Plan Review Details - Permit 06031113
Plan Review Stops For Permit 06031113
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-07-06 Cont ID  
Sent By alange Date 2006-07-06 Time 14:41 Rev Time 0.50
Received By alange Date 2006-07-06 Time 14:41 Sent To  
Notes
2006-07-06 00:00:00TRUSS SUBMITTAL REVIEWED AND APPROVED

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-05-16 Cont ID  
Sent By alange Date 2006-05-16 Time 09:07 Rev Time 1.50
Received By alange Date 2006-05-16 Time 09:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-18 Cont ID  
Sent By alange Date 2006-04-18 Time 08:40 Rev Time 2.00
Received By alange Date 2006-04-18 Time 08:29 Sent To  
Notes
2006-04-18 00:00:00DENIED
  
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUE HAS BEEN REVISED TO
 $50,526.ADDITIONAL PERMIT FEES ARE
 DUE.
  
 3.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC AND SIGN.
  
 4.PRODUCT APPROVALS REQUIRED FOR
 LINTELS.
  
 5.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 6.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 7.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
  
 8.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 9. ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2005 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.INCLUDING ALL
 CODE SECTIONS MENTIONED.SEE A-8 DESIGN
 LOADS.
  
 10.R613.6.2 BUCKS SHALL EXTEND BEYOND
 THE INTERIOR FACE OF THE WINDOW OR DOOR
 FRAME SUCH THAT FULL SUPPORT OF THE
 FRAME IS PROVIDED.SQUARE EDGE BUCK.
 SHOW REVISED DETAIL.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-05-11 Cont ID  
Sent By jleahy Date 2006-05-11 Time 18:05 Rev Time 1.00
Received By jleahy Date 2006-05-11 Time 17:56 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-10 Cont ID  
Sent By jleahy Date 2006-04-10 Time 07:51 Rev Time 0.45
Received By jleahy Date 2006-04-10 Time 07:51 Sent To M
Notes
2006-04-10 00:00:00LOAD CALCULATION ONLY SHOWS NEW LOADS
  
 NO INFORMATION ON EXISTING215.5
  
 NO A/C ON PLANS
  
 NO ARC FAULTS SHOWN210.12
  
 QUESTIONS CALL PHILLIP PETTY805-6742

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-06 Cont ID  
Sent By adarroug Date 2006-07-06 Time 09:25 Rev Time 0.00
Received By adarroug Date 2006-07-06 Time 09:25 Sent To B
Notes
2006-07-06 00:00:00TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-11 Cont ID  
Sent By adarroug Date 2006-05-11 Time 15:32 Rev Time 0.00
Received By adarroug Date 2006-05-11 Time 15:32 Sent To E
Notes
2006-05-11 00:00:00TO "JLEAHY" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-05 Cont ID  
Sent By adarroug Date 2006-04-05 Time 10:09 Rev Time 0.00
Received By adarroug Date 2006-04-05 Time 10:09 Sent To E
Notes
2006-04-05 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-18 Cont ID  
Sent By adarroug Date 2006-04-18 Time 08:40 Rev Time 0.00
Received By alange Date 2006-03-24 Time 13:20 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-05-15 Cont ID  
Sent By tgordon Date 2006-05-15 Time 14:14 Rev Time 0.15
Received By tgordon Date 2006-05-15 Time 14:14 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-04-10 Cont ID  
Sent By tgordon Date 2006-04-10 Time 11:05 Rev Time 0.25
Received By tgordon Date 2006-04-10 Time 11:05 Sent To P
Notes
2006-04-10 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY PREPARER AND OWNER/AGENT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-05-15 Cont ID  
Sent By jleech Date 2006-05-15 Time 12:52 Rev Time 0.00
Received By jleech Date 2006-05-15 Time 12:52 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-04-10 Cont ID  
Sent By jleech Date 2006-04-10 Time 14:13 Rev Time 0.00
Received By jleech Date 2006-04-10 Time 14:13 Sent To B
Notes
2006-04-10 00:00:00DENIED;
 1. CODES TO BE USED ARE FBC-2004 NOT
 2001.
 2.MINIMUM PLUMBING FACILITIES REQUIRED
 INCLUDE A AUTOMATIC CLOTHES WASHER, NONE
 SHOWN ON DRAWINGS. SEE FBC-2004 PLUMBING
 TABLE 403.1.7(R-3).
 3.PLUMBING NOTES;A/C CONDENSATE TO
 DISCHARGE TO THE OUTSIDE 12" FROM THE
 BUILDING, NOT SEFE WASTED TO SANITARY.
 PLEASE DELETE NOTE.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-04-04 Cont ID  
Sent By alange Date 2006-04-18 Time 08:40 Rev Time 0.00
Received By mmclean Date 2006-04-04 Time 08:13 Sent To I
Notes
2006-04-04 00:00:00AN ADDITION IN THE REAR OF THE EXISTING
 STRCUTURE.