| Plan Review Stops For Permit 06031107 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-08-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-08-07 |
Time |
10:40 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2006-08-07 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2006-08-07 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 06031107 | | | ADD: 345 30TH ST | | | CONT: WILLIAM J. HOLTEC | | | TEL: (954)731-2998 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | /2004 EXISTING BUILDINGS- LEVEL 1 | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | | | | 1)CHALAIRE & ASSOCIATES, INC. IS MISSING | | | THEIR:471.023 F.S.CERTIFICATE OF | | | AUTHORIZATION.THE TITLE BLOCK FOR ANY | | | SHEET BEARING THE NAME OF AN ENGINEER | | | PRACTICING UNDER A FICTITIOUS NAME, A | | | CORPORATION, OR A PARTNERSHIP, OFFERING | | | ENGINEERING SERVICES, SHALL INCLUDE THE | | | CERTIFICATE OF AUTHORIZATION NUMBER. | | | ADD THE NUMBER TO EACH SHEET.THIS MAY | | | BE ADDED BY HAND. | | | | | | 2) COMPLIED. | | | | | | 3) COMPLIED. | | | | | | 4) COMPLIED. | | | | | | 5) COMPLIED. | | | | | | 6)2ND REQUEST, 1009.11 HANDRAILS. | | | STAIRWAYS SHALL HAVE HANDRAILS ON EACH | | | SIDE. HANDRAILS SHALL BE ADEQUATE IN | | | STRENGTH AND ATTACHMENT IN ACCORDANCE | | | WITH SECTION 1607.7 . HANDRAILS FOR | | | RAMPS, WHERE REQUIRED BY SECTION 1010.8 | | | | | | 7) 2ND REQUEST,HANDRAIL | | | 1009.11.5 HANDRAIL EXTENSIONS. | | | HANDRAILS SHALL RETURN TO A WALL, GUARD | | | OR THE WALKING SURFACE OR SHALL BE | | | CONTINUOUS TO THE HANDRAIL OF AN | | | ADJACENT STAIR FLIGHT. WHERE HANDRAILS | | | ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE | | | HANDRAILS SHALL EXTEND HORIZONTALLY AT | | | LEAST 12 INCHES (305 MM) BEYOND THE TOP | | | RISER AND CONTINUE TO SLOPE FOR THE | | | DEPTH OF ONE TREAD BEYOND THE BOTTOM | | | RISER. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-05-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-05-08 |
Time |
15:11 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2006-05-08 |
Time |
15:11 |
Sent To |
|
|
| Notes |
| 2006-05-08 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 06031107 | | | ADD: 345 30TH ST | | | CONT: WILLIAM J. HOLTEC | | | TEL: (954)731-2998 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | /2004 EXISTING BUILDINGS- LEVEL 1 | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1)CHALAIRE & ASSOCIATES, INC. IS MISSING | | | THEIR:471.023 F.S.CERTIFICATE OF | | | AUTHORIZATION.THE TITLE BLOCK FOR ANY | | | SHEET BEARING THE NAME OF AN ENGINEER | | | PRACTICING UNDER A FICTITIOUS NAME, A | | | CORPORATION, OR A PARTNERSHIP, OFFERING | | | ENGINEERING SERVICES, SHALL INCLUDE THE | | | CERTIFICATE OF AUTHORIZATION NUMBER. | | | ADD THE NUMBER TO EACH SHEET.THIS MAY | | | BE ADDED BY HAND. | | | | | | 2) 110.2* W. P. B. ADMINISTRATIVE CODE, | | | INFORMATION THAT IS REQUIRED FOR RECORD | | | KEEPING & FOR CERTIFICATE OF OCCUPANCY: | | | A) THE EDITION OFTHE CODE UNDER WHICH | | | THE PERMIT WAS ISSUED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | | WITH THE PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | | IN CHAPTER 6, TABLE 601. | | | | | | 3) 2004 FL. BLD CODE 1603.1.4 THE | | | FOLLOWING INFORMATION RELATED TO WIND | | | SHALL BE SHOWN ON THE CONSTRUCTION | | | DRAWINGS, | | | 1)- BASIC WIND SPEED, MPH | | | 2)- WIND IMPORTANCE FACTOR, & BUILDING | | | CATEGORY | | | 3)- WIND EXPOSURE | | | 4)- INTERNAL PRESSURE COEFFICIENT, | | | 5)- COMPONENTS & CLADDING, THE DESIGN | | | WIND PRESSURES IN TERMS OF PSF. | | | | | | 4) TABLE 1607.1 PROVIDE LIVE LOADS FOR | | | FIRE ESCAPE. | | | | | | 5)1012.2 HEIGHT. | | | GUARDS SHALL FORM A PROTECTIVE BARRIER | | | NOT LESS THAN 42 INCHES (1067 MM) HIGH, | | | MEASURED VERTICALLY ABOVE THE LEADING | | | EDGE OF THE TREAD, ADJACENT WALKING | | | SURFACE OR ADJACENT SEATBOARD. 38" FOR | | | R-2 CAN ONLY BE USED FOR WITHIN R-2 | | | DWELLING UNIT WHEN THE TOP RAIL OF THE | | | GUARD ALSO SERVES AS A HANDRAIL. | | | | | | 6) 1009.11 HANDRAILS. | | | STAIRWAYS SHALL HAVE HANDRAILS ON EACH | | | SIDE. HANDRAILS SHALL BE ADEQUATE IN | | | STRENGTH AND ATTACHMENT IN ACCORDANCE | | | WITH SECTION 1607.7 . HANDRAILS FOR | | | RAMPS, WHERE REQUIRED BY SECTION 1010.8 | | | | | | 7)HANDRAIL | | | 1009.11.5 HANDRAIL EXTENSIONS. | | | HANDRAILS SHALL RETURN TO A WALL, GUARD | | | OR THE WALKING SURFACE OR SHALL BE | | | CONTINUOUS TO THE HANDRAIL OF AN | | | ADJACENT STAIR FLIGHT. WHERE HANDRAILS | | | ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE | | | HANDRAILS SHALL EXTEND HORIZONTALLY AT | | | LEAST 12 INCHES (305 MM) BEYOND THE TOP | | | RISER AND CONTINUE TO SLOPE FOR THE | | | DEPTH OF ONE TREAD BEYOND THE BOTTOM | | | RISER. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-08-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-05 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-05 |
Time |
10:01 |
Sent To |
|
|
| Notes |
| 2006-08-05 00:00:00 | *** USNAT 2ND REVIEW *** | | | | | | 1) NOTE: PLEASE SEE NOTE #2 FROM | | | PREVIOUS REVIEW WHICH REQUESTED TO | | | PLEASE PROVIDE NEW OR SHWOING NEW | | | EMERGENCY EGRESS AND NORMAL EGRESS | | | LIGHTING AS REQUIRED IN NFPA-101 | | | 7.8.1.3, 7.9.2.2 | | | PLEASE PROVIDE MIN FT CANDLES AS | | | SPECIFIED. | | | PLEASE SEE PLANS SHALL ALSO BE SPECIFIC | | | TO THE CODES IN REFERENCE. | | | SEE 101, IS FROM THE 2003 CURRENTLY AS | | | ADOPTED BY THE STATE OF FLORIDA. | | | | | | 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH | | | RESPECT TO DESIGN PROFESSIONALS AND | | | REPEAT COMMENTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-05-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-05-17 |
Time |
19:35 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-05-17 |
Time |
19:35 |
Sent To |
|
|
| Notes |
| 2006-05-17 00:00:00 | ** UNSAT ** | | | | | | 1) NOTE: PLEASE SEE MISSING INFORMATION | | | ON TITLE BLOCKS PER FAC 61G15-23.002, FS | | | 471.023. | | | PLEASE ALSO SEE PLANS APPEAR TO BE | | | SIGNED WITH "INITIALS", IF INDEED THIS | | | IS THE "LEGAL" SIGNATURE FOR SAID | | | ENGINEER, PLEASE PROVIDE A SIGNED, DATED | | | AND SEALED LETTER NOTING LEGAL | | | SIGNATURE. PLEASE KNOW, THE LETTER MUST | | | BE PROPERLY NOTORIZED PER FS117.05. | | | THIS LTR WILL BE PLACED IN OUR SIGNATURE | | | FILE FOR FUTURE REFERENCES. | | | | | | 2)NOTE: PLEASE INDICATE NEW OR EXISTING | | | LIGHTING FOR MEANS OF EGRESS TO THE | | | PUBLIC RIGHT OF WAY. | | | PLEASE SEE 2003 NFPA-101, 7.8.1.3 WHICH | | | REQUIRES A MIN OF 10 FT CANDLES UNDER | | | NORMAL CONDITIONS AND 1FT CANDLE UNDER | | | EM CONDITIONS. | | | PLEASE SEE 7.9.2.2 FOR SOME SORT OF | | | BATTERY BACK UP FIXTURE REQUIRED FOR A | | | MIN OF 90MIN. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2006-09-12 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-09-12 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-09-12 |
Time |
14:22 |
Sent To |
|
|
| Notes |
| 2006-09-12 00:00:00 | ***DENIED*** | | | | | | PLEASE SEE SOME COMMENTS STILL NEED TO | | | BE ADDRESSED FROM FIRST FIRE REVIEW: | | | | | | 1) PLEASE INDICATE THE ADOPTED EDITION | | | WHEN REFERENCING CODES. NFPA 101 AND | | | NFPA 1, 2003 EDITIONS. | | | | | | 2) NO RESPONSE: PLEASE SEE NFPA 101, | | | SECTION 7.2.8.1.2.1. DOES THIS | | | ARRANGEMENT CONSTITUTE MORE THAN 50 | | | PERCENT OF THE REQUIRED MEANS OF EGRESS? | | | | | | 3) NO RESPONSE: PLEASE SEE NFPA 101, | | | SECTION 7.2.8.2 REGARDING PROTECTION OF | | | OPENINGS. PLEASE INDICATE IF THIS | | | REQUIREMENT IS BEING MET? | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-05-18 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-05-18 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-05-18 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2006-05-18 00:00:00 | ***DENIED*** | | | | | | 1) IN ADDITION TO APPLICABLE BUILDING | | | CODES, LIFE SAFETY SHALL COMPLY WITH | | | NFPA 101, 2003 EDITION. | | | | | | 2) PLEASE SEE NFPA 101, SECTION | | | 7.2.8.1.2.1. DOES THIS ARRANGEMENT | | | CONSTITUTE MORE THAN 50 PERCENT OF THE | | | REQUIRED MEANS OF EGRSS? | | | | | | 3) PLEASE SEE NFPA 101, SECTION | | | REGARDING PROTECTION OF OPENINGS. PLEASE | | | INDICATE IF THIS REQUIREMENT IS BEING | | | MET. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-07-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-28 |
Time |
18:27 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-28 |
Time |
18:27 |
Sent To |
|
|
| Notes |
| 2006-07-28 00:00:00 | TO COMM BOARD #11 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-07-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-14 |
Time |
18:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-14 |
Time |
18:11 |
Sent To |
|
|
| Notes |
| 2006-07-14 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-06-13 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-06-13 |
Time |
12:25 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-03-24 |
Time |
17:20 |
Sent To |
|
|
| Notes |
| 2006-03-24 00:00:00 | WAITING FOR COMM BOARD. NEEDS B | | | VERIFY WITH ZOING AS THESE ARE EXTERIOR | | | ESCAPES. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2006-07-31 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-07-31 |
Time |
07:36 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-07-31 |
Time |
07:36 |
Sent To |
|
|
| Notes |
| 2006-07-31 00:00:00 | DENIED, 2ND REQUEST - SF14 | | | 1. NEED TO PROVIDE THE ADDRESS OF THE | | | PROPERTY ON THE TWO COPY OF SITEPLAN | | | WITH SETBACKS OF THE EXISTING STRUCTURE. | | | 2. MUST PROVIDE A COPY OF EXISTING | | | SURVEY SHOWING THE EXISTING (3) FIRE | | | ESCAPES. | | | 3. MUST PROVIDE THE SETBACK OF THE | | | PROPOSED FIRE ESCAPES (3) FROM PROPERTY | | | LINE & EXISTING STRUCTURE. | | | | | | SEC 94-305(9) OUTSIDE STAIRWAYS OVER | | | THREE FEET IN HEIGHT ABOVE GRADE SHALL | | | MEET ALL SETBACK OF REQUIREMENTS OF THE | | | MAIN STRUCTURE. | | | | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-06-13 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-06-13 |
Time |
12:16 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-06-13 |
Time |
12:16 |
Sent To |
|
|
| Notes |
| 2006-06-13 00:00:00 | DENIED, | | | 1. NEED TO PROVIDE THE ADDRESS OF THE | | | PROPERTY ON THE TWO COPY OF SITEPLAN | | | WITH SETBACKS OF THE EXISTING STRUCTURE. | | | 2. MUST PROVIDE A COPY OF EXISTING | | | SURVEY SHOWING THE EXISTING (3) FIRE | | | ESCAPES. | | | 3. MUST PROVID THE SETBACK OF THE | | | PROPOSED FIRE ESCAPES (3) FROM PROPERTY | | | LINE. | | | | | | SEC 94-305(9) OUTSIDE STAIRWAYS OVER | | | THREE FEET IN HEIGHT ABOVE GRADE SHALL | | | MEET ALL SETBACK OF REQUIREMENTS OF THE | | | MAIN STRUCTURE. | | | | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|