| 2006-09-15 00:00:00 | INSTALLATION OF GENERATOR & PAD |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-07-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-07-19 |
Time |
13:56 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2006-07-19 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2006-07-19 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 06031314 | | | ADD: 7105 NORTON AV | | | CONT: BAM SERVICES | | | TEL: (863)324-7577 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | 1) GENERATOR SLAB & ANCHOR REQUIREMENT | | | PLEASE PROVIDE SIZE OF GENERATOR(WXL), | | | PLUS PROVIDE PLANS WITH THE INFORMATION | | | DEPICTING HOLD DOWN BRACKETS, TYPE OF | | | FASTENER, AND THE MINIMUM EDGE DISTANCE | | | THE DEVICE REQUIRES WITHOUT LOAD | | | REDUCTION. | | | SECOND, PROVIDE INFORMATION ON THE | | | SLAB, THICKNESS, WIDTH AND LENGTH, IF | | | WIREMESH, FIBER MESH OR IF STEEL REBAR | | | WILL BEUSED. | | | THE NEW SLAB AND HOLD DOWN DETAILS: | | | 104.2.1* ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA | | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-05-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-05-08 |
Time |
16:44 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2006-05-08 |
Time |
16:44 |
Sent To |
|
|
| Notes |
| 2006-05-08 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 06031314 | | | ADD: 7105 NORTON AV | | | CONT: BAM SERVICES | | | TEL: (863)324-7577 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | 1) GENERATOR SLAB & ANCHOR REQUIREMENT | | | PLEASE PROVIDE SIZE OF GENERATOR(WXL), | | | PLUS PROVIDE PLANS WITH THE INFORMATION | | | DEPICTING HOLD DOWN BRACKETS, TYPE OF | | | FASTENER, AND THE MINIMUM EDGE DISTANCE | | | THE DEVICE REQUIRES WITHOUT LOAD | | | REDUCTION. | | | SECOND, PROVIDE INFORMATION ON THE | | | SLAB, THICKNESS, WIDTH AND LENGTH, IF | | | WIREMESH, FIBER MESH OR IF STEEL REBAR | | | WILL BEUSED. | | | THE NEW SLAB AND HOLD DOWN DETAILS: | | | 104.2.1* ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA | | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-08-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-18 |
Time |
19:49 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-18 |
Time |
19:49 |
Sent To |
|
|
| Notes |
| 2006-08-18 00:00:00 | STAMPED ELECTRICAL PLANS, GEN SPECS, WP | | | HOUSING, AND ATS SPECS |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-07-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-02 |
Time |
12:47 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-02 |
Time |
11:59 |
Sent To |
|
|
| Notes |
| 2006-07-02 00:00:00 | *********** UNSAT 2ND REVIEW ********** | | | | | | ** PLEASE SEE SOME NOTS FROM PREVIOUS | | | REVIEW WHICH STILL NEED TO BE ADDRESSED. | | | PLEASE SEE NOTES BELOW ARE TAKEN | | | DIRECTLY FROM PREVIOUS REVIEW. | | | | | | 1) NOTE: OK,NO, PLEASE SEE NEW | | | ELECTRICAL SHEETS ARE OK, HOWEVER NEW | | | SHEET "C-1" CONTAINS A RAISED SEAL OVER | | | A COLORED PHOTO-COPY OF SIGNATURE WHICH | | | IS REQUIRED TO BE ORIGINAL UNDER FS | | | 471.025. | | | PLEASE KNOW, COPIES OF THESE SHEETS ARE | | | BEING RETAINED AND WILL PLACED WITH | | | OTHER PREVIOUS PLANS WHICH WERE ALSO | | | SEALED PHOTO-COPIES OF THE DESIGNER'S | | | SIGNATURE. | | | PLEASE KNOW, PLANS NOW MAY BE TURNED | | | OVER TO THE FLORIDA BOARD OF ENGINEERS | | | AND STATE'S LEGAL COUNSEL TO THE FBPE'S | | | FOR REVIEW OF SAID PLANS. | | | ** PLEASE KNOW, THIS HAS BEEN | | | PREVIOUSLY NOTED ON THIS PERMIT AND MANY | | | OTHER PROJECTS WHICH ARE BEING DONE BY | | | THIS FIRM AND ALL PLANS FROM ALL | | | PROJECTS HAVE BEEN RETAINED AS THIS | | | COMMENT IS BEING REPEATED. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE PLANS ARE CONTAIN A | | | RAISED SEALED ON PLANS WHICH ARE | | | PHOTO-COPIES OF THE SIGNATURE FOR THE | | | ENGINEER OF RECORD. | | | PLEASE KNOW, BOTH SETS OF PLANS ARE | | | BEING RETAINED. | | | PLEASE SEE FS 471.025, FAC 61G15-23.002, | | | WHICH REQUIRES BOTH SETS TO CONTAIN AN | | | ORIGINAL SIGNATURE. | | | | | | 2) NOTE: NO, THIS HAS NOT BEEN ADJUSTED | | | AND A VALUE WILL BE ACCESSED BY THIS | | | OFFICE BEFORE PERMIT ISSUANCE USING THE | | | "MARSHALLS/ SWIFT" GUIDE. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE FBC ADMINISTRATIVE | | | SECTION 108.3 WHICH VALUE FOR COMPLETE | | | SCOPE OF WORK SHALL INCLUDE ALL LABOUR | | | AND MATERIALS WHETHER OR NOT ANY | | | EQUIPMENT IS OWNER SUPPLIED. | | | PLEASE SEE VALUE OF $5K IS NOT ACCURATE | | | FIGURE.PLEASE ADJUST. | | | | | | 3) NOTE: OK. | | | | | | 4) NOTE: OK. | | | | | | 5) NOTE: OK. | | | | | | 6) NOTE: NO, PLEASE SEE PANEL "PPC" DOES | | | NOT INDICATE IF IT CONTAINS A MCB. | | | PLEASE KNOW, IF THIS PANEL DOES NOT | | | CONTAIN A MCB, A DISCONNECT RATED FOR | | | THE LOAD SERVED SHALL BE GROUPED WITH | | | OTHER MAIN IN ORDER TO SHUT OFF POWER | | | FOR FEEDERS COMING TO THIS EQUIPMENT. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE INDICATE IF PANEL SHOWN | | | CONTAINS A MCB AND IF THIS IS RGOUPED | | | WITH ANY OTHER MAINS. RISER SHOWS "TO | | | EXISTING POWER SOURCE" HOWEVER THIS | | | SOURCE IS NOT CLEAR? METER, MAIN ? | | | PLEASE KNOW, THE DISCONNECTING MEANS | | | SHALL ALL MEET | | | 230.70,230.72,225.31-225.39, | | | 230.76,230.79. | | | | | | | | | ** PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-04-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-04-26 |
Time |
08:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-04-26 |
Time |
07:05 |
Sent To |
E |
|
| Notes |
| 2006-04-26 00:00:00 | ************* UNSAT ************* | | | | | | 1) NOTE: PLEASE SEE PLANS ARE CONTAIN A | | | RAISED SEALED ON PLANS WHICH ARE | | | PHOTO-COPIES OF THE SIGNATURE FOR THE | | | ENGINEER OF RECORD. | | | PLEASE KNOW, BOTH SETS OF PLANS ARE | | | BEING RETAINED. | | | PLEASE SEE FS 471.025, FAC 61G15-23.002, | | | WHICH REQUIRES BOTH SETS TO CONTAIN AN | | | ORIGINAL SIGNATURE. | | | | | | 2) NOTE: PLEASE SEE FBC ADMINISTRATIVE | | | SECTION 108.3 WHICH VALUE FOR COMPLETE | | | SCOPE OF WORK SHALL INCLUDE ALL LABOUR | | | AND MATERIALS WHETHER OR NOT ANY | | | EQUIPMENT IS OWNER SUPPLIED. | | | PLEASE SEE VALUE OF $5K IS NOT ACCURATE | | | FIGURE.PLEASE ADJUST. | | | | | | 3) NOTE: PLEASE PROVIDE IDENTIFICATION | | | ON SITE PLANS E-2 OF ALL EQUIPMENT. | | | (PANEL, ATS ETC.) | | | PLEASE SEE CONDUITS FROM GEN APPEAR TO | | | BE SHOWN HEADING TOWARD FENCE LINE, AND | | | PLANS ONLY INDICATES METER BOARD? | | | 215.5 | | | | | | 4) NOTE: PLEASE CORRELATE THE ATS BEING | | | INSTALLED. PLEASE SEE PLANS INDICATE | | | ASCO AND SPECS SUBMITTED ARE SHOWING | | | KOHLER. | | | 215.5 | | | | | | 5) NOTE: PLEASE INDICATE THE FLOOD ZONE | | | ON SITE PLAN, (IF ANY) AND ELEVATION OF | | | EQUIPMENT. | | | | | | 6) NOTE: PLEASE INDICATE OF PANEL SHOWN | | | CONTAINS A MCB AND IF THIS IS RGOUPED | | | WITH ANY OTHER MAINS. RISER SHOWS "TO | | | EXISTING POWER SOURCE" HOWEVER THIS | | | SOURCE IS NOT CLEAR? METER, MAIN ? | | | PLEASE KNOW, THE DISCONNECTING MEANS | | | SHALL ALL MEET | | | 230.70,230.72,225.31-225.39, | | | 230.76,230.79. | | | | | | | | | ** PLEASE KNOW, THE SITE PLAN CONTAINING | | | THE ZONING SIGN OFF HAS BEEN VOIDED DUE | | | TO THE FACT THE PLANS ARE SEALED | | | PHOTO-COPIES. | | | ZONING WILL BE REQUIRED TO RE-STAMPED | | | NEW PLANS WHEN PACKAGE IS RESUBMITTED | | | ONCE ALL REVIEWS ARE COMPLETED. | | | | | | ** PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2006-09-15 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-09-15 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-09-15 |
Time |
15:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2006-07-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2006-07-10 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2006-07-10 |
Time |
14:33 |
Sent To |
|
|
| Notes |
| 2006-07-10 00:00:00 | 1. PLEASE INDICATE DISTANCES FROM THE | | | FUEL TANK TO THE PROPERTY LINES, OTHER | | | IMPORTANT BUILDINGS, ETC. SINCE THE | | | GENERATOR IS EXPECTED TO CONTAIN DEISEL | | | FUEL PROPER DISTANCES FROM THE PROPERTY | | | LINE IS NECESSARY. | | | | | | 2. IT APPEARS FROM THE PRODUCT DATA, THE | | | FUEL TANK IS UL 142 LISTED. | | | | | | 3. IT APPEARS THAT PLANS HAVE BEEN | | | REVISED. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-05-12 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-05-12 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-05-12 |
Time |
13:04 |
Sent To |
|
|
| Notes |
| 2006-05-12 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE SEE MECHANICAL REVIEW COMMENT | | | REGARDING LOCATION OF EXHAUSTING. | | | | | | 2) WORK SHALL COMPLY WITH APPLICABLE | | | BUILDING CODES, AND NFPA 110. | | | | | | 3) PLANS SHOW INSTALLATION OF DIESEL | | | GENERATOR. PLEASE PROVIDE MORE DETAILS | | | REGARDING FUEL STORAGE, LOCATION AND | | | QUANTITY, PROTECTION AGAINST MECHANICAL | | | DAMAGE, ETC. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FUEL |
DIESEL GENERATOR |
| Rev No |
1 |
Status |
N |
Date |
2006-08-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-08-07 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2006-09-25 |
Time |
17:07 |
Sent To |
|
|
| Notes |
| 2006-08-07 00:00:00 | DENIED: | | | 247 GALLON SUB-BASE FUEL TANK.SELF | | | CONTAINED. | | | | | | PERMIT APPLICATION INDICATES A 30KW | | | KOHLER DIESEL GENERATOR.PLEASE | | | INDICATE ALL ACCESSORY ITEMS. SUBMITTAL | | | DATA DOES NOT HAVE WHICH GENERATOR OR | | | ANY OF THE SETTINGS OR ACCESSORIES | | | IDENTIFIED. | | | | | | GENERATOR SUBMITTAL INDICATES ALL UNITS | | | ARE CONFIGURED FOR OPERATION WITH | | | NATURAL GAS FUEL.PLEASE CLARIFY | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2006-09-25 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2006-09-25 |
Time |
17:08 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2006-09-25 |
Time |
17:08 |
Sent To |
|
|
| Notes |
| 2006-09-25 00:00:00 | NO NATURAL GAS. DIESEL FUEL TANK AT BASE | | | OF GENERATOR. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2006-08-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-08-07 |
Time |
12:44 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-08-07 |
Time |
12:44 |
Sent To |
|
|
| Notes |
| 2006-08-07 00:00:00 | DENIED: | | | SUBMITTAL FOR GENERATOR INDICATES ALL | | | UNITS ARE CONFIGURED FOR OPERATION WITH | | | NATRURAL GAS.PLEASE PROVIDE GAS PIPING | | | INFORMATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT MIKE PERSON OR KENNY STEVENS AT | | | (561)805-6730 OR 805-6721 RESPECTIVELY. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-08-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-09 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-09 |
Time |
11:09 |
Sent To |
|
|
| Notes |
| 2006-08-18 00:00:00 | TO COMM BOARD #22 | | 2006-08-09 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-06-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-21 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-21 |
Time |
16:19 |
Sent To |
|
|
| Notes |
| 2006-07-02 00:00:00 | TO COMM BOARD SPACE #10 B | | 2006-06-21 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-04-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-04-06 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-04-06 |
Time |
09:57 |
Sent To |
|
|
| Notes |
| 2006-04-19 00:00:00 | TO "COMM" BD#17 | | 2006-04-06 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-08-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-04-05 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-03-29 |
Time |
15:08 |
Sent To |
|
|
| Notes |
| 2006-03-29 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2006-09-25 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2006-09-25 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2006-09-25 |
Time |
16:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2006-08-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-08-07 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-08-07 |
Time |
10:41 |
Sent To |
|
|
| Notes |
| 2006-08-07 00:00:00 | DENIED: | | | 1. PLANS INDICATE ANCHORING DETAIL ON | | | PLAN SHEET C-1.C-1 IS MISSING FROM | | | THREE SETS OF PLANS. | | | | | | 2. PLEASE ALSO NOTE COMMENTS BY JIM | | | WITMER, BUILDING PLANS EXAMINER FOR THE | | | SLAB INFORMATION. | | | | | | 3. PLAN SHEET E2 INDICATES CLEARANCES TO | | | IRRIGATION PUMP AND WAVEGUIDE BRIDGE BUT | | | DOES NOT GIVE A CLEARANCE FROM THE SELF | | | SUPPORTING TOWER OR PROPERTY LINE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-05-10 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-05-10 |
Time |
11:05 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2006-05-10 |
Time |
11:05 |
Sent To |
|
|
| Notes |
| 2006-05-10 00:00:00 | *** DENIED *** | | | 1) PLEASE SEE ELECTRICAL REVIEW NOTES | | | #1,2, AND 5. | | | | | | 2) PLEASE BE ADVISED AND NOTE ON PLANS. | | | GENERATOR EXHUST MUST BE TEN FEET AWAY | | | FROM ANY BUILDING OPENINGS (WINDOWS, | | | DOORS, ROOF & EAVE VENTS), AND TEN FEET | | | AWAY FROM ADJECENT BUILDING OPENS. PER | | | 2004 FBC/M 401.5.1 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2006-08-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-08-07 |
Time |
12:55 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-08-07 |
Time |
12:47 |
Sent To |
|
|
| Notes |
| 2006-08-07 00:00:00 | NO PLUMBING PLANS SUBMITTED FOR REVIEW |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2006-07-17 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-07-17 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-07-17 |
Time |
10:21 |
Sent To |
|
|
| Notes |
| 2006-07-17 00:00:00 | NOTE: THE PROPOSED GENERATOR SHALL BE | | | SCREENED WITH WALL (BRICK, DECORATIVE | | | CONCRETE, OTHER DECORATIVE MASONRY) AND | | | BE LANDSCAPE WITH SHRUBS & HEDGES | | | PLANTED AT TWO-FOOT INTERVALS. SEC | | | 94.444 (B) | | | | | | | | 2006-04-26 00:00:00 | WILL REQUIRE ZONING WHEN PLANS COME BACK | | | FOR A RE-STAMP, AS PLANS WITH ZONING | | | STAMP HAVE BEEN VOIDED, DUE TO PLAN | | | BEING SEALED PHOTO-COPIES OF ENGINEERS | | | SIGNATURE. | | | FS 471.025 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2006-04-05 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-04-05 |
Time |
07:18 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-04-05 |
Time |
07:18 |
Sent To |
I |
|
| Notes |
|
|