Plan Review Details - Permit 06031314
Plan Review Stops For Permit 06031314
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-09-15 Cont ID  
Sent By jwitmer Date 2006-09-15 Time 14:19 Rev Time 0.55
Received By jwitmer Date 2006-09-15 Time 14:19 Sent To  
Notes
2006-09-15 00:00:00INSTALLATION OF GENERATOR & PAD

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-19 Cont ID  
Sent By jwitmer Date 2006-07-19 Time 13:56 Rev Time 0.77
Received By jwitmer Date 2006-07-19 Time 13:56 Sent To  
Notes
2006-07-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06031314
 ADD: 7105 NORTON AV
 CONT: BAM SERVICES
 TEL: (863)324-7577
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 1) GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-08 Cont ID  
Sent By jwitmer Date 2006-05-08 Time 16:44 Rev Time 0.77
Received By jwitmer Date 2006-05-08 Time 16:44 Sent To  
Notes
2006-05-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06031314
 ADD: 7105 NORTON AV
 CONT: BAM SERVICES
 TEL: (863)324-7577
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 1) GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-08-18 Cont ID  
Sent By dpalmer Date 2006-08-18 Time 19:49 Rev Time 0.00
Received By dpalmer Date 2006-08-18 Time 19:49 Sent To  
Notes
2006-08-18 00:00:00STAMPED ELECTRICAL PLANS, GEN SPECS, WP
 HOUSING, AND ATS SPECS

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-02 Cont ID  
Sent By dpalmer Date 2006-07-02 Time 12:47 Rev Time 0.00
Received By dpalmer Date 2006-07-02 Time 11:59 Sent To  
Notes
2006-07-02 00:00:00*********** UNSAT 2ND REVIEW **********
  
 ** PLEASE SEE SOME NOTS FROM PREVIOUS
 REVIEW WHICH STILL NEED TO BE ADDRESSED.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
  
 1) NOTE: OK,NO, PLEASE SEE NEW
 ELECTRICAL SHEETS ARE OK, HOWEVER NEW
 SHEET "C-1" CONTAINS A RAISED SEAL OVER
 A COLORED PHOTO-COPY OF SIGNATURE WHICH
 IS REQUIRED TO BE ORIGINAL UNDER FS
 471.025.
 PLEASE KNOW, COPIES OF THESE SHEETS ARE
 BEING RETAINED AND WILL PLACED WITH
 OTHER PREVIOUS PLANS WHICH WERE ALSO
 SEALED PHOTO-COPIES OF THE DESIGNER'S
 SIGNATURE.
 PLEASE KNOW, PLANS NOW MAY BE TURNED
 OVER TO THE FLORIDA BOARD OF ENGINEERS
 AND STATE'S LEGAL COUNSEL TO THE FBPE'S
 FOR REVIEW OF SAID PLANS.
 ** PLEASE KNOW, THIS HAS BEEN
 PREVIOUSLY NOTED ON THIS PERMIT AND MANY
 OTHER PROJECTS WHICH ARE BEING DONE BY
 THIS FIRM AND ALL PLANS FROM ALL
 PROJECTS HAVE BEEN RETAINED AS THIS
 COMMENT IS BEING REPEATED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS ARE CONTAIN A
 RAISED SEALED ON PLANS WHICH ARE
 PHOTO-COPIES OF THE SIGNATURE FOR THE
 ENGINEER OF RECORD.
 PLEASE KNOW, BOTH SETS OF PLANS ARE
 BEING RETAINED.
 PLEASE SEE FS 471.025, FAC 61G15-23.002,
 WHICH REQUIRES BOTH SETS TO CONTAIN AN
 ORIGINAL SIGNATURE.
  
 2) NOTE: NO, THIS HAS NOT BEEN ADJUSTED
 AND A VALUE WILL BE ACCESSED BY THIS
 OFFICE BEFORE PERMIT ISSUANCE USING THE
 "MARSHALLS/ SWIFT" GUIDE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC ADMINISTRATIVE
 SECTION 108.3 WHICH VALUE FOR COMPLETE
 SCOPE OF WORK SHALL INCLUDE ALL LABOUR
 AND MATERIALS WHETHER OR NOT ANY
 EQUIPMENT IS OWNER SUPPLIED.
 PLEASE SEE VALUE OF $5K IS NOT ACCURATE
 FIGURE.PLEASE ADJUST.
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE: OK.
  
 6) NOTE: NO, PLEASE SEE PANEL "PPC" DOES
 NOT INDICATE IF IT CONTAINS A MCB.
 PLEASE KNOW, IF THIS PANEL DOES NOT
 CONTAIN A MCB, A DISCONNECT RATED FOR
 THE LOAD SERVED SHALL BE GROUPED WITH
 OTHER MAIN IN ORDER TO SHUT OFF POWER
 FOR FEEDERS COMING TO THIS EQUIPMENT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE IF PANEL SHOWN
 CONTAINS A MCB AND IF THIS IS RGOUPED
 WITH ANY OTHER MAINS. RISER SHOWS "TO
 EXISTING POWER SOURCE" HOWEVER THIS
 SOURCE IS NOT CLEAR? METER, MAIN ?
 PLEASE KNOW, THE DISCONNECTING MEANS
 SHALL ALL MEET
 230.70,230.72,225.31-225.39,
 230.76,230.79.
  
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-26 Cont ID  
Sent By dpalmer Date 2006-04-26 Time 08:12 Rev Time 0.00
Received By dpalmer Date 2006-04-26 Time 07:05 Sent To E
Notes
2006-04-26 00:00:00************* UNSAT *************
  
 1) NOTE: PLEASE SEE PLANS ARE CONTAIN A
 RAISED SEALED ON PLANS WHICH ARE
 PHOTO-COPIES OF THE SIGNATURE FOR THE
 ENGINEER OF RECORD.
 PLEASE KNOW, BOTH SETS OF PLANS ARE
 BEING RETAINED.
 PLEASE SEE FS 471.025, FAC 61G15-23.002,
 WHICH REQUIRES BOTH SETS TO CONTAIN AN
 ORIGINAL SIGNATURE.
  
 2) NOTE: PLEASE SEE FBC ADMINISTRATIVE
 SECTION 108.3 WHICH VALUE FOR COMPLETE
 SCOPE OF WORK SHALL INCLUDE ALL LABOUR
 AND MATERIALS WHETHER OR NOT ANY
 EQUIPMENT IS OWNER SUPPLIED.
 PLEASE SEE VALUE OF $5K IS NOT ACCURATE
 FIGURE.PLEASE ADJUST.
  
 3) NOTE: PLEASE PROVIDE IDENTIFICATION
 ON SITE PLANS E-2 OF ALL EQUIPMENT.
 (PANEL, ATS ETC.)
 PLEASE SEE CONDUITS FROM GEN APPEAR TO
 BE SHOWN HEADING TOWARD FENCE LINE, AND
 PLANS ONLY INDICATES METER BOARD?
 215.5
  
 4) NOTE: PLEASE CORRELATE THE ATS BEING
 INSTALLED. PLEASE SEE PLANS INDICATE
 ASCO AND SPECS SUBMITTED ARE SHOWING
 KOHLER.
 215.5
  
 5) NOTE: PLEASE INDICATE THE FLOOD ZONE
 ON SITE PLAN, (IF ANY) AND ELEVATION OF
 EQUIPMENT.
  
 6) NOTE: PLEASE INDICATE OF PANEL SHOWN
 CONTAINS A MCB AND IF THIS IS RGOUPED
 WITH ANY OTHER MAINS. RISER SHOWS "TO
 EXISTING POWER SOURCE" HOWEVER THIS
 SOURCE IS NOT CLEAR? METER, MAIN ?
 PLEASE KNOW, THE DISCONNECTING MEANS
 SHALL ALL MEET
 230.70,230.72,225.31-225.39,
 230.76,230.79.
  
  
 ** PLEASE KNOW, THE SITE PLAN CONTAINING
 THE ZONING SIGN OFF HAS BEEN VOIDED DUE
 TO THE FACT THE PLANS ARE SEALED
 PHOTO-COPIES.
 ZONING WILL BE REQUIRED TO RE-STAMPED
 NEW PLANS WHEN PACKAGE IS RESUBMITTED
 ONCE ALL REVIEWS ARE COMPLETED.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-09-15 Cont ID  
Sent By mwennerg Date 2006-09-15 Time 15:06 Rev Time 0.00
Received By mwennerg Date 2006-09-15 Time 15:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-07-10 Cont ID  
Sent By mcarsill Date 2006-07-10 Time 14:36 Rev Time 0.00
Received By mcarsill Date 2006-07-10 Time 14:33 Sent To  
Notes
2006-07-10 00:00:001. PLEASE INDICATE DISTANCES FROM THE
 FUEL TANK TO THE PROPERTY LINES, OTHER
 IMPORTANT BUILDINGS, ETC. SINCE THE
 GENERATOR IS EXPECTED TO CONTAIN DEISEL
 FUEL PROPER DISTANCES FROM THE PROPERTY
 LINE IS NECESSARY.
  
 2. IT APPEARS FROM THE PRODUCT DATA, THE
 FUEL TANK IS UL 142 LISTED.
  
 3. IT APPEARS THAT PLANS HAVE BEEN
 REVISED.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-05-12 Cont ID  
Sent By mwennerg Date 2006-05-12 Time 13:04 Rev Time 0.00
Received By mwennerg Date 2006-05-12 Time 13:04 Sent To  
Notes
2006-05-12 00:00:00******DENIED******
  
 1) PLEASE SEE MECHANICAL REVIEW COMMENT
 REGARDING LOCATION OF EXHAUSTING.
  
 2) WORK SHALL COMPLY WITH APPLICABLE
 BUILDING CODES, AND NFPA 110.
  
 3) PLANS SHOW INSTALLATION OF DIESEL
 GENERATOR. PLEASE PROVIDE MORE DETAILS
 REGARDING FUEL STORAGE, LOCATION AND
 QUANTITY, PROTECTION AGAINST MECHANICAL
 DAMAGE, ETC.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status N Date 2006-08-07 Cont ID  
Sent By pkrauss Date 2006-08-07 Time 10:48 Rev Time 0.00
Received By rregueir Date 2006-09-25 Time 17:07 Sent To  
Notes
2006-08-07 00:00:00DENIED:
 247 GALLON SUB-BASE FUEL TANK.SELF
 CONTAINED.
  
 PERMIT APPLICATION INDICATES A 30KW
 KOHLER DIESEL GENERATOR.PLEASE
 INDICATE ALL ACCESSORY ITEMS. SUBMITTAL
 DATA DOES NOT HAVE WHICH GENERATOR OR
 ANY OF THE SETTINGS OR ACCESSORIES
 IDENTIFIED.
  
 GENERATOR SUBMITTAL INDICATES ALL UNITS
 ARE CONFIGURED FOR OPERATION WITH
 NATURAL GAS FUEL.PLEASE CLARIFY
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2006-09-25 Cont ID  
Sent By rregueir Date 2006-09-25 Time 17:08 Rev Time 0.00
Received By rregueir Date 2006-09-25 Time 17:08 Sent To  
Notes
2006-09-25 00:00:00NO NATURAL GAS. DIESEL FUEL TANK AT BASE
 OF GENERATOR.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-08-07 Cont ID  
Sent By pkrauss Date 2006-08-07 Time 12:44 Rev Time 0.00
Received By pkrauss Date 2006-08-07 Time 12:44 Sent To  
Notes
2006-08-07 00:00:00DENIED:
 SUBMITTAL FOR GENERATOR INDICATES ALL
 UNITS ARE CONFIGURED FOR OPERATION WITH
 NATRURAL GAS.PLEASE PROVIDE GAS PIPING
 INFORMATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT MIKE PERSON OR KENNY STEVENS AT
 (561)805-6730 OR 805-6721 RESPECTIVELY.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-09 Cont ID  
Sent By adarroug Date 2006-08-09 Time 11:09 Rev Time 0.00
Received By adarroug Date 2006-08-09 Time 11:09 Sent To  
Notes
2006-08-18 00:00:00TO COMM BOARD #22
2006-08-09 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-21 Cont ID  
Sent By adarroug Date 2006-06-21 Time 16:19 Rev Time 0.00
Received By adarroug Date 2006-06-21 Time 16:19 Sent To  
Notes
2006-07-02 00:00:00TO COMM BOARD SPACE #10 B
2006-06-21 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-06 Cont ID  
Sent By adarroug Date 2006-04-06 Time 09:57 Rev Time 0.00
Received By adarroug Date 2006-04-06 Time 09:57 Sent To  
Notes
2006-04-19 00:00:00TO "COMM" BD#17
2006-04-06 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-07 Cont ID  
Sent By pkrauss Date 2006-04-05 Time 11:14 Rev Time 0.00
Received By pkrauss Date 2006-03-29 Time 15:08 Sent To  
Notes
2006-03-29 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-09-25 Cont ID  
Sent By rregueir Date 2006-09-25 Time 16:59 Rev Time 0.00
Received By rregueir Date 2006-09-25 Time 16:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-08-07 Cont ID  
Sent By pkrauss Date 2006-08-07 Time 10:41 Rev Time 0.00
Received By pkrauss Date 2006-08-07 Time 10:41 Sent To  
Notes
2006-08-07 00:00:00DENIED:
 1. PLANS INDICATE ANCHORING DETAIL ON
 PLAN SHEET C-1.C-1 IS MISSING FROM
 THREE SETS OF PLANS.
  
 2. PLEASE ALSO NOTE COMMENTS BY JIM
 WITMER, BUILDING PLANS EXAMINER FOR THE
 SLAB INFORMATION.
  
 3. PLAN SHEET E2 INDICATES CLEARANCES TO
 IRRIGATION PUMP AND WAVEGUIDE BRIDGE BUT
 DOES NOT GIVE A CLEARANCE FROM THE SELF
 SUPPORTING TOWER OR PROPERTY LINE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-05-10 Cont ID  
Sent By tgordon Date 2006-05-10 Time 11:05 Rev Time 0.20
Received By tgordon Date 2006-05-10 Time 11:05 Sent To  
Notes
2006-05-10 00:00:00*** DENIED ***
 1) PLEASE SEE ELECTRICAL REVIEW NOTES
 #1,2, AND 5.
  
 2) PLEASE BE ADVISED AND NOTE ON PLANS.
 GENERATOR EXHUST MUST BE TEN FEET AWAY
 FROM ANY BUILDING OPENINGS (WINDOWS,
 DOORS, ROOF & EAVE VENTS), AND TEN FEET
 AWAY FROM ADJECENT BUILDING OPENS. PER
 2004 FBC/M 401.5.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-08-07 Cont ID  
Sent By pkrauss Date 2006-08-07 Time 12:55 Rev Time 0.00
Received By pkrauss Date 2006-08-07 Time 12:47 Sent To  
Notes
2006-08-07 00:00:00NO PLUMBING PLANS SUBMITTED FOR REVIEW

Review Stop Z ZONING
Rev No 2 Status P Date 2006-07-17 Cont ID  
Sent By mmclean Date 2006-07-17 Time 10:21 Rev Time 0.00
Received By mmclean Date 2006-07-17 Time 10:21 Sent To  
Notes
2006-07-17 00:00:00NOTE: THE PROPOSED GENERATOR SHALL BE
 SCREENED WITH WALL (BRICK, DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY) AND
 BE LANDSCAPE WITH SHRUBS & HEDGES
 PLANTED AT TWO-FOOT INTERVALS. SEC
 94.444 (B)
  
  
2006-04-26 00:00:00WILL REQUIRE ZONING WHEN PLANS COME BACK
 FOR A RE-STAMP, AS PLANS WITH ZONING
 STAMP HAVE BEEN VOIDED, DUE TO PLAN
 BEING SEALED PHOTO-COPIES OF ENGINEERS
 SIGNATURE.
 FS 471.025

Review Stop Z ZONING
Rev No 1 Status P Date 2006-04-05 Cont ID  
Sent By mmclean Date 2006-04-05 Time 07:18 Rev Time 0.00
Received By mmclean Date 2006-04-05 Time 07:18 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved