2006-03-28 00:00:001) THE APPROVED ASSEMBLY SELECTED FOR
 THE MODIFIED BITUMEN ROOF SYSTEM STATES
 GENERAL LIMITAATION #7. HOWEVER
 LIMITATION #7 REQUIRED SIGNED AND SEALED
 CALCULATIONS FROM A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER,ARCHITECT OR ROOF
 CONSULTANT
 WHICH WILL MEET THE REQUIRED (-PSF) FOR
 THE FLAT ROOF.SEE FL985-R1 PAGE 42. ALSO
 REFERE TO PG.45 #7. YOU MAY ALSO CHOOSE
 A DIFFERENT PRODUCT WHICH HAVE PRESSURES
 WHICH ARE HIGHER THAN -89PSF.
  