| 2006-03-27 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | MYRON JACOBS(561) 805 6726 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2004 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | 1) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 2) FBC TABLE 1609.6B.THE SYSTEM |
| | SELECTED FROM THE SUBMITTED FLAT ROOF |
| | PRODUCT APPROVAL NOA HAS A MAXIMUM |
| | DESIGN PRESSURE OF LESS THAN -89 PSF AND |
| | CITES GENERAL LIMITATION #9. GENERAL |
| | LIMITATION #9 PROHIBITS RATIONAL |
| | ANALYSIS OR EXTRAPOLATION TO ENHANCE THE |
| | UPLIFT PRESSURE AT PERIMETER AND CORNER |
| | AREAS BY REDUCING THE FASTENER SPACING |
| | IN THESE AREAS.EITHER SELECT AN |
| | ALTERNATIVE SYSTEM (OR PRODUCT APPROVAL) |
| | THAT DOES NOT CITE GENERAL LIMITATION |
| | #9.ALTERNATIVELY IF THE SELECTED |
| | SYSTEM DOES CITE GENERAL LIMITATION #9, |
| | IT MUST HAVE A MAXIMUM DESIGN PRESSURE |
| | THAT EXCEEDS THE PRESSURE IN ROOF ZONE 3 |
| | (TYPICALLY -89 PSF FOR MEAN ROOF HEIGHT |
| | OF 30 FEET OR LESS). WHEN SUBMITTING |
| | PRODUCT APPROVALS FOR 'BUILT UP OR |
| | MODIFIED ROOFS, HI-LIGHT ORCIRCLE |
| | WHICH ASSEMBY WILL BE USED. BE AWARE OF |
| | THE GENERAL LIMITATION #7 WHICH |
| | SOMETIMES REQUIRES CALCULATIONS PREPARED |
| | BY A FLORIDA REGISTERED PROFESSIONAL |
| | SIGNED AND SEALED. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | TEL:(561)805-6726 |