| 2006-03-24 00:00:00 | DENIED |
| | |
| | 1) THE PRODUCT APPROVAL SUBMITTED FOR |
| | THE FLAT ROOF IS FOR STEEL DECKS. THE |
| | BUILDING PLANS ON FILE INDICATE A |
| | CONCRETE DECK. |
| | |
| | 2) SUBMIT RAS 117 CALCULATIONS FOR THE |
| | FLAT ROOF SYSTEM ENHANCED FASTENING. |
| | |
| | 3) SPECIFY THE METHOD OF ATTACHMENT THAT |
| | WILL BE USED TO SECURE THE CLAY TILE. |
| | CIRCLE THE APPROPRIATE FASTENER TYPE ON |
| | THE NOA. NOTE: THE ATTACHMENT RESISTANCE |
| | MUST MEET OR EXCEED THE UPLIFT MOMENT |
| | REQUIRED FOR THE STRUCTURE. |
| | |
| | 4) PRODUCTS FOR FLAT ROOF AND CLAY ROOF |
| | TILES ARE NOT THE SAME AS THE ONES WITH |
| | THE APPROVED PLANS. A REVISION WILL BE |
| | REQUIRED. |
| | |
| | 5) THE MASTER PERMIT LISTS IMPACT |
| | ROOFING AS THE ROOFING SUBCONTRACTOR. IN |
| | ORDER TO GET A PERMIT FOR THE NEW |
| | CONTRACTOR, TWO OPTIONS ARE AVAILABLE. A |
| | NOTARIZED LETTER FROM THE EXISTING |
| | ROOFING CONTRACTOR TRANSFERING THE |
| | EXISTING PERMIT TO THE NEW CONTRACTOR |
| | WITH A FEE FOR CHANGE OF CONTRACTOR IS |
| | ONE OPTION. THE OTHER IS TO SUBMIT A |
| | NOTARIZED LETTER FROM THE BUILDING |
| | CONTRACTOR STATING THAT THE PREVIOUS |
| | ROOFING SUBCONTRACTOR HAS BEEN |
| | TERMINATED AND THE EXISTING ROOFING |
| | PERMIT WILL BE VOIDED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |