Plan Review Details - Permit 06030810
Plan Review Stops For Permit 06030810
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-05-04 Cont ID  
Sent By amorse Date 2006-05-04 Time 07:01 Rev Time 0.75
Received By amorse Date 2006-05-04 Time 07:01 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-10 Cont ID  
Sent By amorse Date 2006-04-10 Time 07:02 Rev Time 0.50
Received By amorse Date 2006-04-10 Time 07:02 Sent To PC
Notes
2006-04-10 00:00:00 
  
 DENIED
  
 1) PROVIDE PLAN VIEW OF HOUSE SHOWING
 ALL WINDOWS AND DOORS. SECTION 507.3 OF
 THE EXISTING BUILDING CODE AS ATTACHED
 ALLOWS UP TO 25% OF WINDOWS TO BE
 REPLACED WITHOUT MANDITORY SHUTTER
 PROTECTION. OVER 25% AND SHUTTERS WILL
 BE REQUIRED AND AS SUCH WILL REQUIRE
 PRODUCT APPROVALS
  
 2) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
  
 NOTE: THE FL# IS 5974 FOR CHOSEN WINDOWS
 SUBMIT 2 COPIES OF THIS STATE APPROVAL
 AND THE EVALUATION REPORT THAT IS
 ATTACHED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-02 Cont ID  
Sent By adarroug Date 2006-05-02 Time 16:19 Rev Time 0.00
Received By adarroug Date 2006-05-02 Time 16:19 Sent To B
Notes
2006-05-02 00:00:00TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-04-10 Time   Rev Time 0.00
Received By dpalmer Date 2006-03-21 Time 16:29 Sent To  
Notes
2006-03-21 00:00:00TO MISC INBOX.