| Plan Review Stops For Permit 06030904 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2006-03-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-03-21 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-03-21 |
Time |
11:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-03-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-03-20 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-03-20 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2006-03-20 00:00:00 | DENIED | | | | | | 1) THE CURRENT FLORIDA PRODUCT APPROVAL | | | AS LISTED ON WWW.FLORIDABUILDING.ORG IS | | | FL# 741-R1. SUBMIT UPDATED COVER PAGE. | | | | | | 2) THE EVALUATION DOCUMENT LISTED ON THE | | | SITE IS MIAMI-DADE NOA 01-0830.07. | | | LIMITATION #7 ON THIS NOA DOES NOT | | | REQUIRE THE RAS 117 CALCULATIONS FOR | | | ENHANCED FASTENING TO BE DONE BY AN | | | ENGINEER. | | | | | | 3) UNDER LIMITATIONS ON PAGE 20 OF NOA | | | 02-0212.07, NUMBER 7 REQUIRES RAS 117 | | | CALCULATIONS TO BE PREPARED BY AN | | | ENGINEER, ARCHITECT OR REGISTERED ROOF | | | CONSULTANT. PAGE 20 WAS MISSING FROM | | | YOUR SUBMITTAL. I HAVE PROVIDED YOU WITH | | | ONE COPY OF IT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
|