Plan Review Details - Permit 06031107
Plan Review Stops For Permit 06031107
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-07 Cont ID  
Sent By jwitmer Date 2006-08-07 Time 10:40 Rev Time 0.77
Received By jwitmer Date 2006-08-07 Time 10:40 Sent To  
Notes
2006-08-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06031107
 ADD: 345 30TH ST
 CONT: WILLIAM J. HOLTEC
 TEL: (954)731-2998
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 /2004 EXISTING BUILDINGS- LEVEL 1
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1)CHALAIRE & ASSOCIATES, INC. IS MISSING
 THEIR:471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ENGINEERING SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 2) COMPLIED.
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) COMPLIED.
  
 6)2ND REQUEST, 1009.11 HANDRAILS.
 STAIRWAYS SHALL HAVE HANDRAILS ON EACH
 SIDE. HANDRAILS SHALL BE ADEQUATE IN
 STRENGTH AND ATTACHMENT IN ACCORDANCE
 WITH SECTION 1607.7 . HANDRAILS FOR
 RAMPS, WHERE REQUIRED BY SECTION 1010.8
  
 7) 2ND REQUEST,HANDRAIL
 1009.11.5 HANDRAIL EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD
 OR THE WALKING SURFACE OR SHALL BE
 CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT STAIR FLIGHT. WHERE HANDRAILS
 ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE
 HANDRAILS SHALL EXTEND HORIZONTALLY AT
 LEAST 12 INCHES (305 MM) BEYOND THE TOP
 RISER AND CONTINUE TO SLOPE FOR THE
 DEPTH OF ONE TREAD BEYOND THE BOTTOM
 RISER.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-08 Cont ID  
Sent By jwitmer Date 2006-05-08 Time 15:11 Rev Time 1.11
Received By jwitmer Date 2006-05-08 Time 15:11 Sent To  
Notes
2006-05-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06031107
 ADD: 345 30TH ST
 CONT: WILLIAM J. HOLTEC
 TEL: (954)731-2998
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 /2004 EXISTING BUILDINGS- LEVEL 1
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)CHALAIRE & ASSOCIATES, INC. IS MISSING
 THEIR:471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ENGINEERING SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 2) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
  
 3) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4) TABLE 1607.1 PROVIDE LIVE LOADS FOR
 FIRE ESCAPE.
  
 5)1012.2 HEIGHT.
 GUARDS SHALL FORM A PROTECTIVE BARRIER
 NOT LESS THAN 42 INCHES (1067 MM) HIGH,
 MEASURED VERTICALLY ABOVE THE LEADING
 EDGE OF THE TREAD, ADJACENT WALKING
 SURFACE OR ADJACENT SEATBOARD. 38" FOR
 R-2 CAN ONLY BE USED FOR WITHIN R-2
 DWELLING UNIT WHEN THE TOP RAIL OF THE
 GUARD ALSO SERVES AS A HANDRAIL.
  
 6) 1009.11 HANDRAILS.
 STAIRWAYS SHALL HAVE HANDRAILS ON EACH
 SIDE. HANDRAILS SHALL BE ADEQUATE IN
 STRENGTH AND ATTACHMENT IN ACCORDANCE
 WITH SECTION 1607.7 . HANDRAILS FOR
 RAMPS, WHERE REQUIRED BY SECTION 1010.8
  
 7)HANDRAIL
 1009.11.5 HANDRAIL EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD
 OR THE WALKING SURFACE OR SHALL BE
 CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT STAIR FLIGHT. WHERE HANDRAILS
 ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE
 HANDRAILS SHALL EXTEND HORIZONTALLY AT
 LEAST 12 INCHES (305 MM) BEYOND THE TOP
 RISER AND CONTINUE TO SLOPE FOR THE
 DEPTH OF ONE TREAD BEYOND THE BOTTOM
 RISER.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-05 Cont ID  
Sent By dpalmer Date 2006-08-05 Time 10:03 Rev Time 0.00
Received By dpalmer Date 2006-08-05 Time 10:01 Sent To  
Notes
2006-08-05 00:00:00*** USNAT 2ND REVIEW ***
  
 1) NOTE: PLEASE SEE NOTE #2 FROM
 PREVIOUS REVIEW WHICH REQUESTED TO
 PLEASE PROVIDE NEW OR SHWOING NEW
 EMERGENCY EGRESS AND NORMAL EGRESS
 LIGHTING AS REQUIRED IN NFPA-101
 7.8.1.3, 7.9.2.2
 PLEASE PROVIDE MIN FT CANDLES AS
 SPECIFIED.
 PLEASE SEE PLANS SHALL ALSO BE SPECIFIC
 TO THE CODES IN REFERENCE.
 SEE 101, IS FROM THE 2003 CURRENTLY AS
 ADOPTED BY THE STATE OF FLORIDA.
  
 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONALS AND
 REPEAT COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-17 Cont ID  
Sent By dpalmer Date 2006-05-17 Time 19:35 Rev Time 0.00
Received By dpalmer Date 2006-05-17 Time 19:35 Sent To  
Notes
2006-05-17 00:00:00** UNSAT **
  
 1) NOTE: PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCKS PER FAC 61G15-23.002, FS
 471.023.
 PLEASE ALSO SEE PLANS APPEAR TO BE
 SIGNED WITH "INITIALS", IF INDEED THIS
 IS THE "LEGAL" SIGNATURE FOR SAID
 ENGINEER, PLEASE PROVIDE A SIGNED, DATED
 AND SEALED LETTER NOTING LEGAL
 SIGNATURE. PLEASE KNOW, THE LETTER MUST
 BE PROPERLY NOTORIZED PER FS117.05.
 THIS LTR WILL BE PLACED IN OUR SIGNATURE
 FILE FOR FUTURE REFERENCES.
  
 2)NOTE: PLEASE INDICATE NEW OR EXISTING
 LIGHTING FOR MEANS OF EGRESS TO THE
 PUBLIC RIGHT OF WAY.
 PLEASE SEE 2003 NFPA-101, 7.8.1.3 WHICH
 REQUIRES A MIN OF 10 FT CANDLES UNDER
 NORMAL CONDITIONS AND 1FT CANDLE UNDER
 EM CONDITIONS.
 PLEASE SEE 7.9.2.2 FOR SOME SORT OF
 BATTERY BACK UP FIXTURE REQUIRED FOR A
 MIN OF 90MIN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-09-12 Cont ID  
Sent By mwennerg Date 2006-09-12 Time 14:22 Rev Time 0.00
Received By mwennerg Date 2006-09-12 Time 14:22 Sent To  
Notes
2006-09-12 00:00:00***DENIED***
  
 PLEASE SEE SOME COMMENTS STILL NEED TO
 BE ADDRESSED FROM FIRST FIRE REVIEW:
  
 1) PLEASE INDICATE THE ADOPTED EDITION
 WHEN REFERENCING CODES. NFPA 101 AND
 NFPA 1, 2003 EDITIONS.
  
 2) NO RESPONSE: PLEASE SEE NFPA 101,
 SECTION 7.2.8.1.2.1. DOES THIS
 ARRANGEMENT CONSTITUTE MORE THAN 50
 PERCENT OF THE REQUIRED MEANS OF EGRESS?
  
 3) NO RESPONSE: PLEASE SEE NFPA 101,
 SECTION 7.2.8.2 REGARDING PROTECTION OF
 OPENINGS. PLEASE INDICATE IF THIS
 REQUIREMENT IS BEING MET?
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-05-18 Cont ID  
Sent By mwennerg Date 2006-05-18 Time 10:49 Rev Time 0.00
Received By mwennerg Date 2006-05-18 Time 10:49 Sent To  
Notes
2006-05-18 00:00:00***DENIED***
  
 1) IN ADDITION TO APPLICABLE BUILDING
 CODES, LIFE SAFETY SHALL COMPLY WITH
 NFPA 101, 2003 EDITION.
  
 2) PLEASE SEE NFPA 101, SECTION
 7.2.8.1.2.1. DOES THIS ARRANGEMENT
 CONSTITUTE MORE THAN 50 PERCENT OF THE
 REQUIRED MEANS OF EGRSS?
  
 3) PLEASE SEE NFPA 101, SECTION
 REGARDING PROTECTION OF OPENINGS. PLEASE
 INDICATE IF THIS REQUIREMENT IS BEING
 MET.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-28 Cont ID  
Sent By dpalmer Date 2006-07-28 Time 18:27 Rev Time 0.00
Received By dpalmer Date 2006-07-28 Time 18:27 Sent To  
Notes
2006-07-28 00:00:00TO COMM BOARD #11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-14 Cont ID  
Sent By adarroug Date 2006-07-14 Time 18:11 Rev Time 0.00
Received By adarroug Date 2006-07-14 Time 18:11 Sent To  
Notes
2006-07-14 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-13 Cont ID  
Sent By mmclean Date 2006-06-13 Time 12:25 Rev Time 0.00
Received By mmclean Date 2006-03-24 Time 17:20 Sent To  
Notes
2006-03-24 00:00:00WAITING FOR COMM BOARD. NEEDS B
 VERIFY WITH ZOING AS THESE ARE EXTERIOR
 ESCAPES.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-07-31 Cont ID  
Sent By mmclean Date 2006-07-31 Time 07:36 Rev Time 0.00
Received By mmclean Date 2006-07-31 Time 07:36 Sent To  
Notes
2006-07-31 00:00:00DENIED, 2ND REQUEST - SF14
 1. NEED TO PROVIDE THE ADDRESS OF THE
 PROPERTY ON THE TWO COPY OF SITEPLAN
 WITH SETBACKS OF THE EXISTING STRUCTURE.
 2. MUST PROVIDE A COPY OF EXISTING
 SURVEY SHOWING THE EXISTING (3) FIRE
 ESCAPES.
 3. MUST PROVIDE THE SETBACK OF THE
 PROPOSED FIRE ESCAPES (3) FROM PROPERTY
 LINE & EXISTING STRUCTURE.
  
 SEC 94-305(9) OUTSIDE STAIRWAYS OVER
 THREE FEET IN HEIGHT ABOVE GRADE SHALL
 MEET ALL SETBACK OF REQUIREMENTS OF THE
 MAIN STRUCTURE.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-06-13 Cont ID  
Sent By mmclean Date 2006-06-13 Time 12:16 Rev Time 0.00
Received By mmclean Date 2006-06-13 Time 12:16 Sent To  
Notes
2006-06-13 00:00:00DENIED,
 1. NEED TO PROVIDE THE ADDRESS OF THE
 PROPERTY ON THE TWO COPY OF SITEPLAN
 WITH SETBACKS OF THE EXISTING STRUCTURE.
 2. MUST PROVIDE A COPY OF EXISTING
 SURVEY SHOWING THE EXISTING (3) FIRE
 ESCAPES.
 3. MUST PROVID THE SETBACK OF THE
 PROPOSED FIRE ESCAPES (3) FROM PROPERTY
 LINE.
  
 SEC 94-305(9) OUTSIDE STAIRWAYS OVER
 THREE FEET IN HEIGHT ABOVE GRADE SHALL
 MEET ALL SETBACK OF REQUIREMENTS OF THE
 MAIN STRUCTURE.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720