Plan Review Details - Permit 06031101
Plan Review Stops For Permit 06031101
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-11-15 Cont ID  
Sent By alange Date 2006-11-15 Time 15:38 Rev Time 0.00
Received By alange Date 2006-11-15 Time 15:38 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-10-03 Cont ID  
Sent By amorse Date 2006-10-03 Time 09:58 Rev Time 0.00
Received By amorse Date 2006-10-03 Time 09:58 Sent To PC
Notes
2006-10-03 00:00:00 
  
 DENIED
  
 1) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 *****PLEASE SUBMIT UPDATED COVER LETTER
 LISTING ALL REVIEWED AND APPROVED
 PRODUCT APPROVALS*****
  
 2) SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 *****ENERGY CALC'S DO NOT MATCH DRAWINGS
 PLEASE SEE THAT DRAWING SPECIFIES R-30
 INSULATION IN THE CEILING AND THE ENERGY
 CALC'S SHOW R-19*****
  
 3) PRODUCT APPROVAL FOR CLOPAY SECTIONAL
 DOOR HAS A MAXIMUM WIDTH OF 9'-0" WHILE
 THE DRAWING SPECIFIES A 7X16 GARAGE DOOR
  
 4) PER 713.13(2) F.S.
 IF THE IMPROVEMENT DESCRIBED IN THE NOC
 HAS NOT COMMENCED WITHIN 90 DAYS OF
 RECORDING THE NOTICE IS VOID
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-24 Cont ID  
Sent By amorse Date 2006-04-24 Time 09:24 Rev Time 0.00
Received By amorse Date 2006-04-24 Time 09:24 Sent To PC
Notes
2006-04-24 00:00:00 
  
 DENIED
  
 1) INDICATE 2004 FBC AND CORRECT WIND
 LOAD TABLES 1609.6 A-E
  
 2) FOOTING TYPE NOTES ON S/1 SEND TO
 WRONG DETAILS PLEASE VERIFY
  
 3) NO PRECAST LINTELS SHOWN ON S/1 BUT
 PRODUCT APPROVALS WERE SUBMITTED. BEAM
 HEIGHT 8'-1", WINDOW AND DOOR HEIGHT
 6'-8" LEAVES ONLY 5". IS TIE BEAM POURED
 DOWN OVER DOORS AND WINDOWS, PLEASE
 VERIFY, IF SO REMOVE LINTEL PRODUCT
 APPROVALS
  
 4) BEAM SPANS ON S/2 REQUIRE ENGINEERED
 INTERPOLATION TO CLARIFY THAT SPANS OF
 TRIPLE 2X12 WILL CARRY THE LOADS FOR
 SPANS OVER 12'-2" AS SHOWN IN CHAPTER 23
 TABLE 2308.9.5 FBC
  
 5) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION
  
 6) SUBMIT ENERGY CALC'S FOR NEW ADDITION
 PER 106.3.5.4 (10) FBC*
  
 7) ADDITION WILL REQUIRE MECHANICAL
 DRAWINGS TO BE SUBMITTED
  
 8) SURVEY IS REQUIRED TO SHOW ALL
 CHANGES TO THE FOOTPRINT OF THE BUILDING
 UPDATE SURVEY TO INCLUDE THE LANAI WHICH
 IS COVERED BY THE MAIN ROOF STRUCTURE
  
 9) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC* (APPLICATION HAS BEEN
 ADJUSTED)
  
 10) THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE PER 10D-91 FAC (APPLICATION
 HAS BEEN ADJUSTED)
  
 11) PROVIDE WINDOW SIZES ON REPLACEMENT
 WINDOWS
  
 12) PRODUCT APPROVALS WERE NOT SUBMITTED
 FOR ROOF COVERING, GARAGE DOOR, FIXED
 WINDOW, FRECH DOORS, SINGLE DOOR INTO
 GARAGE OR STORM SHUTTERS
  
 13) MARK THE MULL SIZE THAT WILL BE USED
 (PAGE 4 OF NOA) AS THERE ARE DIFFERENT
 PRESSURES FOR EACH TYPE
  
 14) THE THERMA-TRU STATE COVER SHEET
 DOES NOT COVER "BENCHMARK SERIES" UNDER
 FL# 5262. THE MIAMI-DADE NOA MAY BE
 SUBMITTED FOR LOCAL PRODUCT APPROVAL IF
 NO STATE COVER IS AVAILABLE, BUT YOU
 MUST PROVIDE LOCATION OF THIS PRODUCT.
 THE NOA IS FOR DOUBLE DOORS IS THIS FOR
 FRONT ENTRY OF LANAI ?
  
 15) THOSE PRODUCTS WHICH ARE REGULATED
 BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 16) STRUCTURAL REQUIREMENTS SHALL
 INCLUDE A WALL SECTION FROM FOUNDATION
 THROUGH ROOF, INCLUDING ASSEMBLY AND
 MATERIALS, CONNECTOR TABLES, WIND
 REQUIREMENTS, AND STRUCTURAL
 CALCULATIONS PER 106.3.5.4 (6) FBC*
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004
 FBC* = WEST PALM BEACH
 ADMINISTATIVE AMMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-05-17 Cont ID  
Sent By btrobaug Date 2007-05-17 Time 08:23 Rev Time 0.50
Received By btrobaug Date 2007-05-17 Time 07:58 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-11-07 Cont ID  
Sent By jleahy Date 2006-11-07 Time 06:45 Rev Time 0.30
Received By btrobaug Date 2006-11-07 Time 06:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-21 Cont ID  
Sent By jleahy Date 2006-09-21 Time 15:06 Rev Time 0.45
Received By jleahy Date 2006-09-20 Time 15:08 Sent To P
Notes
2006-09-20 00:00:00PANEL SCHEDULE SHOWS ALL 2 POLE CIRCUIT
 BREAKERS
  
 ALL 120V CIRCUITS ARE SHOWN AS 20A AND 2
 POLE EXCEPT GFI
  
 OUTLET SPACING IN LIVING ROOM AND FAMILY
 ROOMS DOES NOT SHOW ENOUGH OUTLETS TO
 MEET SPACING REQUIREMENTS.210.52A1
  
 LIGHT FIXTURE HAS TO BE INSTALLED AT THE
 J BOX AT THE FRONT DOOR.
  
 SLIDING DOOR IN FAMILY ROOM MAY NEED
 OUTLETS INSTALLED PLEASE SEE 210.52

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-10 Cont ID  
Sent By jleahy Date 2006-04-10 Time 09:07 Rev Time 0.45
Received By jleahy Date 2006-04-10 Time 09:07 Sent To P
Notes
2006-04-10 00:00:00LOAD CALCULATION ONLY SHOWS NEW LOADS NO
 EXISTING LOADS SHOWN.
  
 NEED PANEL SCHEDULE.
  
 GFCI IN KITCHEN AND OUTLET SPACING NOT
 TO CODE IN KITCHEN.
  
 ARC FAULTS IN BEDROOMS.
  
 PLANS NOT SIGNED.
  
 SMOKE DETECTORS NOT SHOWN.
  
 CALL PHILLIP PETTY805-6742

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-10-30 Cont ID  
Sent By adarroug Date 2007-10-30 Time 09:37 Rev Time 0.00
Received By adarroug Date 2007-10-30 Time 09:37 Sent To E
Notes
2007-10-30 09:38:28TO "JLEAHY" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-05-08 Cont ID  
Sent By adarroug Date 2007-05-08 Time 08:21 Rev Time 0.00
Received By adarroug Date 2007-05-08 Time 08:21 Sent To E
Notes
2007-05-08 08:27:46TO "JLEAHY" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-11-03 Cont ID  
Sent By adarroug Date 2006-11-03 Time 09:52 Rev Time 0.00
Received By adarroug Date 2006-11-03 Time 09:52 Sent To E
Notes
2006-11-03 09:52:56TO "JLEAHY" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-18 Cont ID  
Sent By adarroug Date 2006-09-18 Time 09:43 Rev Time 0.00
Received By adarroug Date 2006-09-18 Time 09:43 Sent To E
Notes
2006-09-18 00:00:00TO "JLEAHY" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-09 Cont ID  
Sent By adarroug Date 2006-09-09 Time 17:23 Rev Time 0.00
Received By adarroug Date 2006-09-09 Time 17:23 Sent To Z
Notes
2006-09-09 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-05 Cont ID  
Sent By adarroug Date 2006-04-05 Time 10:26 Rev Time 0.00
Received By adarroug Date 2006-04-05 Time 10:26 Sent To E
Notes
2006-04-05 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-04-24 Time   Rev Time 0.00
Received By adarroug Date 2006-03-28 Time 14:45 Sent To  
Notes
2006-03-28 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-11-16 Cont ID  
Sent By btrobaug Date 2007-11-08 Time 13:26 Rev Time 0.00
Received By jleech Date 2006-11-16 Time 08:30 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-10-02 Cont ID  
Sent By jleech Date 2006-10-02 Time 14:48 Rev Time 0.00
Received By jleech Date 2006-10-02 Time 14:48 Sent To B1
Notes
2006-10-02 00:00:00DENIED;
 1.RISER DIAGRAM NOT TO CODE. USE BRANCH
 DRAINS FOR BATHROOM GROUPS AND DISCHARGE
 INTO THE BUILDING DRAIN. ONE SET OF
 PLANS MARKED IN RED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-04-10 Cont ID  
Sent By jleech Date 2006-04-10 Time 15:07 Rev Time 0.00
Received By jleech Date 2006-04-10 Time 15:07 Sent To B
Notes
2006-04-10 00:00:00DENIED;
 1. THE PRINTED NAME AND SIGNITURE OF THE
 PERSON WHO DREW THE PLANS IS REQUIRED TO
 BE ON THE PLANS.
 2.SANITARY RISER DIAGRAM DOES NOT MEET
 CODE.
 3.WATER HAMMER ARRESTORS ARE TO BE USED
 NOT AIR CHAMBERS TO COMPLY WITH, SEC.
 604.9
 4.PLEASE LABLE PLUMBING FIXTURES
 PROPERLY, BAR SINK, LAVATORY, SHOWER,
 ETC.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2006-09-14 Cont ID  
Sent By mmclean Date 2006-09-14 Time 15:53 Rev Time 0.00
Received By mmclean Date 2006-09-14 Time 15:53 Sent To I
Notes
2006-09-14 00:00:00NOTE: THE WETBAR REG. MUST BE AN U/C
 REF.
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2006-04-04 Cont ID  
Sent By mmclean Date 2006-04-04 Time 14:37 Rev Time 0.00
Received By mmclean Date 2006-04-04 Time 14:37 Sent To I
Notes
2006-04-04 00:00:00NOTE: THE WETBAR REG. MUST BE AN U/C
 REF.
  