Plan Review Details - Permit 06031268
Plan Review Stops For Permit 06031268
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-06-27 Cont ID  
Sent By shill Date 2006-06-27 Time 17:52 Rev Time 0.00
Received By shill Date 2006-06-27 Time 17:43 Sent To  
Notes
2006-06-27 00:00:00PROVISO
  
 SEP PERMITS ROOF, DOOR, SKYLIGHT
  
 SUBMIT A.0 AS A REVISION INCORPORATING
 CHANGES (ARCHITECT'S LETTER)

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-22 Cont ID  
Sent By shill Date 2006-06-22 Time 12:42 Rev Time 0.00
Received By shill Date 2006-06-22 Time 11:02 Sent To  
Notes
2006-06-27 00:00:00****CORRECTIONS****
 ****SHUTTER INSTALLATION PLAN****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBEXISTING BUILDING
 FBC R RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)SEE ATTACHED IMPLEMENTATION
 STANDARD, ITEM 13.PROVIDE THE
 FOLLOWING INFORMATION:
  
 A.SHOW ON-SITE LOCATION OF SHUTERS.
  
 B.PROVIDE ENOUGH INFORMATION IN
 REGARDS TO THE PARTY RESPONSIBLE FOR
 SECURING THE SHUTTERS TO DETERMINE
 WHETHER OR NOT THE PLAN AS SUBMITTED IS
 EASILY EXECUTED (SUCH AS, TOTAL STAFF,
 LOCATION, OTHER RESPONSIBILITIES DURING
 PRE-STORM PREPARATION, ETC.).
  
 C.STATE THE TOTAL NUMBER OF OPENINGS.
  
 D.STATE THE TOTAL TIME REQUIRED TO
 SECURE THE OPENINGS.
  
 E.STATE WHEN THE SHUTTERS WILL BE
 INSTALLED."WHEN THE NEED ARISES" IS
 NOT A TIME FRAME CONSISTENT WITH THE
 IMPLEMENTATION STANDARD.
  
2006-06-22 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS REVIEW:
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)SHEET A.0 DECLARES BUILDING TYPE AS
 1V.SEE FBC6, THIS SHOULD REFER TO A OR
 B.
  
 2ND REVIEW - BUILDING TYPE NOW CHANGED
 TO 2A.SEE FBC602.2, FBC603.THE
 DETAILS ARE NOT COMPLIANT WITH THIS
 CONSTRUCTION TYPE.PLEASE DECLARE A
 MINIMUM BUILDING CONSTRUCTION TYPE.
  
 3.-4.)ADDRESSED.
  
 5.)PROVIDE FLOOD ZONE DESIGNATION.IF
 THIS IS LOCATED IN A HIGH HAZARD FLOOD
 ZONE, THE FINIHSED FLOOR IS TO BE 6"
 ABOVE BFE, CITY OF WEST PALM BEACH
 MINICIPAL CODE 94-546(B).IF THIS IS IN
 A HIGH HAZARD FLOOZ ZONE, DECLARE BFE
 AND SHOW MINIMUM FFE ON THE PLAN.FORM
 BOARD WITH ELEVATIONS WILL BE REQUIRED.
  
 ARCHITECT RESPONDED WITH X500 FROM GIS
 SYSTEM.THIS IS NOT ACCURATE.IT HAS
 BEEN DETERMINED THAT THE FLOOD ZONE IS
 "B", PLEASE INDICATE AS SUCH ON THE
 PLAN.
  
 6.)ALL PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD
 FBC*106.3.3.
  
 SKYLIGHT IS NOT IMPACT RESISTANT, SEE
 FLORIDA STATE PRODUCT APPROVAL
 LIMITATIONS.DOCUMENTATION DOES NOT
 SHOW DESIGN PRESSURE FOR THE PRODUCT;
 HOW HAS ARCHITECT DETERMINED THAT THIS
 IS CODE COMPLIANT?THE PHRASE "IMPACT
 RESISTANT" HAS BEEN HIGHLIGHTED, NOTE
 THAT THIS FIELD IS BLANK AND UNDERNEATH
 INDICATES NO IMPACT RATING, MFGR SPEC
 STATES "CHECK LOCAL BUILDING CODES FOR
 GLASS REQUIREMENTS".
  
 HURRICANE SHUTTERS - MUST BE APPROVED
 THROUGH AN INSTALLATION PLAN AS
 DISCUSSED.SEE ATTACHED SCHEDULE FOR
 INFORMATION REQUIRED FOR PERMITTING.
  
 THE CURRIE DOOR PRODUCT APPROVAL APPEARS
 CODE COMPLIANT SUBJECT TO APPROVAL OF
 THE HURRICANE SHUTTER INSTALLATION PLAN
 AS DISCUSSED.
  
 7-8.)ADDRESSED.
  
 9.)PROVIDE WIND DESIGN INFORMATION
 REQUIRED BY FBC1603.1.4.
  
 NOT ADDRESSED.REQUIRED TO SHOW CODE
 COMPLIANCE.
  
 10.)SHUTTERS ARE REQUIRED FOR THE
 LOUVERED DOOR.SHUTTERS FOR COMMERCIAL
 BUILDINGS MUST BE APPROVED BY THE
 BUILDING OFFICIAL.SEE ATTACHED POLICY,
 ITEM 13.SUBMIT AN INSTALLATION PLAN.
 FAILURE TO ADDRESS THIS COMMENT WILL
 RESULT IN DELAYS IN PERMITTING.THE
 PLAN MAY BE SUBMITTED SEPARATELY FROM
 THE PERMIT RESUBMITTAL.
  
 11.)PROVIDE THE APPROVED ASSEMBLY YOU
 ARE USING FOR THE FLAT DECK.
  
 NONE FROM THE PRODUCT APPROVAL WAS
 SUBMITTED.THE MFGR SPEC SHEET IS FOR
 CONCRETE DECK.THE PAGE WITH THE
 APPROVED ASSEMBLY FROM THE NOA IS
 REQUIRED.
  
 12.)THE SPEC SHEET FOR THE ROOF IS FOR
 A CONCRETE DECK, THIS IS WOOD.
  
 THE CONCRETE MODIFIED SYSTEM IS STILL IN
 THE PACKAGE.PLEASE REMOVE AS YOUR PLAN
 SHOWS A WOOD DECK.
  
 13.)ADDRESSED.
  
 14.)DOCUMENTS PREPARED BY A LANDSCAPE
 ARCHITECT ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS FS481.306.THE SITE
 PLAN PREPARED BY URBAN DESIGN DOES NOT
 SHOW THE PROPOSED IMPROVEMENT.SEE ALSO
 #13.
  
 THE UNSEALED SHEET FROM URBAN DESIGN
 STUDIO IS STILL IN THE PACKAGE.IS THIS
 REQUIRED?I HAVE USED THE SURVEY TO
 DETERMINE CODE COMPLIANCE.IF THIS
 SHEET IS REQUIRED FROM ANOTHER TRADE,
 THIS MUST BE A SIGNED, SEALED, DATED
 ORIGINAL.OTHERWISE, REMOVE FROM THE
 PACKAGE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-09 Cont ID  
Sent By shill Date 2006-05-09 Time 11:13 Rev Time 0.00
Received By shill Date 2006-05-09 Time 11:13 Sent To  
Notes
2006-05-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)SHEET A.0 DECLARES BUILDING TYPE AS
 1V.SEE FBC6, THIS SHOULD REFER TO A OR
 B.
  
 3.)DECLARE BUILDING SIZE, FBC5.
  
 4.)OCCUPANCY IS TO BE ONE IN CHAPTER
 3."PUMP HOUSE" IS NOT AN OCCUPANCY
 CLASSIFICATION.
  
 5.)PROVIDE FLOOD ZONE DESIGNATION.IF
 THIS IS LOCATED IN A HIGH HAZARD FLOOD
 ZONE, THE FINISHED FLOOR IS TO BE 6"
 ABOVE BFE, CITY OF WEST PALM BEACH
 MUNICIPAL CODE 94-546(B).IF THIS IS IN
 A HIGH HAZARD FLOOD ZONE, DECLARE BFE
 AND SHOW MINIMUM FFE ON THE PLAN.FORM
 BOARD WITH ELEVATIONS WILL BE REQUIRED.
  
 6.)ALL PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD
 FBC*106.3.3.
  
 7.)PROVIDE INSTALLATION INSTRUCTIONS
 FROM THE MANUFACTUER FOR THE SKYLIGHT.
  
 8.)THE FLORIDA STATE PRODUCT APPROVALS
 FOR THE CONNECTORS ARE EXPIRED, 2001
 CODE RATHER THAN 2004.
  
 9.)PROVIDE WIND DESIGN INFORMATION
 REQUIRED BY FBC1603.1.4.
  
 10.)SHUTTERS ARE REQUIRED FOR THE
 LOUVERED DOOR.SHUTTERS FOR COMMERCIAL
 BUILDINGS MUST BE APPROVED BY THE
 BUILDING OFFICIAL.SEE ATTACHED POLICY,
 ITEM 13.SUBMIT AN INSTALLATION PLAN.
 FAILURE TO ADDRESS THIS COMMENT WILL
 RESULT IN DELAYS IN PERMITTING.THE
 PLAN MAY BE SUBMITTED SEPARATELY FROM
 THE PERMIT RESUBMITTAL.
  
 11.)PROVIDE THE APPROVED ASSEMBLY YOU
 ARE USING FOR THE FLAT DECK.
  
 12.)THE SPEC SHEET FOR THE ROOF IS FOR
 A CONCRETE DECK, THIS IS WOOD.
  
 13.)THE SITE PLAN IS REQUIRED TO SHOW
 TABLE 601 COMPLIANCE.PROVIDE A SIGNED,
 SEALED, DATED SITE PLAN SHOWING DISTANCE
 TO EITHER THE PROPERTY LINE OR TO
 ADJACENT BUILDINGS AND ASSUMED PROPERTY
 LINES.
  
 14.)DOCUMENTS PREPARED BY A LANDSCAPE
 ARCHITECT ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS FS481.306.THE SITE
 PLAN PREPARED BY URBAN DESIGN DOES NOT
 SHOW THE PROPOSED IMPROVEMENT.SEE ALSO
 #13.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-06-13 Cont ID  
Sent By btrobaug Date 2006-06-13 Time 18:26 Rev Time 0.50
Received By btrobaug Date 2006-06-13 Time 18:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-21 Cont ID  
Sent By btrobaug Date 2006-04-21 Time 16:46 Rev Time 0.50
Received By btrobaug Date 2006-04-21 Time 16:40 Sent To  
Notes
2006-04-21 00:00:00 
 THE SCOPE OF THIS ELECTRICAL WORK
 REQUIRES ENGINEERING PER 471.003(1)(H).
 PLEASE HAVE ELCTRICAL PLANS DRAWN,
 SIGNED AND SEALED BY AN ENGINEER.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-06-23 Cont ID  
Sent By mwennerg Date 2006-06-27 Time 11:39 Rev Time 0.00
Received By mwennerg Date 2006-06-23 Time 11:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-05-09 Cont ID  
Sent By mwennerg Date 2006-05-09 Time 15:57 Rev Time 0.00
Received By mwennerg Date 2006-05-09 Time 15:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-06-22 Cont ID  
Sent By nbigby Date 2006-06-27 Time 15:40 Rev Time 0.00
Received By adarroug Date 2006-06-22 Time 13:46 Sent To B
Notes
2006-06-22 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-31 Cont ID  
Sent By adarroug Date 2006-05-31 Time 10:09 Rev Time 0.00
Received By adarroug Date 2006-05-31 Time 10:08 Sent To  
Notes
2006-06-18 00:00:00TO COMM BOARD SPACE #12
2006-05-31 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-18 Cont ID  
Sent By adarroug Date 2006-04-18 Time 10:48 Rev Time 0.00
Received By adarroug Date 2006-04-18 Time 10:48 Sent To E
Notes
2006-04-18 00:00:00WAITING FOR "COMM" BD
 TO "COMM" BD#16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-31 Cont ID  
Sent By adarroug Date 2006-05-09 Time 10:02 Rev Time 0.00
Received By adarroug Date 2006-03-28 Time 12:23 Sent To  
Notes
2006-03-28 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-06-23 Cont ID  
Sent By tgordon Date 2006-06-23 Time 14:25 Rev Time 0.20
Received By tgordon Date 2006-06-23 Time 14:25 Sent To  
Notes
2006-06-23 00:00:00EXHAUST FAN FOR PUMP HOUSE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-05-09 Cont ID  
Sent By tgordon Date 2006-05-09 Time 15:44 Rev Time 0.20
Received By tgordon Date 2006-05-09 Time 15:44 Sent To  
Notes
2006-05-09 00:00:00EXHAUST FAN FOR PUMP HOUSE.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-06-27 Cont ID  
Sent By nbigby Date 2006-06-27 Time 15:41 Rev Time 0.00
Received By nbigby Date 2006-06-27 Time 15:15 Sent To I
Notes
2006-06-27 00:00:00RESUBMITTAL 6/27/06
 PLANNING AND ZONING DEPARTMENT: PASSED
 NADINE BIGBY - PLANNER
  
2006-04-14 00:00:00PLANNING AND ZONING - FAILED
  
 1.APPLICANT SHALL APPLY FOR A MINOR
 AMENDMENT THROUGH THE PLANNING
 DEPARTMENT.
  
 2. A MINOR AMENDMENT IS REQUIRED FOR
 REMOVING THE EXISTING PUMP HOUSE AND
 REPLACING IT IN ANOTHER LOCATION. THE
 NEW LOCATION AND DETAIL AREA FOR THE
 PUMP IS REQUIRED ON THE SITE PLAN.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT NADINE BIGBY AT THE PLANNING
 DEPARTMENT (561) 822-1435.