| 2006-03-28 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | MYRON JACOBS(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2004 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | 1) FBC 1609 THE SYSTEM SELECTED FROM THE |
| | SUBMITTED FLAT ROOF PRODUCT APPROVAL NOA |
| | HAS A MAXIMUM DESIGN PRESSURE OF LESS |
| | THAN -89 PSF AND CITES GENERAL |
| | LIMITATION #9. GENERAL LIMITATION #9 |
| | PROHIBITS RATIONAL ANALYSIS OR |
| | EXTRAPOLATION TO ENHANCE THE UPLIFT |
| | PRESSURE AT PERIMETER AND CORNER AREAS |
| | BY REDUCING THE FASTENER SPACING IN |
| | THESE AREAS.EITHER SELECT AN |
| | ALTERNATIVE SYSTEM (OR PRODUCT APPROVAL) |
| | THAT DOES NOT CITE GENERAL LIMITATION |
| | #9.ALTERNATIVELY IF THE SELECTED |
| | SYSTEM DOES CITE GENERAL LIMITATION #9, |
| | IT MUST HAVE A MAXIMUM DESIGN PRESSURE |
| | THAT EXCEEDS THE PRESSURE IN ROOF ZONE 3 |
| | (TYPICALLY -89 PSF FOR MEAN ROOF HEIGHT |
| | OF 30 FEET OR LESS). ALSO IF GENERAL |
| | LIMITATION #7 IS USED, CALCULATIONS |
| | SIGNED AND SEALED SHALL BE DONE BY A |
| | FLORIDA REGISTERED PROFESSIONAL |
| | ENGINEER,ARCHITECT OR ROOF |
| | CONSULTANT.SEE PG 22. |
| | PLEASE HI-LIGHT OR CIRCLE WHICH APPROVED |
| | ASSEMBLY WILL BE USED. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | TEL:(561)805-6726 |
| | |
| | |
| | |
| | |
| | |