| 2006-05-08 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 06030895 |
| | ADD: 5011 BROADWAY AV |
| | CONT: A&M BUILDERS |
| | TEL: (561)305-1605 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | SHEET A-1: |
| | |
| | 1) WRONG ADDITION OF THE CODE. |
| | 110.2* W. P. B. ADMINISTRATIVE CODE, |
| | INFORMATION THAT IS REQUIRED FOR RECORD |
| | KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| | A) THE EDITION OF THE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | G) SQ. FT. FOOTPRINT |
| | H) SQ. FT. UNDER ROOF (TOTAL) |
| | I) OCCUPANT LOAD |
| | J) FLOOD ZONE |
| | K) THERE IS NO TABLE 600 UNDER 2004 |
| | CODE. |
| | |
| | 2) 109.3.10* IMPACT OF CONSTRUCTION. ALL |
| | CONSTRUCTION ACTIVITY REGULATED BY THIS |
| | CODE SHALL BE PERMORMED IN A MANNER SO |
| | AS NOT TO ADVERSLY IMPACT THE CONDITION |
| | OF ADJACENT PROPERTY, UNLESS SUCH |
| | ACTIVITY IS PERMITTED TO AFFECT SAID |
| | PROPERTY PURSUANT TO A CONSENT BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS & |
| | CONDITIONS AGREEABLE TO THE APPLICABLE |
| | PROPERTY OWNER.THIS INCLUDES BUT IS NOT |
| | LIMITED TO THE CONTROL OF DUST, NOISE, |
| | WATER OR DRAINAGE RUN-OFF, DEBRIS, AND |
| | THE STORAGE OF CONSTRUCTION MATERIALS. |
| | NEW CONSTRUCTION ACTIVITY SHALL NOT |
| | ADVERSELY IMPACT HISTORICSURFACE WATER |
| | DRAINAGE FLOWS SERVING ADJACENT |
| | PROPERTIES, & MAY REQUIRE SPECIAL |
| | DRAINAGE DESIGNCOMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED |
| | SITES.ACCORDINGLY, DEVELOPERS, |
| | CONTRACTORS, AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENET, INCLUDING |
| | ADDITIONS, POOLS, PATIOS, DRIVEWAYS, |
| | DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN |
| | EXCESS OF 800SQ FT OF PERMEABLE LAND |
| | AREA ON ANY PARCELL SHALL AS A PERMIT |
| | CONDITION, PROVIDE A PROFESSIONALY |
| | PREPARED DRAINAGE PLAN CLEARLY |
| | INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE |
| | IMPROVEMENT, A CERTIFICATE FROM A |
| | LICENSED ENGINEER SHALL BE SUBMITTED TO |
| | THE INSPECTOR IN ORDER TO RECEIVE |
| | APPROVAL OF THE FINAL INSPECTION. |
| | |
| | 3) 109.3.10.1 HURICANE PROTECTION. |
| | IT SHALL BE UNLAWFUL FOR ANY PERSON TO |
| | ALLOW CONSTRUCTION RELATED MATERIALS |
| | EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION |
| | SITE FROM 24 HRS. AFTER A HURRICANE |
| | WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN |
| | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, |
| | EQUIPMENT AND DEBRIS SHALL BE EITHER |
| | REMOVED FROM THE CONSTRUCTION SITE OR |
| | SECURED IN SUCH A MANNER AS TO MINIMIZE |
| | THE DANGER OF SUCH CONSTRUCTION |
| | MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM |
| | HIGHWINDS. |
| | ANY PERSONS WHO FAILS TO COMPLY TO |
| | REMOVE OR SECURE THE CONSTRUCTION |
| | MATERIALS EQUIPMENT AND DEBRIS WITHIN |
| | 24 HRS AFTER A HURRICANE WATCH HAS BEEN |
| | ISSUED SHALL BE SUBJECT TO A FINE NOT TO |
| | EXCEED $500.00. |
| | IN ADDITION TO THE ABOVE, A LICENSED |
| | CONTRACTOR WHO VIOLATES THIS SECTION |
| | SHALL BE SUBJECT TO DISCIPLINE PURSUANT |
| | TO SECTION 113 OF THIS CHAPTER. |
| | |
| | 4) WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 5) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 6)FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) AUTOMATIC SLIDING DOORS |
| | B) SHUTTERS |
| | C) PREFABRICATED A/C STANDS |
| | |
| | 7A) MISSING INFO FOR ROOFING REPORT : |
| | THIS ROOF IS MISSING OR NOT IN |
| | COMPLIANCE WITH THE FOLLOW ITEMS: |
| | (FLAT ROOF) |
| | _X__ CONTRACTOR DID NOT PROVIDE THE MEAN |
| | |
| | ROOF HEIGHT. |
| | |
| | ___ CONTRACTOR DID NOT INDICATE THE ROOF |
| | PITCH. |
| | |
| | _X__ CONTRACTOR FAILED TO INDICATE WHICH |
| | SYSTEM TO BE USED. |
| | |
| | ___ THE SYSTEM PROVIDED HAS A LOW |
| | PRESSURE FOR ZONE ___ . |
| | |
| | _X__ THE SYSTEM PROVIDED STATES |
| | LIMITATION# 7, SHOULD THE FASTENER |
| | RESISTANCE BE LESS THAN THAT |
| | REQUIRED, AS DETERMINED BY THE |
| | BUILDING OFFICIAL, A REVISED |
| | FASTENER SPACING, PREPARED , SIGNED |
| | |
| | AND SEALED BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER, REGISTERED |
| | ARCHITECT OR REGISTERED ROOF |
| | CONSULTANT MAY BE SUBMITTED. |
| | |
| | ___THE SYSTEM PROVIDED INDICATES |
| | LIMITATION# 9, NO ENHANCED |
| | FASTENING ALLOWED. |
| | |
| | 7B) ROOF TILE, CONTRACTOR DIDN'T CIRCLE |
| | WHICH TYPE OF FASTENING SYSTEM THAT WILL |
| | BE USED. |
| | |
| | 7C) NO INFORMATION FOR FASTENING OF HIP |
| | BOARD OR HIP TILE.1507.3.8 APPLICATION. |
| | TILE SHALL BE APPLIED ACCORDING TO THE |
| | MANUFACTURER?S INSTALLATION INSTRUCTIONS |
| | OR RECOMMENDATIONS OF THE FRSA/RTI |
| | 07320/08-05 (FOURTH EDITION). |
| | |
| | 8) FLOOR PLAN A-4 INDICATES USE OF POWER |
| | HORIZONTAL SLIDING DOORS. SHOW |
| | COMPLIANCE WITH: |
| | 1008.1.3.3 HORIZONTAL SLIDING DOORS. |
| | IN OTHER THAN GROUP H OCCUPANCIES, |
| | HORIZONTAL SLIDING DOORS PERMITTED TO BE |
| | A COMPONENT OF A MEANS OF EGRESS IN |
| | ACCORDANCE WITH EXCEPTION 5 TO SECTION |
| | 1008.1.2 SHALL COMPLY WITH ALL OF THE |
| | FOLLOWING CRITERIA: |
| | 1.THE DOORS SHALL BE POWER OPERATED |
| | AND SHALL BE CAPABLE OF BEING OPERATED |
| | MANUALLY IN THE EVENT OF POWER FAILURE. |
| | 2.THE DOORS SHALL BE OPENABLE BY A |
| | SIMPLE METHOD FROM BOTH SIDES WITHOUT |
| | SPECIAL KNOWLEDGE OR EFFORT. |
| | 3.THE FORCE REQUIRED TO OPERA TE |
| | THE DOOR SHALL NOT EXCEED 30 POUNDS (133 |
| | N) TO SET THE DOOR IN MOTION AND 15 |
| | POUNDS (67 N) TO CLOSE THE DOOR OR OPEN |
| | IT TO THE MINIMUM REQUIRED WIDTH. |
| | 4.THE DOOR SHALL BE OPENABLE WITH A |
| | FORCE NOT TO EXCEED 15 POUNDS (67 N) |
| | WHEN A FORCE OF 250 POUNDS (1100 N) IS |
| | APPLIED PERPENDICULAR TO THE DOOR |
| | ADJACENT TO THE OPERATING DEVICE. |
| | 5.THE DOOR ASSEMBLY SHALL COMPLY |
| | WITH THE APPLICABLE FIRE PROTECTION |
| | RATING AND, WHERE RATED, SHALL BE |
| | SELF-CLOSING OR AUTOMATIC-CLOSING BY |
| | SMOKE DETECTION, SHALL BE INSTALLED IN |
| | ACCORDANCE WITH NFPA 80 AND SHALL COMPLY |
| | WITH SECTION 715 . |
| | 6.THE DOOR ASSEMBLY SHALL HAVE AN |
| | INTEGRATED STANDBY POWER SUPPLY. |
| | 7.THE DOOR ASSEMBLY POWER SUPPLY |
| | SHALL BE ELECTRICALLY SUPERVISED. |
| | |
| | 9) PLANS INDICATE THIS PROJECT IS TO BE |
| | PHASED, WILL THE WORK TO BE INCLUDED IN |
| | BOTH PHASES UNDER THIS PERMIT? |
| | IF SO CONTACT KEN CONRAD FOR |
| | REQUIREMENTS FOR PHASED WORK.805 6666. |
| | |
| | 10A) SHEET A-6 INDICATES ON THE NORTH |
| | ELEVATION A MEZZANINE LEVEL FOR |
| | EQUIPMENT. THERE IS NO MENTION OF THIS |
| | IN THE NEW PLAN? |
| | |
| | 10B) THE SAME NORTH ELEVATION INDICATES |
| | VENTS FOR THE EQUIPMENT ROOM, THERE IS |
| | NO DETAILS SHOWING VENTS FOR MEZZANINE |
| | LEVEL ON THE NEW ELEVATIONS. |
| | |
| | 10C) 505.1 A MEZZANINE OR MEZZANINES IN |
| | COMPLIANCE WITH THIS SECTION SHALL BE |
| | CONSIDERED A PORTION OF THE FLOOR BELOW. |
| | SUCH MEZZANINES SHALL NOT CONTRIBUTE TO |
| | EITHER THE BUILDING AREA OR NUMBER OF |
| | STORIES AS REGULATED BY SECTION 503.1 . |
| | THE AREA OF THE MEZZANINE SHALL BE |
| | INCLUDED IN DETERMINING THE FIRE AREA |
| | DEFINED IN SECTION 702 . THE CLEAR |
| | HEIGHT ABOVE AND BELOW THE MEZZANINE |
| | FLOOR CONSTRUCTION SHALL NOT BE LESS |
| | THAN 7 FEET (2134 MM). |
| | |
| | 10D) SHOW EGRESS REQUIREMENTS FOR THE |
| | MEZZANINE LEVEL. |
| | 505.2 AREA LIMITATION. |
| | THE AGGREGATE AREA OF A MEZZANINE OR |
| | MEZZANINES WITHIN A ROOM SHALL NOT |
| | EXCEED ONE-THIRD OF THE AREA OF THAT |
| | ROOM OR SPACE IN WHICH THEY ARE LOCATED. |
| | THE ENCLOSED PORTIONS OF ROOMS SHALL NOT |
| | BE INCLUDED IN A DETERMINATION OF THE |
| | SIZE OF THE ROOM IN WHICH THE MEZZANINE |
| | IS LOCATED. IN DETERMINING THE ALLOWABLE |
| | MEZZANINE AREA, THE AREA OF THE |
| | MEZZANINE SHALL NOT BE INCLUDED IN THE |
| | AREA OF THE ROOM. |
| | |
| | 11) 505.5 INDUSTRIAL EQUIPMENT |
| | PLATFORMS. INDUSTRIAL EQUIPMENT |
| | PLATFORMS IN BUILDINGS SHALL NOT BE |
| | CONSIDERED AS A PORTION OF THE FLOOR |
| | BELOW. SUCH EQUIPMENT PLATFORMS SHALL |
| | NOT CONTRIBUTE TO EITHER THE BUILDING |
| | AREA OR THE NUMBER OF STORIES AS |
| | REGULATED BY SECTION 503.1 . THE AREA OF |
| | THE INDUSTRIAL EQUIPMENT PLATFORM SHALL |
| | NOT BE INCLUDED IN DETERMINING THE FIRE |
| | AREA. INDUSTRIAL EQUIPMENT PLATFORMS |
| | SHALL NOT BE A PART OF ANY MEZZANINE , |
| | AND SUCH PLATFORMS AND THE WALKWAYS, |
| | STAIRS AND LADDERS PROVIDING ACCESS TO |
| | AN EQUIPMENT PLATFORM SHALL NOT SERVE AS |
| | A PART OF THE MEANS OF EGRESS FROM THE |
| | BUILDING. |
| | |
| | 505.5.1 AREA LIMITATIONS. |
| | THE AGGREGATE AREA OF ALL INDUSTRIAL |
| | EQUIPMENT PLATFORMS WITHIN A ROOM SHALL |
| | NOT EXCEED TWO-THIRDS OF THE AREA OF THE |
| | ROOM IN WHICH THEY OCCUR. WHERE AN |
| | EQUIPMENT PLATFORM IS LOCATED IN THE |
| | SAME ROOM AS A MEZZANINE , THE AREA OF |
| | THE MEZZANINE SHALL BE DETERMINED BY |
| | SECTION 505.2 , AND THE COMBINED |
| | AGGREGATE AREA OF THE EQUIPMENT |
| | PLATFORMS AND MEZZANINES SHALL NOT |
| | EXCEED TWO-THIRDS OF THE ROOM IN WHICH |
| | THEY OCCUR. |
| | |
| | 12) STUCTURAL SHEETS MISSING STRUCTURAL |
| | ENGINEERS ADDRESS, SEE FAC |
| | 61G15-23.002(2). |
| | |
| | 13)S-2 DETAIL# 1 PLANS DO NOT PROVIDE |
| | BOLT PATTERN BASE PLATE, NOR THE LENGHT |
| | NOR TYPE OF ANCHOR. |
| | |
| | 14) SHEET D-1 INDICATES THE USE OF EFIS |
| | IN THE HORIZONTAL POSITION PROVIDE |
| | PRODUCT APPROVAL FOR SUCH USAGE. |
| | |
| | 15) PROVIDE INFORMATION ON THE WALK-IN |
| | COOLERS AND FREEZERS. |
| | 2603.4.1.2 COOLER AND FREEZER WALLS. |
| | FOAM PLASTIC INSTALLED IN A MAXIMUM |
| | THICKNESS OF 10 INCHES (254 MM) IN |
| | COOLER AND FREEZER WALLS SHALL: |
| | 1.HAVE A FLAME SPREAD INDEX OF 25 |
| | OR LESS AND A SMOKE-DEVELOPED INDEX OF |
| | NOT MORE THAN 450, WHERE TESTED IN A |
| | MINIMUM 4 INCH (102 MM) THICKNESS. |
| | 2.HAVE FLASH IGNITION AND |
| | SELF-IGNITION TEMPERATURES OF NOT LESS |
| | THAN 600?F AND 800?F (316?C AND 427?C), |
| | RESPECTIVELY. |
| | 3.HAVE A COVERING OF NOT LESS THAN |
| | 0.032-INCH (0.8 MM) ALUMINUM OR |
| | CORROSION-RESISTANT STEEL HAVING A BASE |
| | METAL THICKNESS NOT LESS THAN 0.0160 |
| | INCH (0.4 MM) AT ANY POINT. |
| | 4.BE PROTECTED BY AN AUTOMATIC |
| | SPRINKLER SYSTEM. WHERE THE COOLER OR |
| | FREEZER IS WITHIN A BUILDING, BOTH THE |
| | COOLER OR FREEZER AND THAT PART OF THE |
| | BUILDING IN WHICH IT IS LOCATED SHALL BE |
| | SPRINKLERED. |
| | |
| | 2603.4.1.3 WALK-IN COOLERS. |
| | IN NONSPRINKLERED BUILDINGS, FOAM |
| | PLASTIC HAVING A THICKNESS THAT DOES NOT |
| | EXCEED 4 INCHES (102 MM) AND A MAXIMUM |
| | FLAME SPREAD INDEX OF 75 IS PERMITTED IN |
| | WALK-IN COOLERS OR FREEZER UNITS WHERE |
| | THE AGGREGATE FLOOR AREA DOES NOT EXCEED |
| | 400 SQUARE FEET (37 M 2 ) AND THE FOAM |
| | PLASTIC IS COVERED BY A METAL FACING NOT |
| | LESS THAN 0.032-INCH-THICK (0.81 MM) |
| | ALUMINUM OR CORROSION-RESISTANT STEEL |
| | HAVING A MINIMUM BASE METAL THICKNESS OF |
| | 0.016 INCH (0.41 MM). A THICKNESS OF UP |
| | TO 10 INCHES (254 MM) IS PERMITTED WHERE |
| | PROTECTED BY A THERMAL BARRIER. |
| | |
| | 16) PROVIDE INFORMATION FOR CHECK-OUT |
| | AISLES.11-7.3(2)-(4) |
| | (2)CLEAR AISLE WIDTH FOR ACCESSIBLE |
| | CHECK-OUT AISLES SHALL COMPLY WITH |
| | SECTION 11-4.2.1 AND MAXIMUM ADJOINING |
| | COUNTER HEIGHT SHALL NOT EXCEED 38 |
| | INCHES (965 MM) ABOVE THE FINISH FLOOR. |
| | THE TOP OF THE LIP SHALL NOT EXCEED 40 |
| | INCHES (1015 MM) ABOVE THE FINISH FLOOR. |
| | |
| | (3)SIGNAGE IDENTIFYING ACCESSIBLE |
| | CHECK-OUT AISLES SHALL COMPLY WITH |
| | SECTION 11-4.30.7 AND SHALL BE MOUNTED |
| | ABOVE THE CHECK-OUT AISLE IN THE SAME |
| | LOCATION WHERE THE CHECK-OUT NUMBER OR |
| | TYPE OF CHECK-OUT IS DISPLAYED. |
| | (4)ALL CUSTOMER CHECK-OUT AISLES |
| | NOT REQUIRED BY THIS CODE TO BE |
| | ACCESSIBLE SHALL HAVE AT LEAST 32 INCHES |
| | (813 MM) OF CLEAR PASSAGE. |
| | |
| | 17) 11-7.4 SECURITY BOLLARDS. |
| | ANY DEVICE USED TO PREVENT THE REMOVAL |
| | OF SHOPPING CARTS FROM STORE PREMISES |
| | SHALL NOT PREVENT ACCESS OR EGRESS TO |
| | PEOPLE IN WHEELCHAIRS. AN ALTERNATE |
| | ENTRY THAT IS EQUALLY CONVENIENT TO THAT |
| | PROVIDED FOR THE AMBULATORY POPULATION |
| | IS ACCEPTABLE. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |