Plan Review Details - Permit 06030890
Plan Review Stops For Permit 06030890
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-09-28 Cont ID  
Sent By jwitmer Date 2006-09-28 Time 14:29 Rev Time 0.77
Received By jwitmer Date 2006-09-28 Time 14:29 Sent To  
Notes
2006-09-28 00:00:00REVISION-AS BUILT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-06-21 Cont ID  
Sent By jwitmer Date 2006-06-21 Time 13:32 Rev Time 1.11
Received By jwitmer Date 2006-06-21 Time 13:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-08 Cont ID  
Sent By jwitmer Date 2006-05-08 Time 16:11 Rev Time 0.77
Received By jwitmer Date 2006-05-08 Time 16:11 Sent To  
Notes
2006-05-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06030890
 ADD: 8989 OKEECHOBEE BLVD
 CONT: HALLMARK CONSTRUCTION
 TEL: (561)586-7664
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2)110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 3) CORRECT OCCUPANT LOAD FROM TABLE
 7.3.1.2, NOT IN THE 2004 FBC.
  
 4) NEW STOREFRONT,
 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A)STOREFRONT/ TRANSOM.
 B) MULLION
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-09-17 Cont ID  
Sent By dpalmer Date 2006-09-17 Time 10:36 Rev Time 0.00
Received By dpalmer Date 2006-09-17 Time 10:16 Sent To B
Notes
2006-09-17 00:00:00REDLINED ,,
 VERIFY NEW MAIN FOR TENANT, AS RISER
 SEEMS TO SHOW THIS BEING PROPOSED
 SOMWHERE ELSE?

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-07-07 Cont ID  
Sent By dpalmer Date 2006-07-07 Time 11:25 Rev Time 0.00
Received By dpalmer Date 2006-07-07 Time 11:25 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-08 Cont ID  
Sent By dpalmer Date 2006-06-08 Time 20:23 Rev Time 0.00
Received By dpalmer Date 2006-06-08 Time 20:09 Sent To  
Notes
2006-06-08 00:00:00**** UNSAT ***
  
  
 1) NOTE: PLEASE SEE A "SYSTEM" IS NOT
 BEING SHOWN FOR CONTROL AND SCHEDULING
 OF LIGHTING.
 PLEASE SEE THE OVER RIDE DEVIES SHOWN
 ARE OK AND ARE REQUIRED, HOWEVER PLEASE
 PROVIDE SPECS FOR UNITS BEING PROPOSED,
 AS THE DISTANCE NEEDS TO BE VERIFIED IF
 MOTION SENSORS ARE GOING TO BE USED FOR
 THE ENTIRE TENANT SPACE.NOT PART OF A
 NORMAL LIGHTING CONTROL SYSTEM.
 13-415.1.ABC.1.1, 13-415.1.ABC.1.2.
  
 2) NOTE: PLEASE SEE CONDUIT SIZES AHLL
 BE VERIFIED AND SPECIFIED ON RISER.
 PLEASE SEE CONDUIT FILL IS EXCEDDING ON
 RISER FOR 5- 4/0'S IN A 2" CONDUIT.
 TABLE 9, 215.5
 PLEASE VERIFY ALSO THE 4" CONDUIT SHOWN
 AS THIS SIZE INTO THE PANEL AS SHOWN
 DOES NOT SEEM LIKELY OR POSSIBLE.
  
 3) NOTE: PLEASE SEE A 3/0 IS BEING SHOWN
 FOR THE "EQUIPMENT GROUNDING
 CONDUCTOR"??
 3/0 SEEMS VERY LARGE AND ESP SINCE
 CONDUIT FILL IS EXCEEDED.
 PLEASE SEE 250.122 FOR SIZING WHICH MAY
 HELP IN CONDUIT SIZZING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-12 Cont ID  
Sent By dpalmer Date 2006-04-12 Time 07:15 Rev Time 0.00
Received By dpalmer Date 2006-04-11 Time 19:26 Sent To  
Notes
2006-04-12 00:00:00**** UNSAT ****
  
 1) NOTE: PLEASE SEE WE ARE UNDER THE
 2004 FBC. PLEASE SEE CHAPTER 13
 13-415.1.ABC.1.1 &.2
 PLEASE PROVIDE SYSTEM TO MEET ABOVE AND
 DETAIL FOR WHAT WILL BE USED AND TIME OF
 SCHEDULING.
  
 2) NOTE: PLEASE CLARIFY THE TWO CIRCUITS
 SHOWN IN PANEL FOR SD'S, YET THIS COULD
 NOT BE LCOATED>
 215.5
  
 3) NOTE: PLEASE SUBMIT/ INDICATE THE AIC
 RATINGS FOR ALL NEW SERVICE EQUIPMENT.
 110.9,215.5
  
 4) NOTE: PLEASE INDICATE THE EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO METERS
 AND METER TO TENANT PANELS. PLEASE KNOW,
 THE NUETRAL IN TENANT METER SHOULD BE
 INDICATED WITH A "FLOATING NUETRAL".
 PLEASE SEE 250.6,250.24B.
 250.110,250.122
  
 5) NOTE: PLEASE SEE PANELS BOTH INDICATE
 SIGN CIRCUITS ,HOWEVER PLEASE SHOW
 EITHER THE NEW OR EXISTING LOCATIONS ON
 PLANS.
 600.5
  
  
 WHEN AND BEFORE RESUBMITTING PLANS,
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEET INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-04-11 00:00:00NOTES TO FOLLOW

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-06-22 Cont ID  
Sent By mwennerg Date 2006-06-22 Time 11:00 Rev Time 0.00
Received By mwennerg Date 2006-06-22 Time 11:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-05-18 Cont ID  
Sent By mwennerg Date 2006-05-18 Time 10:22 Rev Time 0.00
Received By mwennerg Date 2006-05-18 Time 10:22 Sent To  
Notes
2006-05-18 00:00:00***DENIED***
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
 2) SMOKE DETECTORS SHOWN ON NEW PANEL
 SCHEDULE ON SHT A.2. IF THIS REFERS TO
 DUCT SMOKE DETECTORS, NEW INSTALLATIONS
 SHALL INITIATE A GENERAL FIRE ALARM IF
 PROVIDED, IN ACCORDANCE WITH LOCAL
 REQUIREMENTS.
  
 3) ADDITIONAL 2A,-10B,C RATED FIRE
 EXTINGUISHERS ARE REQUIRED IN PROXIMITY
 OF EXIT DOORS IN SPACES #206 & #210.
  
 4) CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-09 Cont ID  
Sent By adarroug Date 2006-09-09 Time 14:15 Rev Time 0.00
Received By adarroug Date 2006-09-09 Time 14:15 Sent To E
Notes
2006-09-09 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-07 Cont ID  
Sent By adarroug Date 2006-07-07 Time 10:10 Rev Time 0.00
Received By adarroug Date 2006-07-07 Time 10:10 Sent To E
Notes
2006-07-07 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-07 Cont ID  
Sent By adarroug Date 2006-06-07 Time 14:43 Rev Time 0.00
Received By adarroug Date 2006-06-07 Time 14:43 Sent To  
Notes
2006-06-07 00:00:00TO "BOB"#12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-18 Cont ID  
Sent By lmartine Date 2006-05-18 Time 11:02 Rev Time 0.00
Received By lmartine Date 2006-03-21 Time 19:01 Sent To  
Notes
2006-04-11 00:00:00TO "COMM" BD#5
2006-03-21 00:00:00WAITING FOR COMM BOARD

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-04-29 Cont ID  
Sent By pschmitz Date 2006-04-29 Time 13:40 Rev Time 0.00
Received By pschmitz Date 2006-04-29 Time 13:40 Sent To  
Notes
2006-04-29 00:00:00SHELL BUILD OUT ONLY, EXISTING
 FACILITIES.