Plan Review Details - Permit 06031168
Plan Review Stops For Permit 06031168
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-08-16 Cont ID  
Sent By shill Date 2006-08-16 Time 16:13 Rev Time 0.00
Received By shill Date 2006-08-16 Time 16:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-04 Cont ID  
Sent By shill Date 2006-08-04 Time 09:11 Rev Time 0.00
Received By shill Date 2006-08-04 Time 09:10 Sent To  
Notes
2006-08-04 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS REVIEW:
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)SEALS AND TITLE BLOCKS ARE TO BE IN
 COMPLIANCE WITH FAC61G15-23.002,
 FAC61G1-16.003,004.THE SEAL HAS BEEN
 SIGNED BUT NOT DATED, AND CERTIFICATE OF
 AUTHORIZATION INFORMATION IS NOT ON THE
 PLAN.COMPLY WITH ALL REQUIREMENTS OF
 THE REFERENCED CODES, ALL DESIGN
 PROFESSIONALS.
  
 2ND REVIEW - SEE ELECTRICAL COMMENTS IN
 REGARDS TO TITLE BLOCK. FEEL FREE TO
 CONTACT ME IF YOU NEED ASSISTANCE.
  
 3.)ADDRESSED.
  
 8.)THIS IS A LEVEL TWO ALTERATION, FBC
 EB304.
  
 2ND REVIEW - YOUR RESPONSE THAT THE EXIT
 DOORS ARE RATED IS NOTED.PLEASE NOTE
 ON PROJECT INFORMATION THAT THIS IS A
 LEVEL 2 ALTERATION.
  
 9.)ADDRESSED.
  
 10.)NEW COMMENT - SIGN OWNER AGENT
 LINE OF THE ENERGY CALC FBC13-103.1 .

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-09 Cont ID  
Sent By shill Date 2006-05-09 Time 08:53 Rev Time 0.00
Received By shill Date 2006-05-09 Time 07:41 Sent To  
Notes
2006-05-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)SEALS AND TITLE BLOCKS ARE TO BE IN
 COMPLIANCE WITH FAC61G15-23.002,
 FAC61G1-16.003,004.THE SEAL HAS BEEN
 SIGNED BUT NOT DATED, AND CERTIFICATE OF
 AUTHORIZATION INFORMATION IS NOT ON THE
 PLAN.COMPLY WITH ALL REQUIREMENTS OF
 THE REFERENCED CODES, ALL DESIGN
 PROFESSIONALS.
  
 3.)PROVIDE DETAILS FOR THE ACCESSIBLE
 RESTROOMS.SEE FBC11-4.1.6(2)(2)(A).
 INCLUDE DIMENSIONS FOR THE TURNING
 RADIUS, CLEAR FLOORS SPACE FOR FIXTURES,
 FIXTURE DIMENSIONS, GRAB BARS.
  
 4.)SHOW MANEUVERING CLEARANCE, PULL
 SIDE, FBC11-4.13.6, FIGURE 11-25, FOR
 THE BATHROOM DOORS AND CONFERENCE ROOM
 DOOR 526.
  
 5.)THE BREAK ROOM SINK IS TO BE
 ACCESSIBLE FBC11-4.24.THE SINK AS
 SHOWN LACKS THE KNEE CLEARANCE REQUIRED
 FBC-4.24.3.
  
 5.)THE PLAN SHOWS CORRIDORS WITH NO
 FIRE RATING.SEE FBC1002, DEFINITIONS.
  
 6.)INTERIOR FINISHED TO COMPLY WITH
 FBC TABLE 803.5.
  
 7.)THE LAN ROOM IS TO COMPLY WITH
 NFPA75.ALSO SEE FBC712 AS MECHANICAL
 SHEETS WILL REQUIRE REVISIONS.
  
 8.)THIS IS A LEVEL TWO ALTERATION, FBC
 EB304.
  
 9.)SHOW COMPLIANCE WITH FBC EB603.2,
 603.4.1.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-08-17 Cont ID  
Sent By dpalmer Date 2006-08-17 Time 18:36 Rev Time 0.00
Received By dpalmer Date 2006-08-17 Time 17:59 Sent To  
Notes
2006-08-17 00:00:00REDLINED,
  
 LAN RM IS NOT BEING CONSIDERED AS AN IT
 ROOM PER RISK FACTORS AND CONSIDERATIONS
 TAKENS BY THE OWNERS OF RECORD. THE RISK
 FACTORS WERE CONSIDERED AND DO NOT APPLY
 AS OWNER OF RECORD HAS STATED IN LETTER
 WHICH IS PART OF THE RECORD DOCUMENTS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-16 Cont ID  
Sent By dpalmer Date 2006-07-16 Time 08:29 Rev Time 0.00
Received By dpalmer Date 2006-07-16 Time 18:26 Sent To  
Notes
2006-07-16 00:00:00 
 **** UNSAT 2ND REVIEW *****
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
  
 1) NOTE: OK/NO, PLEASE SEE THIS WAS DONW
 ON ELECTRICAL PLANS HOWEVER PLEASE SEE
 COVER SHEETS STILL REFLECT THE 1999
 LS101.
 PLEASE SEE THIS SHOULE BE THE 2003.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE BE SURE PLANS REFLECT
 THE FOLLOWING CODES.
 NFPA-101 2003, NFPA-70 2002, NFPA-72
 2002. PLEASE KNOW, THIS IS FOR
 ELECTRICAL AND ARCHITECTURAL SHEETS.
  
 2) NOTE: NO, PLEASE SEE TITLE BLOCKS ARE
 STILL MISSING THE REQUIRED CERTIFICATE
 OF AUTHORIZATION NUMBER FOR ALL SHEETS
 CONTAINING "INTERIOR ARCHITECTS.
 PLEASE SEE NUMEROUS PRINT OUT FROM THE
 STATE OF FLORIDA WEBSITEDBPR WHICH
 INDICATES THE ARCHITECT OF RECORD MR
 ANGELO LUIS LEBRON BEING THE QUALIFYING
 ARCHITECT AND RESPONSIBLE SUPERVISOR FOR
 A "INTERIOR ARCHITECTS PC" LOCATED IN
 SAN FRANCISCO CA.
 PLEASE SEE THERE A CA NUMBER FOR THAT
 COMPANY SHOWN ON THE STATE'S SITE.
 ** IMPORTANT** PLEASE SEE ALL LOCATIONS
 ON PLANS AND TITLE BLOCK INDICATE THE
 ARCHITECT'S LICENSE NUMBER AS 18990,
 WHEN THE SEAL INDICATES #16990 AND THE
 STATE'S WEBSITE ALSO LIST #16990. THIS
 SEEMS TO BE A MISPRINT OF THE WRONG
 NUMBER. ?? PLEASE SEE THAT A CERTIFICATE
 OF AUTHORIZATION NUMBER IS OBTAINED FOR
 COMPANY AS LISTED ON TITLE BLOCKS AND
 PLEASE BE SURE TO PLACE THIS NUMBER ON
 PLANS AS REQUIRED UNDER FAC 61G1-16.004,
 FS 481.219
 ** THIS IS REQUIRED FOR ALL SHEETS AND
 FOR ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCKS FOR THE ARCHITECT,
 ARCHITECTURAL FIRM.
 PLEASE SEE MISSING THE PRINTED NAME,
 PRINTED LINCENSE # FOR SIAD ARCHITECT.
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION #.
 PLEASE SEE ABOVE ALL REQUIRED UNDER THE
 FLORIDA ADMINISTIVE CODE 61G1-16.004 AND
 FLORIDA STATUES, 481.219
 ** PLEASE KNOW THIS INFORMATION IS
 REQUIRED ON ALL SHEETS AND FOR ALL
 TRADES WHETHER OR NOT COMMENT IS MADE BY
 ANY OF THE OTHER REVIEWERS.
  
 3) NOTE:OK, ENGINEERING FIRM'S TITLE
 BLOCK WAS CORRECTED.
  
 4 )NOTE: OK.
  
 5) NOTE: NO, PLEASE SEE LIGHTING
 CALCULATIONS FOR LIGHTING POWER
 DENSITIES,WATTAGE PERMITTED AND ACTUAL
 WATTAGE PERMITTED COULD NOT BE LOCATED.
 THIS COULD NOT BE LOCATED ON PLANS OR
 ENERGY CALCS.
 PLEASE SEE 13-415.1.ABC.1, TABLES
 415.2.C.1, 415.2.B1.
 IF THIS CAN BE NOTED ON PLANS, THIS
 WOULD BE ACCEPTABLE.
 PLEASE ALSO SEE CONFERENCE ROOM IS NOTED
 AND SHOWN BEING CONTROLLED BY THE TIME
 CLOCK AND OVER RIDE DEVICE AT FRONT DOOR
 LOCATION, HOWEVER THIS SEEMS TO BE A
 "SEPARATE SPACE" WITH FLR TO CEILING
 HEIGHT PARTITIONS, WHICH WOULD ALSO
 REQUIRESEPARATE OVER-RIDE DEVICE(S).
 PLEASE SEE 13-415.1.ABC.1.3
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1, .2 AND .3 ETC
 PLEASE SEE THE SYSTEM FOR ENERGY
 CONSERVATION SHALL BE BASED FOR ENTIRE
 AREA AND THE "OC" AS SHOWN MUST BE
 CAPABLE OF OVER-RIDING THE BASE SYSTEM.
 PLEASE PROVIDE INFORMATION ON TYOE OF OC
 BEING INSTALLED.
 PLEASE SEE SOME AREAS DO NOT INDICATE
 ALL CIRCUITING AS SHOWN AS PART OF THIS
 SYSTEM.
 PLEASE PROVIDE THE SCHEDULE FOR THESE
 FOR ALL AREAS.
 IT WAS NOTED THAT THE TIMED SPRING WOUND
 TIMER IS BEING INSTALLED IN SOME AREAS.
 PLEASE KNOW, COMMON AREA SHALL PROVIDE
 SOME SORT OF NOTICE FOR "LTS OUT" AND/OR
 EGRESS LTS PROVIDED.
 PLEASE PROVIDE DETAIL FOR THE
 OVER-RIDING OF THE TIME CLOCK SYSTEM AS
 NOTED ON PLANS.
 PLEASE SEE ABOVE REFERENCED CODES AS A
 OVERIDE DEVICE OF ONE OR MORE DEPENDING
 ON EGRESSED AREAS SHALL BE IN A READILY
 ACCESSIBLE LOCATION/ENTRANCE TO SPACE.
  
 6) NOTE: OK.
  
 7) NOTE:NO, PLEASE KNOW, IF THE RM IS
 NOT GOING TO RATED AND THE ELECTRICAL
 AND A/C SYSTEM SHOWN IS NOT GOING TO BE
 SHUT DOWN, THEN THE FOLLOWING MUST TAKE
 PLACE.
 THE RESPONSE MENTIONS THE RISK FACTORS
 WERE REVIEWED BY THE "CLIENT" AND BY
 THEIR DETERMINATION THIS ROOM DOES NOT
 REQUIRE RATING ETC.
 PLEASE OBTAIN ORIGINAL LETTER WHICH MUST
 BE ON COMPANY LETTER HEAD WHICH STATES
 THE ADDRESS LOCATION OF CONSIDERATION,
 THE RISK FACTORS, AND THAT THESE HAVE
 BEEN CONSIDERED, AND THAT THERE WOULD NO
 AFFECTS AS LISTED IN NFPA-75.
 *OR WORDS TO THAT AFFECT*
 PLEASE KNOW, THIS LETTER MUST SIGNED BY
 THE OWNER/CLIENT OF RECORD AND SHALL BE
 PROPERLY NOTORIZED UNDER FS 117.05.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLAN NOTES MENTIONS,
 INSTALLATION FOR ROOMS CONTAINING
 COMPUTER EQUIPMENT TO MEET 645.
 PLEASE SEE "LAN RM", PLEASE PROVIDE
 DETAILED INFORMATION ON THIS ROOM AS IT
 SEEMS TO IMPLEMENT THE CRITERIA FOR AN
 "IT" ROOM. NFPA-75
 PLEASE PROVIDE DETAILS FOR ANY AREA
 BEING CONSIDERED AS AN "IT" FOR
 DISCONNECTING MEANS, FIRE RATINGS FOR
 RM, A/C SHUT DOWN ETC.
  
 ** WHEN RESUBMITTING PLANS, PLEASE
 SUBMIT ONE COPY OF THE OLD/VOIDED SHEETS
 FOR REFERENCE ONLY..
  
 PLEASE BE AWARE OF ANY POSSIBLE COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 EELCTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITE IN CONTACTING THIS
 OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected].

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-26 Cont ID  
Sent By dpalmer Date 2006-04-26 Time 15:46 Rev Time 0.00
Received By dpalmer Date 2006-04-26 Time 12:06 Sent To  
Notes
2006-04-26 00:00:00************* UNSAT **********
  
 1) NOTE: PLEASE BE SURE PLANS REFLECT
 THE FOLLOWING CODES.
 NFPA-101 2003, NFPA-70 2002, NFPA-72
 2002. PLEASE KNOW, THIS IS FOR
 ELECTRICAL AND ARCHITECTURAL SHEETS.
  
 2) NOTE: PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCKS FOR THE ARCHITECT,
 ARCHITECTURAL FIRM.
 PLEASE SEE MISSING THE PRINTED NAME,
 PRINTED LINCENSE # FOR SIAD ARCHITECT.
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION #.
 PLEASE SEE ABOVE ALL REQUIRED UNDER THE
 FLORIDA ADMINISTIVE CODE 61G1-16.004 AND
 FLORIDA STATUES, 481.219
 ** PLEASE KNOW THIS INFORMATION IS
 REQUIRED ON ALL SHEETS AND FOR ALL
 TRADES WHETHER OR NOT COMMENT IS MADE BY
 ANY OF THE OTHER REVIEWERS.
  
 3) NOTE: PLEASE SEE COPIES ATTACHED TO
 ELECTRICLA COMMENTS WITH RESPECT TO
 TITLE BLOCK(S) ON PLANS FOR ENGINEERING
 FIRM.
 PLEASE SEE CERTIFICATE OF AUTHORIZATION
 NUMBER AS INDICATED ON PLANS DO NOT
 CORRELATE WITH FIRM AS LISTED ON STATE'S
 WEBSITE. PLEASE SEE THE NUMBER AS SHOWN
 FOR A DIFFERENT COMPANY.
 PLEASE ALSO SEE ATTACHED COPY OF THE
 COMPANY AS LISTED ON STATE'S SITE WHICH
 INDICATES TWO OTHER KLG'S. "KLG INC",
 KLG, LLC, AND THE PREVIOUS MENTIONED
 "KLG/PAIGE INC.
 PLEASE UPDATE ALL LICENSE INFORMATION,
 PLEASE UPDATE ALL TITLE BLOCKS AS
 REQUIRED.
 ** PLEASE KNOW, THIS IS REQUIRED OF ALL
 TRADES AND FOR ALL MEP SHEETS CONTAINING
 THESE SAID TITLE BLOCKS.
  
 4 )NOTE: PLEASE SEE PLANS MUST BE
 RE-SEALED AS THE SEAL AS SHOWN IS NO
 LONGER ACCEPTABLE AS PUBLIC RECORD FOR
 THE FLORIDA BOARD OF PROFESSINAL
 ENGINEER'S. PLEASE SEE FAC 61G15-23.001
 WHICH IN FEB 04 CHANGED TO NOW REQUIRE
 ALL SEALS TO CONTAIN THE WORDING OF
 "LICENSE" AND COULD NO LONGER USE
 "CERTIFICATE". PLEASE KNOW, AN EXTENSION
 WAS GRANTED TO THE DATE OF 12/31/05 TO
 GIVE ALL ENGINEERS 2 YRS TO OBTAIN NEW
 SEALS. WE CAN NO LONGER ACCEPT OLD
 SEALS.
 ** PLEASE SEE THIS IS REQUIRED OF ALL
 SAID PLANS WITH SEAL FROM MR.DANNY
 LUNSTROM PE RESPECTIVELY.
  
  
 5) NOTE: PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1, .2 AND .3.
 PLEASE SEE THE SYSTEM FOR ENERGY
 CONSERVATION SHALL BE BASED FOR ENTIRE
 AREA AND THE "OC" AS SHOWN MUST BE
 CAPABLE OF OVER-RIDING THE BASE SYSTEM.
 PLEASE PROVIDE INFORMATION ON TYOE OF OC
 BEING INSTALLED.
 PLEASE SEE SOME AREAS DO NOT INDICATE
 ALL CIRCUITING AS SHOWN AS PART OF THIS
 SYSTEM.
 PLEASE PROVIDE THE SCHEDULE FOR THESE
 FOR ALL AREAS.
 IT WAS NOTED THAT THE TIMED SPRING WOUND
 TIMER IS BEING INSTALLED IN SOME AREAS.
 PLEASE KNOW, COMMON AREA SHALL PROVIDE
 SOME SORT OF NOTICE FOR "LTS OUT" AND/OR
 EGRESS LTS PROVIDED.
 PLEASE PROVIDE DETAIL FOR THE
 OVER-RIDING OF THE TIME CLOCK SYSTEM AS
 NOTED ON PLANS.
 PLEASE SEE ABOVE REFERENCED CODES AS A
 OVERIDE DEVICE OF ONE OR MORE DEPENDING
 ON EGRESSED AREAS SHALL BE IN A READILY
 ACCESSIBLE LOCATION/ENTRANCE TO SPACE.
  
 6) NOTE: PLEASE PROVIDE COMPLETE LOAD
 CALCUALTIONS ON PANELS INCLUDING NEW
 LOADS TO EXISTING.
 215.5,,220.11,220.3,220.13 ETC.
 PLEASE BE SURE TO INDICATE ALL THE
 CONTINUOUS LOADS AT 125%. 215.3,230.42
  
 7) NOTE: PLEASE SEE PLAN NOTES MENTIONS,
 INSTALLATION FOR ROOMS CONTAINING
 COMPUTER EQUIPMENT TO MEET 645.
 PLEASE SEE "LAN RM", PLEASE PROVIDE
 DETAILED INFORMATION ON THIS ROOM AS IT
 SEEMS TO IMPLEMENT THE CRITERIA FOR AN
 "IT" ROOM. NFPA-75
 PLEASE PROVIDE DETAILS FOR ANY AREA
 BEING CONSIDERED AS AN "IT" FOR
 DISCONNECTING MEANS, FIRE RATINGS FOR
 RM, A/C SHUT DOWN ETC.
  
 ** WHEN RESUBMITTING PLANS, PLEASE
 SUBMIT ONE COPY OF THE OLD/VOIDED SHEETS
 FOR REFERENCE ONLY..
  
 PLEASE BE AWARE OF ANY POSSIBEL COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 EELCTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITE IN CONTACTING THIS
 OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected].

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-08-18 Cont ID  
Sent By mwennerg Date 2006-08-18 Time 11:32 Rev Time 0.00
Received By mwennerg Date 2006-08-18 Time 11:32 Sent To  
Notes
2006-08-17 00:00:00NEEDS, AS FIRE PROTECTION OR FA SHEETS
 DO NOT HAVE STAMPS.
  
 ALSO, THE FIRE DEVICE SPECS SHOULD NOT
 BE ATTACHED AS THESE ARE REQUIRED UNDER
 SEPARATE PERMITS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-07-12 Cont ID  
Sent By mcarsill Date 2006-07-12 Time 11:29 Rev Time 0.00
Received By mcarsill Date 2006-07-12 Time 11:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-06-07 Cont ID  
Sent By mwennerg Date 2006-06-07 Time 10:24 Rev Time 0.00
Received By mwennerg Date 2006-06-07 Time 10:24 Sent To  
Notes
2006-06-07 00:00:00***DENIED***
  
 1) PLEASE PROVIDE MINIMUM INTERIOR
 FINISH CLASSIFICATION FORE WALLS AND
 CEILING IN TERMS OF CLASS A,B OR C.
  
 2) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
 3) IN ADDITION TO FIRE SPRINKLER,
 SEPARATE SHOP DRAWINGS AND PERMIT
 REQUIRED FOR FIRE ALARM REMODEL.
  
 4) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-12 Cont ID  
Sent By adarroug Date 2006-08-12 Time 14:22 Rev Time 0.00
Received By adarroug Date 2006-08-12 Time 14:22 Sent To  
Notes
2006-08-12 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-26 Cont ID  
Sent By adarroug Date 2006-06-26 Time 12:04 Rev Time 0.00
Received By adarroug Date 2006-06-26 Time 12:04 Sent To  
Notes
2006-07-11 00:00:00TO "COMM" BD#2
2006-06-26 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-07 Cont ID  
Sent By shill Date 2006-06-07 Time 10:02 Rev Time 0.00
Received By rbrown Date 2006-03-24 Time 17:19 Sent To  
Notes
2006-04-18 00:00:00TO "COMM" BD#42
2006-03-24 00:00:00WAITING FOR COMM BOARD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-10-18 Cont ID  
Sent By hmoser Date 2006-10-18 Time 15:46 Rev Time 0.00
Received By hmoser Date 2006-10-18 Time 15:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-08-18 Cont ID  
Sent By tgordon Date 2006-08-18 Time 10:32 Rev Time 0.30
Received By tgordon Date 2006-08-16 Time 14:49 Sent To  
Notes
2006-08-16 00:00:00RETURNED TO LUIS M.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-08-04 Cont ID  
Sent By tgordon Date 2006-08-04 Time 11:39 Rev Time 0.20
Received By tgordon Date 2006-08-04 Time 11:39 Sent To  
Notes
2006-08-04 00:00:00*** DENIED ***
 1) SEE OTHER REVIEW NOTES REGUARDING
 TITLE BLOCK AND SEALS, PLEASE CORRECT.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-05-08 Cont ID  
Sent By tgordon Date 2006-05-08 Time 16:00 Rev Time 0.45
Received By tgordon Date 2006-05-08 Time 16:00 Sent To  
Notes
2006-05-08 00:00:00*** DENIED ***
 1) PLEASE SEE ELECTRICAL REVIEW NOTES
 #2-4 REGUARDING TITLE BLOCK, LICENSE,
 AND SEAL.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-08-17 Cont ID  
Sent By pschmitz Date 2006-08-17 Time 14:06 Rev Time 0.00
Received By pschmitz Date 2006-08-17 Time 14:06 Sent To  
Notes
2006-08-17 00:00:00RE- SUB

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-08-05 Cont ID  
Sent By pschmitz Date 2006-08-05 Time 09:11 Rev Time 0.00
Received By pschmitz Date 2006-08-05 Time 09:15 Sent To  
Notes
2006-08-05 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT PLUMBING
 PLANS.
  
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-05-31 Cont ID  
Sent By kstevens Date 2006-05-31 Time 16:22 Rev Time 0.00
Received By kstevens Date 2006-05-31 Time 16:22 Sent To  
Notes
2006-05-31 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS: DATE
 REQUIRED ON THE SEAL WHEN THE SEAL AND
 SIGNATURE ARE AFFIXED TO THE DOCUMENTS.
 THE TITLE BLOCK MUST, AT A MINIMUM,
 CONTAIN AMONG OTHER REQUIREMENTS, (2)
 FIRM LICENSE NUMBER, (5) A SPACE FOR THE
 SIGNATURE & DATED SEAL, & (6) A SPACE
 FOR THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT. FAC 61G1-16.003,
 61G1.004(2)(5)(6) & FS 481.219,
 481.2055.
  
 2. ALL PLUMBING, MECHANICAL, FIRE, &
 ELECTRICAL SHEETS: ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME, ADDRESS AND
 LICENSE NUMBER ON EACH SHEET. IF
 PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE
 NUMBER, AS WELL AS, THE NAME, ADDRESS,
 AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS ON EACH
 SHEET. NOTE THAT THE BUSINESS NAME ON
 THE TITLE BLOCK IS DIFFERENT FROM THE
 BUSINESS REGISTERED WITH THE DBPR
 WEBSITE. (KLG/PAIGE INC.). PLEASE
 CORRECT TITLE BLOCKS THE REFLECT
 INFORMATION IN DBPR WEBSITE. (SEE
 ATTACHED SHEETS).
  
 3. ALL PME & FIRE SHEETS. NEW SEAL
 REQUIRED FOR ENGINEER OF RECORD.
 "LICENSE" SHALL APPEAR ON ALL SEALS AS
 OF 01-01-06 AS THAT IS THE END OF A 2
 YEAR GRACE PERIOD FROM THE FLORIDA BOARD
 OF PROFESSIONAL ENGINEERS. (SEE ATTACHED
 SHEET).
  
 4. SHT A7.0 ELEVATION 1 A FORWARD
 APPROACH CLEAR FLOOR SPACE IS REQUIRED
 FOR THE BREAK ROOM SINK EXTENDING A
 MAXIMUM OF 19" UNDERNEATH THE SINK.
 CABINET DOORS ARE NOT APPROVED IN THE
 CLEAR FLOOR SPACE. SECTION 11-4.24.5.
 SHOW ON THE FLOOR PLAN.
  
 5. SHT P1.0 WATER SUPPLY TO THE
 HUMIDIFIER SHALL HAVE BACKFLOW
 PROTECTION. SECTION 608.3. AN RPZV
 BACKFLOW WILL BE REQUIRED, AND BE
 INSTALLED A MAXIMUM 4' ABOVE THE FLOOR
 FOR SERVICING AND CERTIFICATION. PLEASE
 INDICATE ON PLANS. SECTION 608.13.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6713
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy