Plan Review Details - Permit 06031114
Plan Review Stops For Permit 06031114
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-02-22 Cont ID  
Sent By jwitmer Date 2007-02-22 Time 15:51 Rev Time 1.11
Received By jwitmer Date 2007-02-22 Time 15:51 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-08 Cont ID  
Sent By jwitmer Date 2006-08-08 Time 07:11 Rev Time 0.77
Received By jwitmer Date 2006-08-08 Time 07:11 Sent To  
Notes
2006-08-08 00:00:00PERMIT: 06031114
 ADD: 580 VILLAGE BLVD
 CONT: TEKTRON ELECTRICAL SYSTEMS
 TEL: (561)844-3156
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 1)2ND REQUEST,GENERATOR SLAB & ANCHOR
 REQUIREMENT, PLEASE PROVIDE SIZE OF
 GENERATOR(WXL), PLUS PROVIDE PLANS WITH
 THE INFORMATIONDEPICTING HOLD DOWN
 BRACKETS, TYPE OFFASTENER, AND THE
 MINIMUM EDGE DISTANCE THE DEVICE
 REQUIRES WITHOUT LOAD REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
  
 THE PLANS INDICATE THE LENGTH OF
 THE SLAB MISSING THE WIDTH OF THE
 PROPOSED SLAB.
  
  
 2) 2ND REQUEST, 110.2* W. P. B.
 ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED. THIS DESIGN IS
 UNDER THE 2004 FBC, WHICH USES ASCE 7-02
 NOT 7-98. CORRECT. THE M).1 SHEET HAS A
 NOTE THAT THE DESIGN COMPLY WITH HIGH
 VELOCITY HURRICANE ZONE(FBC 1820.5).
 THIS IS A REQUIREMENET FOR DADE AND
 BROWARD COUNTIES UNENFORCEABLE IN PALM
 BEACH COUNTY.
 B) PROVIDE OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3. SOME
 OCCUPANCIES REQUIRE EMERGENCY GENERATORS
 WITH MINIMUM STANDARDS.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601. AGAIN
 PROVIDE THE MINIMUM BUILDING TYPE, SOME
 BUILDING TYPES REQUIRE GENERATORS WITH
 MINIMUM STANDARDS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-08 Cont ID  
Sent By jwitmer Date 2006-05-08 Time 16:29 Rev Time 0.77
Received By jwitmer Date 2006-05-08 Time 16:29 Sent To  
Notes
2006-05-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06031114
 ADD: 580 VILLAGE BLVD
 CONT: TEKTRON ELECTRICAL SYSTEMS
 TEL: (561)844-3156
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 1) GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
  
 2)110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-01-22 Cont ID  
Sent By dpalmer Date 2007-01-22 Time 11:37 Rev Time 0.00
Received By dpalmer Date 2007-01-22 Time 11:37 Sent To  
Notes
2007-01-22 11:38:17STAMPED SUBMITTALS OK FOR ELEC, PENDING OTHER TRADES
 REVIEWS.
 STAMPED:
 GEN.
 ATS,
 UPS.
 AND E-SHEETS

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-06 Cont ID  
Sent By dpalmer Date 2006-08-06 Time 19:02 Rev Time 0.00
Received By dpalmer Date 2006-08-06 Time 18:30 Sent To  
Notes
2006-08-06 00:00:00********** UNSAT2ND REVIEW ***********
  
 ** PLEASE SEE BELOW FOR NOTES FROM
 PREVIOUS REVIEW AN NEW NOTES WHICH NEED
 TO BE ADDRESSED.
  
 *** IMPORTANT **
 BEFORE RSUBMITTING PLANS!!
 MUST SUBMIT TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. PLEASE SEE SOME SETS
 CONTAIN OLD SHEETS WHICH ARE STILL
 RELEVANT HOWEVER THESE ARE NOT IN NEW
 SETS. PLEASE SEE SOME ITEMS THERE IS
 ONLY ONE COPYOF AND IT IS REQUIRED TO
 SUBMIT TWO OF ALL ITEMS. PLEASE PLACE
 ALL ITEMS INTO TWO SETS IN A NEAT AND
 ORDERLY FASHION. THIS WILL HELP IN THE
 REVIEW PROCESS AND TO HELP EXPEDITE THE
 REVIEW PROCESS FOR PERMIT ISSUANCE..
 THIS OFFICE DOES NOT HAVE THE TIME TO DO
 THIS.
  
 1)NOTE: NO, PLEASE SEE THE SPECS WERE
 SUBMITTED, HOWEVER COULD NOT LCOATE ANY
 LISTINGS FROM ANY NRTL. THE CODE BELOW
 WHICH WAS REFERENCED IN PREVIOUS REVIEW
 WAS INCORRECT.SHOULD HAVE BEEN 110.3,
 90.8
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE TO SUBMIT ALL
 SPECS FOR ALL UPS SYSTEMS SHOWING A A
 LISTING FROM A NRTL.
 215.5
  
 2) NOTE:NO, PLEASE SEE GEN AND ATSARE
 OK, HOWEVER NOW UPON REVIEWING SPEC ON
 GEN, COULD NOT LOCATE THE WP HOUSING
 ASSOCITED WITH SAID GEN.
 FBC 106.1.2, 90.8
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT ALL MANUFACTURES
 CUT/SPEC SHEETS FOR GENERATOR AND ATS.
 UNABLE TO VERIFY SOME ITEMS FOR CODE
 COMPLIANCE.
  
 3) NOTE:OK, HOWEVER PLEASE SEE PLANS NOW
 REFLECT THE LATEST EDITION. PLEASE KNOW
 THE LATEST EDITON WOULD BE THE 2005 NEC,
 AND AS OF YET THE STATE OF FLORIDA HAS
 NOT ADOPTED SAID CODE. PLEASE LIST THE
 2002 NFPA-70 AND 2002 NFPA-110
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS REFERENCE THE
 2001 FBC.
 PLEASE KNOW AS OF OCT 1ST, 2005 THE NEW
 FBC 2004 IS IN EFFECT.
 PLEASE ALSO REFERENCE NFPA-110
 STANDARDS.
  
 4) NOTE: OK, NEW MAIN ADDED
  
 ** NEW NOTES **
  
 5) NOTE: AS STATED IN THE BEGINING OF
 THIS REVIEW PLEASE SUBMIT TWO COMPLETE
 SETS. PLEASE SEE ONE SET IS MISSING
 SHEET E2.1. PLEASE SEE SHEETS ARE NOT
 SIGNED, DATED OR SEALED BY THE ENGINEER
 OF RECORD.
 PLEASE ALSO SEE OTHER SHEET FOR A/C
 INFORMATION ARE SIGNED, DATED AND
 SEALED, HOWEVER NO TITLE BLOCKS ARE ON
 PLANS AS REQUIRED. FAC 61G15-23.002
 FS 471.025
  
 6) NOTE: PLEASE SEE DISTANCE FOR SET
 BACKS OF GEN COULD NOT LOCATED ON COPY
 OF THE SURVEYS, SITE PLANS OR LANDSCAPE
 PLANS SUBMITTED.
 PLEASE ALSO SEE ANY SITE LANDSCAPE PLANS
 DONE BY THE LANDSCAPE ARCHITECT AND
 FIRM, SHALL BE SIGNED, DATED AND SEALED,
 PER FS 481.321
 THIS IS REQUIRED EVEN IF COMMENT IS NOT
 MADE BY ZONING.
  
  
  
  
 ** PLEASE SEE POSSIBLE ZONING AND
 BUILDING COMMENTS, AS A SURVEY/SITE PLAN
 SHOWING ALL SETBACKS FOR LOCATION OF GEN
 WAS NOT SUBMITTED, AND ALSO A SLAB
 DETAIL AND ELEVATION COULD NOT BE
 LOCATED IN PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-26 Cont ID  
Sent By dpalmer Date 2006-04-26 Time 11:37 Rev Time 0.00
Received By dpalmer Date 2006-04-26 Time 10:47 Sent To  
Notes
2006-04-26 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE BE SURE TO SUBMIT ALL
 SPECS FOR ALL UPS SYSTEMS SHOWING A A
 LISTING FROM A NRTL.
 215.5
  
 2) NOTE:PLEASE SUBMIT ALL MANUFACTURES
 CUT/SPEC SHEETS FOR GENERATOR AND ATS.
 UNABLE TO VERIFY SOME ITEMS FOR CODE
 COMPLIANCE.
  
 3) NOTE: PLEASE SEE PLANS REFERENCE THE
 2001 FBC.
 PLEASE KNOW AS OF OCT 1ST, 2005 THE NEW
 FBC 2004 IS IN EFFECT.
 PLEASE ALSO REFERENCE NFPA-110
 STANDARDS.
  
 4) NOTE: PLEASE MEANS OF DISCONNECT FOR
 POWER COMING FROM GENERATOR SHALL BE
 GROUPED WITH EXISTING MAIN(S).
 230.72,230.76,230.79, 225.31-225.39.
 UNABLE TO VERIFY AT THIS TIME AS
 EXISTING MAIN FOR BUILDING IS NOT SHOWN.
  
  
 ** PLEASE SEE POSSIBLE ZONING ABD
 BUILDING COMMENTS, AS A SURVEY/SITE PLAN
 SHOWING ALL SETBACKS FOR LOCATION OF GEN
 WAS NOT SUBMITTED, AND ALSO A SLAB
 DETAIL AND ELEVATION COULD NOT BE
 LOCATED IN PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
 ** PLEASE BE AWARE OF COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT THE PLANS
 SUBMITTED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-02-20 Cont ID  
Sent By mawillia Date 2007-02-20 Time 16:31 Rev Time 0.00
Received By mawillia Date 2007-02-20 Time 16:30 Sent To  
Notes
2007-02-20 16:32:23*****APPROVED*****
  
  
 SHEET E1.1 WAS STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-09-05 Cont ID  
Sent By mwennerg Date 2006-09-05 Time 15:00 Rev Time 0.00
Received By mwennerg Date 2006-09-05 Time 15:00 Sent To  
Notes
2006-09-05 00:00:00***DENIED***
  
 1) WORK SHALL COMPLY WITH NFPA 110,
 STANDARD FOR EMERGENCY AND STANDBY POWER
 SYSTEMS. PLEASE ACKNOWLEDGE AND INDICATE
 ON PLANS.
  
 2) PLEASE CLARIFY FUEL SOURCE, NATURAL
 GAS, PROPANE ETC.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-05-24 Cont ID  
Sent By nmccray Date 2006-05-24 Time 15:20 Rev Time 0.00
Received By nmccray Date 2006-05-24 Time 15:13 Sent To  
Notes
2006-05-24 00:00:00*********DENIED********************
  
 1) THE INSTALLATION SHALL COMPLY NFPA
 110 STANDARD FOR EMERGENCY & STANDBY
 POWER SYSTEMS.
  
 2) PLEASE PROVIDE CUT/SPEC'S SHEETS ON
 THE GENERATOR
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status N Date 2006-05-13 Cont ID  
Sent By pschmitz Date 2006-05-13 Time 14:48 Rev Time 0.00
Received By pschmitz Date 2006-05-13 Time 14:48 Sent To  
Notes
2006-05-13 00:00:00NATURAL GAS

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2007-04-25 Cont ID  
Sent By mperson Date 2007-04-25 Time 15:13 Rev Time 0.33
Received By mperson Date 2007-04-25 Time 15:13 Sent To PC
Notes
2007-04-25 15:15:09REVISION: CHANGED PIPING FROM ABOVE GROUND GALVANIZED
 TO UNDERGROUND PE.

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2007-04-06 Cont ID  
Sent By mperson Date 2007-04-06 Time 15:56 Rev Time 0.45
Received By mperson Date 2007-04-06 Time 15:56 Sent To PC
Notes
2007-04-06 16:16:34REVISION DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION REQUIRED FOR GAS
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PLEASE NOTE THAT ON SHEET M1.1 THERE IS AN APPROVED
 GAS RISER THAT IS SIGNED AND SEALED BE DANIEL E.
 THOMPSON FLA. REG. NO. 33289 OF THE "THOMPSON &
 YOUNGROSS ENGINEERING CONSULTANTS, LLC" AND ANY
 REVISIONS TO THAT GAS RISER NEEDS TO BE SIGNED AND
 SEALED BY SAID DESIGN PROFESSIONAL PER CHAPTER 471,
 FLORIDA STATUTES. PLEASE NOTE THAT A GAS PERMIT IS
 REQUIRED FOR THIS WORK AND ONE HAS NOT BEEN ISSUED AS
 OF THIS DATE 4/6/07.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-02-21 Cont ID  
Sent By kstevens Date 2007-02-21 Time 11:12 Rev Time 0.00
Received By kstevens Date 2007-02-21 Time 11:12 Sent To  
Notes
2007-02-21 11:14:53PER CONTRACTOR, (R.B.) THE PIPING IS NOT UNDERGROUND,
 BUT STRAPPED TO THE SLAB.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-08-12 Cont ID  
Sent By pschmitz Date 2006-08-12 Time 09:07 Rev Time 0.00
Received By pschmitz Date 2006-08-12 Time 09:07 Sent To  
Notes
2006-08-12 00:00:00 
 PAUL SCHMITZ
 FBC 2004 FUEL GAS CODE, PLAN REVIEW
  
  
 NEW COMMENTSUNSAT
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT.
  
 1) SHT M1.1 GAS SYSTEM NOTES:
 REMOVE NOTES THAT DO NOT PERTAIN TO THE
 GENERATOR INSTALLATION.
  
 2. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 3. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED,FOR EACH PIPE SIZE BEING
 USED.
  
 4. TYPE OF GAS, (LP OR NATURAL)
  
 5.BTU LOAD OF GENERATOR UNDER FULL LOAD.
 REFER TO THE FBC-2004 FUEL GAS CODE
 SECS. 401.8 THRU 402.6.1 AND TABLES
 402.4(1) THRU 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE SYSTEM PER FBC-2004 FUEL
 GAS CODE APPENDIX A - USE OF CAPACITY
 TABLES A.3.1(4).
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7 WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND,
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 8 SEE OTHER PLAN REVIEW COMMENTS, THAT
 MAY EFFECT PLUMBING PLAN REVIEW.
  
  
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-05-13 Cont ID  
Sent By pschmitz Date 2006-05-13 Time 14:52 Rev Time 0.00
Received By pschmitz Date 2006-05-13 Time 14:52 Sent To  
Notes
2006-05-13 00:00:00 
  
 PAUL SCHMITZ
 FBC 2004 FUEL GAS CODE, PLAN REVIEW
  
  
 UNSAT
 1) SHT E2.1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304
 .
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
  
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 10) SEE OTHER PLAN REVIEW COMMENTS, THAT
 MAY EFFECT PLUMBING PLAN REVIEW.
  
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-04-19 Cont ID  
Sent By adarroug Date 2007-04-19 Time 13:05 Rev Time 0.00
Received By adarroug Date 2007-04-19 Time 13:05 Sent To M
Notes
2007-04-19 13:05:49TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-27 Cont ID  
Sent By spalmer Date 2007-03-27 Time 18:38 Rev Time 0.00
Received By spalmer Date 2007-03-27 Time 18:38 Sent To G
Notes
2007-03-27 18:38:51TO MIKE PERSON

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-01-09 Cont ID  
Sent By adarroug Date 2007-01-09 Time 18:43 Rev Time 0.00
Received By adarroug Date 2007-01-09 Time 18:43 Sent To  
Notes
2007-01-22 08:35:25TO "COMM" BD#51
2007-01-09 18:44:03WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-05 Cont ID  
Sent By dpalmer Date 2006-08-05 Time 14:31 Rev Time 0.00
Received By dpalmer Date 2006-08-05 Time 14:31 Sent To  
Notes
2006-08-05 00:00:00TO COMM BOARD #28

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-21 Cont ID  
Sent By adarroug Date 2006-07-21 Time 15:23 Rev Time 0.00
Received By adarroug Date 2006-07-21 Time 15:23 Sent To  
Notes
2006-07-21 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-24 Cont ID  
Sent By adarroug Date 2006-05-24 Time 15:21 Rev Time 0.00
Received By adarroug Date 2006-03-24 Time 13:27 Sent To  
Notes
2006-03-24 00:00:00WAITING FOR COMM BOARD.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-04-20 Cont ID  
Sent By tgordon Date 2007-04-20 Time 08:50 Rev Time 0.30
Received By tgordon Date 2007-04-20 Time 08:50 Sent To G
Notes
2007-04-20 08:52:53GAS REVISION TO PLANS PAGE M1.1, NO MECHANICAL CHANGES
 RE-STAMP.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-01-22 Cont ID  
Sent By tgordon Date 2007-01-22 Time 15:32 Rev Time 0.30
Received By tgordon Date 2007-01-22 Time 15:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-08-15 Cont ID  
Sent By tgordon Date 2006-08-15 Time 09:38 Rev Time 0.25
Received By tgordon Date 2006-08-15 Time 09:38 Sent To  
Notes
2006-08-15 00:00:00*** DENIED ***
 1) NEED TWO COPYS OF THE A/C SIZING
 CALCULATIONS, AND THEY NEED THE
 ENGINEERSINFORMATION ON THEM NAME
 ADDRESS, LICENSE NUMBER, ECT. ON TITLI
 BLOCK OR LETTER HEAD WITH HIE SEAL, PER
 FAC 61G15-23.002 .
  
 2) SEE ELECTRICAL REVIEW NOTE REGUARDING
 TWO COMPLETE SETS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-05-08 Cont ID  
Sent By tgordon Date 2006-05-08 Time 14:02 Rev Time 0.30
Received By tgordon Date 2006-05-08 Time 14:02 Sent To  
Notes
2006-05-08 00:00:00*** DENIED ***
 1) SHOW SIZES OF ALL SUPPLY AIR DUCTS
 (FLEX).
  
 2) PLEASE PROVIDE OUTDOOR AIR FOR AHU
 #1, PER 2004 FBC/M 401 .
  
 3) RETURN AIR TRANSFER DUCTS ARE
 UNDER-SIZED SEE NOTE #4 (A).
  
 4)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-05-13 Cont ID  
Sent By pschmitz Date 2006-05-13 Time 14:49 Rev Time 0.00
Received By pschmitz Date 2006-05-13 Time 14:49 Sent To  
Notes
2006-05-13 00:00:00NATURAL GAS

Review Stop Z ZONING
Rev No 3 Status P Date 2007-01-26 Cont ID  
Sent By kdfreema Date 2007-01-26 Time 08:35 Rev Time 0.00
Received By kdfreema Date 2007-01-26 Time 08:35 Sent To  
Notes
2007-01-26 08:38:36A LANDSCAPED SCREEN WALL IS REQUIRED. THE WALL SHALL BE
 INSTALLED UNDER A SEPERATE PERMIT.
2007-01-22 11:16:19NEW REVISED SITE, SURVEY AND LANDSCAPE SHEETS

Review Stop Z ZONING
Rev No 2 Status P Date 2006-08-17 Cont ID  
Sent By kdfreema Date 2006-08-17 Time 17:50 Rev Time 0.00
Received By kdfreema Date 2006-08-17 Time 17:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-05-12 Cont ID  
Sent By jroach Date 2006-05-12 Time 19:28 Rev Time 0.00
Received By jroach Date 2006-05-12 Time 19:28 Sent To  
Notes
2006-05-12 00:00:005/12/06 ***FAILED***
  
 1) MINOR AMENDMENT TO THE PLANNED
 DEVELOPMENT SHALL BE SUBMITTED AND
 APPROVED BY THE PLANNING AND ZONING
 DEPARTMENT PRIOR TO APPROVAL OF BUILDING
 PERMIT.
  
 2) SURVEY SHALL BE PROVIDED.
  
 3) SITE PLAN SHALL BE PROVIDED
 INDICATING THE LOCATION OF ALL EXTERIOR
 IMPROVEMENTS.
  
 4) ELEVATIONS OF GENERATOR AND OTHER
 EQUIPMENT LOCATED ON THE EXTERIOR SHALL
 BE PROVIDED.
  
 5) GENERATOR AND OTHER EXTERIOR
 EQUIPMENT WILL NEED TO BE SCREENED WITH
 A SOLID WALL/FENCE AND LANDSCAPING.
 LANDSCAPE PLANS SHALL BE PROVIDED.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 SENIOR PLANNER, AT (561) 822-1435.