Plan Review Details - Permit 06031343
Plan Review Stops For Permit 06031343
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-03 Cont ID  
Sent By jleahy Date 2006-04-03 Time 09:53 Rev Time 0.30
Received By jleahy Date 2006-04-03 Time 09:53 Sent To  
Notes
2006-04-03 00:00:00NEED RISER DIAGRAM. 215.5
  
 NEED PANEL SCHEDULE. 408.4
  
 NEED TO SHOW ARC FAULTS. 210.12
  
 NEED TO SHOW GFCI CIRCUITS. 210.8 (A)
  
 NEED OUTLETS ON FRONT AND BACK OF HOUSE.
 210.52 (E)
  
 IF YOU CAN FAX IT TO ME I WILL PUT WITH
 DRAWINGS.JLEAHY 644-7291 C, 805-6676 F

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-30 Cont ID  
Sent By btrobaug Date 2006-03-30 Time 07:18 Rev Time 0.00
Received By btrobaug Date 2006-03-30 Time 07:18 Sent To E
Notes
***NONE***