUNTAINS:
 A. 11-4.15.5 CLEAR FLOOR SPACE
 ****NOT ADDRESSED, NO RESPONSE
 FOR W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 ****NOT ADDRESSED, NO RESPONSE
 B. 11-4.16.6 DISPENSERS
 ****NOT ADDRESSED, NO RESPONSE
 FOR TOILET STALLS:
 A. 11-4.17.3 (EXCEPTION) LAV SHALL BE
 LOCATED 60" OFF W/C WALL TO SIDE OF THE
 FIXTURE PER FIGURE 30E. IT SCALES OUT TO
 BE APPROXIMATELY 58".
 ****NOT ADDRESSED, NO RESPONSE
 FOR URINALS:
 A. 11-4.18.2 HEIGHT
 ****NOT ADDRESSED, NO RESPONSE
 B. 11-4.18.3 CLEAR FLOOR SPACE
 ****NOT ADDRESSED, NO RESPONSE
 C. 11-4.18.4 FLUSH CONTROLS
 ****NOT ADDRESSED, NO RESPONSE
 FOR LAVS:
 A. 11-4.19.3 CLEAR FLOOR SPACE
 ****NO RESPONSE, BUT CLEAR FLOOR SPACE
 IS NOT INDICATED IN TOILET ROOMS 162,
 163.
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 ****NOT ADDRESSED, NO RESPONSE
 C. 11-4.19.5 FAUCETS
 ****NOT ADDRESSED, NO RESPONSE
 FOR THE TOILET ROOMS:
 A. 11-4.22.3 UNOBSTRUCTED TURNING IN
 TOILET ROOM. (NOT IN STALLS).
 ****NO RESPONSE, NOT ADDRESSED. SEE
 TOILET ROOMS 129, & 131.
  
 6. SHT A9.4 DETAILS 03, 04, 05, & 06
 SHOW THE FOLLOWING TO SHOW COMPLIANCE:
  
 A. OK
 B. OK
  
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 ****NOT ADDRESSED, NO RESPONSE
  
 7. OK
 8. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-06-03 Cont ID  
Sent By kstevens Date 2006-06-03 Time 09:37 Rev Time 0.00
Received By kstevens Date 2006-06-01 Time 18:50 Sent To  
Notes
2006-06-03 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SURVEY SHEET 1 OF 1 PER FS 472.025
 ALL FINAL DRAWINGS, PLANS ETC. PREPARED
 BY THE REGISTRANT SHALL BE SIGNED,
 SEALED, AND DATED BY THE RESISTRANT.
  
 2. SHT D-1 KEY NOTES #8, IN THE
 INSTALLATION OR REMOVAL OF ANY PART OF A
 DRAINAGE SYSTEM, DEAD ENDS SHALL BE
 PROHIBITED. SECTION 704.5.
  
 3. SHT A2.1 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS AS
 REQUIRED IN SECTIONS 1106 & 1107 WITH
 ALL SUBSECTIONS. SHOW THE SF OF EACH
 AREA BEING DRAINED, ALONG WITH 1/2 THE
 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS, AND SHOW THE AREAS OF ROOFS
 THAT DRAIN ONTO THE ROOF AREAS FROM
 ABOVE IN CLACULATIONS. - IT APPEARS THAT
 NEW AREA WILL BE ADDED TO THE ROOF AREAS
 IN THE FORM OF NEW ROOF/WALL AREAS AT
 ENTRANCES.
  
 4. SHT A2.1 THE NEW OVERFLOW SCUPPERS
 SIZING CAN NOT BE DETERMINED WITHOUT
 REFERENCE TO THE DEFLECTION OF THE ROOF.
 PLEASE INDICATE THAT SCUPPERS WERE SIZED
 TO COMPLY WITH SECTIONS 1101.7, 1107.3 &
 TABLE 1106.7.
  
 5. SHT A6-1 THE FOLLOWING INFORMATION IS
 REQUIRED TO SHOW COMPLIANCE WITH
 ACCESSIBILITY:
 FOR DRINKING FOUNTAINS:
 A. 11-4.15.5 CLEAR FLOOR SPACE
 FOR W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.6 DISPENSERS
 FOR TOILET STALLS:
 A. 11-4.17.3 (EXCEPTION) LAV SHALL BE
 LOCATED 60" OFF W/C WALL TO SIDE OF THE
 FIXTURE PER FIGURE 30E. IT SCALES OUT TO
 BE APPROXIMATELY 58".
 FOR URINALS:
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
 FOR LAVX:
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 FOR THE TOILET ROOMS:
 A. 11-4.22.3 UNOBSTRUCTED TURNING IN
 TOILET ROOM. (NOT IN STALLS).
  
 6. SHT A9.4 DETAILS 03, 04, 05, & 06
 SHOW THE FOLLOWING TO SHOW COMPLIANCE:
  
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD
 APPROACH REQUIRED)
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
  
 7. SHT P1-1 DEAD ENDS. KEY NOTES 1,3,& 5
 INDICATE LINE TO BE FLUSH TO FLOOR.
 BRANCH LINE PIPES TO BE REMOVED TO
 BUILDING DRAIN AND CAPPED. CAP SHALL NOT
 BE COVERED UNTIL INSPECTED BY FIELD
 INSPECTOR. SECTION 704.5.
  
 8. SHT P2-1 DEFINITION OF DEAD END - 2'
 OR MORE OF ABANDONED PIPE. DEAD ENDS ARE
 SHOWN, (IN LECTURE HALL, SANT. AND
 STORM). PLEASE REMOVE ALL DEAD ENDS.
 SECTION 704.5.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2006-10-12 Cont ID  
Sent By eschneid Date 2006-10-12 Time 19:06 Rev Time 0.00
Received By LFRANCO Date 2006-10-12 Time 19:07 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2006-10-03 Cont ID  
Sent By lfranco Date 2006-09-12 Time 18:44 Rev Time 0.00
Received By lfranco Date 2006-09-12 Time 18:47 Sent To I
Notes
2006-10-03 00:00:00PLANNING AND ZONING: FAILED
 9-12-06- FAILED
 8-3-06
  
 1.THE PROJECT IS UNDER REVIEW FOR AN
 INFORMAL SITE PLAN APPROVAL ISPR 06-06 -
 AN APPROVAL LETTER FOR THE SITE PLAN HAS
 NOT BEEN ISSUED.ALL COMMENTS FROM THE
 SITE PLAN REVIEW FROM THE PLANNING AND
 ZONING DEPARTMENT SHALL BE MET AND AN
 APPROVAL LETTER SHALL BE ISSUED, PRIOR
 TO APPROVAL OF THE BUILDING PERMIT.
  
 2.THE PLANS SUBMITTED FOR THE BUILDING
 PERMIT NEED TO MATCH THE PLANS THAT WILL
 BE APPROVED BY THE PLANNING AND ZONING
 DEPARTMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT THE ASSIGNED PLANNER FOR THIS
 PROJECT, SEE BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 (561) 822-1435
  
 NOTE:
 NADINE BIGBY - PLANNER WAS THE LAST TO
 REVIEW THIS BLDG. PERMIT ON 6-01-06 AND
 FAIL IT FOR THE SAME REASONS.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-08-03 Cont ID  
Sent By lfranco Date 2006-08-03 Time 18:34 Rev Time 0.00
Received By lfranco Date 2006-08-03 Time 18:17 Sent To I
Notes
2006-08-03 00:00:00PLANNING AND ZONING: FAILED
 8-3-06
  
 1.THE PROJECT IS UNDER REVIEW FOR AN
 INFORMAL SITE PLAN APPROVAL ISPR 06-06 -
 AN APPROVAL LETTER FOR THE SITE PLAN HAS
 NOT BEEN ISSUED.ALL COMMENTS FROM THE
 SITE PLAN REVIEW FROM THE PLANNING AND
 ZONING DEPARTMENT SHALL BE MET AND AN
 APPROVAL LETTER SHALL BE ISSUED, PRIOR
 TO APPROVAL OF THE BUILDING PERMIT.
  
 2.THE SIGNAGE EXCEEDS THE MAXIMUM
 HEIGHT ALLOWED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT THE ASSIGNED PLANNER FOR THIS
 PROJECT, SEE BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 (561) 822-1435
  
 NOTE:
 NADINE BIGBY - PLANNER WAS THE LAST TO
 REVIEW THIS BLDG. PERMIT ON 6-01-06 AND
 FAIL IT FOR THE SAME REASONS.

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To I
Notes
2006-06-01 00:00:00PLANNING AND ZONING DEPARTMENT: FAILED
  
 REVIEWED BY: NADINE BIGBY, PLANNER
 561-822-1435
  
 REASON: SIGNAGE EXCEED HEIGHT
 LIMITATIONS AND AN APPROVAL LETTER FOR
 INFORMAL SITE PLAN REVIEW HAS NOT BEEN
 APPROVED.
  
 5/25/06
 6/1/06 RETURNED
 6/1/06