Plan Review Details - Permit 06031104
Plan Review Stops For Permit 06031104
Review Stop G GAS REVIEW
Rev No 4 Status P Date 2006-07-03 Cont ID  
Sent By mperson Date 2006-07-03 Time 08:59 Rev Time 0.45
Received By mperson Date 2006-07-03 Time 08:59 Sent To PC
Notes
2006-07-03 00:00:00REVISION #2: ADD NATURAL GAS TO POOL
 HEATER
  
 ******PROVISO******
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,000 CUBIC FEET REQUIRED.
  
 PER FBC-2004 FUEL GAS, SEC. 623.1, AND
 PER FBC-2004 MECHANICAL, SEC.917.1,
 COOKING APPLIANCES: COOKING APPLIANCES
 THAT ARE DESIGNED FOR PERMANENT
 INSTALLATION, INCLUDINGBARBEQUES,
 SHALL BE LISTED, LABELED AND INSTALLED
 IN ACCORDANCE WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS.
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2006-05-31 Cont ID  
Sent By mperson Date 2006-05-31 Time 14:09 Rev Time 0.45
Received By mperson Date 2006-05-31 Time 14:09 Sent To PC
Notes
2006-05-31 00:00:00REVISION: ADD BARBEQUE TO SYSTEM
  
 ******PROVISO******
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,000 CUBIC FEET REQUIRED.
  
 PER 623.1 FBC-2004 FUEL GAS, AND PER
 917.1 FBC-2004 MECHANICAL COOKING
 APPLIANCES: COOKING APPLIANCES THAT ARE
 DESIGNED FOR PERMANENT INSTALLATION,
 INCLUDING BARBEQUES SHALL BE INSTALLED
 IN ACCORDANCE WITH MANUFACTURER'S
 INSTALLATION INSTRUCTIONS.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-04-17 Cont ID  
Sent By mperson Date 2006-04-17 Time 15:51 Rev Time 0.33
Received By mperson Date 2006-04-17 Time 15:51 Sent To PC
Notes
2006-04-17 00:00:00 
  
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,000 CUBIC FEET REQUIRED.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-03-27 Cont ID  
Sent By adarroug Date 2006-04-13 Time 11:41 Rev Time 1.00
Received By mperson Date 2006-03-27 Time 11:45 Sent To PC
Notes
2006-03-27 00:00:00****DENIED****
 REFERENCE FBC-2004 FUEL GAS AND CITY OF
 WEST PALM BEACH, AMENDMENTS TO FBC-2004
 CHAPTER 1 ADMINISTRATION:
  
 1. NOTE: PER SEC. 106 CONSTRUCTION
 DOCUMENTS, CITY OF WEST PALM BEACH,
 AMENDMENTS TO FBC-2004, CHAPTER 1,
 ADMINISTRATION. IF IT IS YOUR INTENT TO
 USE THE BRENNER ARCHITECTURE GROUP INC,
 TITLE BLOCK, THE DRAWING NEEDS TO BE
 SIGNED AND SEALED BY SAID DESIGN
 PROFESSIONAL. IF THIS IS NOT YOUR IN-
 TENT THEN REMOVE SAID TITLE BLOCK AND
 GAS SYSTEM DESIGNER SHALL SIGN DRAWINGS.
 2. ISOMETRIC DRAWING DOES NOT REFLECT
 THE FLOOR PLAN.
 3. CSST SIZED WRONG WITH WRONG TABLE,
 NEEDS TO BE SIZED BY FBC-2004 TABLE
 402.4(14). PLEASE CORRECT AND SEE
 ENCLOSED LETTERS AND SIZING TABLES FOR
 YOUR REFERENCE FOR RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-22 Cont ID  
Sent By adarroug Date 2006-06-22 Time 16:09 Rev Time 0.00
Received By adarroug Date 2006-06-22 Time 16:09 Sent To G
Notes
2006-06-22 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-13 Cont ID  
Sent By adarroug Date 2006-04-13 Time 11:41 Rev Time 0.00
Received By adarroug Date 2006-04-13 Time 11:41 Sent To P
Notes
2006-04-13 00:00:00TO "P" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-13 Cont ID  
Sent By adarroug Date 2006-03-27 Time 11:41 Rev Time 0.00
Received By adarroug Date 2006-03-24 Time 17:22 Sent To G
Notes
***NONE***