Plan Review Details - Permit 06030886
Plan Review Stops For Permit 06030886
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-05-01 Cont ID  
Sent By rmcdouga Date 2006-05-01 Time 13:43 Rev Time 0.00
Received By rmcdouga Date 2006-05-01 Time 12:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-03-23 Cont ID  
Sent By rmcdouga Date 2006-03-23 Time 12:21 Rev Time 0.00
Received By rmcdouga Date 2006-03-23 Time 12:21 Sent To  
Notes
2006-03-23 00:00:00DENIED
  
 1) THE DESIGN PRESSURE LISTED IN THE NOA
 FOR THE SPECIFIED ASSEMBLY IS TOO LOW
 AND REQUIRES ENHANCED FASTENING IN
 ACCORDANCE WITH RAS 117 IN ORDER TO MEET
 THE REQUIRED PRESSURES. LIMITATION
 NUMBER 7 OF THE NOA REQUIRES THESE
 CALCULATIONS TO BE DONE BY AN ENGNEER,
 ARCHITECT OR REGISTERED ROOF CONSULTANT.
 SUBMIT SIGNED AND SEALED CALCULATIONS.
  
 2) VALUE OF WORK HAS BEEN INCREASED
 BASED ON MARSHALL AND SWIFT ESTIMATING
 GUIDE. 700 SQFT @ $3.78 IS $2646.00.
  
 3)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-20 Cont ID  
Sent By lmartine Date 2006-03-20 Time 15:18 Rev Time 0.00
Received By lmartine Date 2006-03-20 Time 15:18 Sent To  
Notes
2006-03-20 00:00:00 
  
 SPECIFY SYSTEM TO BE INSTALLED,
  
 VERIFY COMPLIANCE WITH LIMITATION #7
  
  
  
  
  
  
 L.MARTINEZ
 805-6710