Plan Review Details - Permit 06030804
Plan Review Stops For Permit 06030804
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-19 Cont ID  
Sent By jgomez Date 2006-04-19 Time 17:29 Rev Time 3.00
Received By jgomez Date 2006-04-19 Time 17:28 Sent To  
Notes
2006-04-19 00:00:00BUILDING REVIEW CHECKLIST:
 1- NOTICE OF COMMENCEMENT IS EXPIRED
 AFTER 90 DAYS IF WORK IS NOT COMMENCED.
 NEED RE-RECORDED NOC.
  
 2- PROVIDE DRAINAGE PLAN AS REQUIRED BY
 SEC. R401.3 2004 FLORIDA RES. CODE.
  
 3- ENGINEER TO PROVIDE ALL HIS
 INFORMATION IN TITLE BLOCK INCLUDING
 LICENSE # AND CERTIFICATE OF
 AUTHORIZATION FOR TREASURE COAST
 BUILDING ENGINEERS, INC. AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTE AND FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002.
  
 4- ENGINEER TO UPDATE ALL PLANS AND
 GENERAL NOTES TO COMPLY WITH 2004
 FLORIDA RESIDENTIAL CODE AND 2004
 FLORIDA BUILDING CODE WHICH ARE THE
 CODES IN EFFECT AFTER OCTOBER 1ST 2005.
 UPDATE ALL GENERAL NOTES AND SPECIFIC
 REFERENCE STANDARDS AND CURRENT EDITION
 ADOPTED BY THE 2004 CODES. SEE COMMENTS
 ON REVIEWED PLANS.
  
 5- ROOF SHEATHING NAILING: REVISE SPECS
 SHOWN ON DETAILS AND NOTES THROUGHOUT
 ALL PLANS TO MATCH OR EXCEED MINIMUM
 FASTENING SPACING AS SHOWN ON TABLE
 2304.9.1 OF FBC 2004.
  
 6- WALL SECTIONS TO SPECIFY FIREBLOCKING
 MATERIAL AND SIZE AT CONCEALED SPACES AS
 REQUIRED BY SEC. R602.8 2004 FLORIDA
 RESIDENTIAL CODE.
  
 7- PROVIDE SPECIFICATIONS FOR DOOR
 INSIDE GARAGE TO COMPLY WITH SECTION
 R309.1 2004 RESIDENTIAL CODE.
  
 8- ALL PRODUCT APPROVALS NEED TO BE
 APPROVED FOR 2004 FLORIDA CODE VERSION.
 RE-SUBMIT ALL FLORIDA OR LOCAL PRODUCT
 APPROVALS FOR:
 A) ENTRY DOORS.
 B) FRENCH DOORS MULLED TOGETHER AS
 SHOWN ON LIVING ROOM.
 ***NOTE: IF PRODUCT APPROVAL DOESN'T
 COVER 2 PAIR OF FRENCH DOORS MULLED
 TOGETHER, THEN, COMPLETE STRUCTURAL
 DETAILS AND SPECS ARE REQUIRED TO SHOW
 INSTALLATION. SEC. 106.1.2 OF CITY
 AMENDMENTS TO FBC 2004.
 C) POCKET SLIDING GLASS DOORS AS SHOWN
 ON PLANS BY LEISURE ROOM.
 D) ALL OTHER SLIDING GLASS DOORS.
 E) OVERHEAD GARAGE DOORS FOR LARGE AND
 SMALL DOORS. SEE PLANS.
 F) FIXED WINDOWS AS SHOWN ON PLANS.
 G) WINDOW MULLIONS.
 H) ALL STRUCTURAL CONNECTORS SPECIFIED
 ON PLANS (SIMPSON AND USP. SEE PLANS)
 I) ROOF TILE.
 J) SINGLE HUNG WINDOWS.
 K) HORIZONTAL SLIDING WINDOWS AS SHOWN
 ON PLANS.
 L) GARAGE SIDE SWING DOOR.
  
 9- STORM SHUTTERS: A) PROVIDE 2004
 VERSION APPROVED FLORIDA OR LOCAL
 PRODUCT APPROVAL.
 B) PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE THAT
 COVERS ALL REQUIRED MINIMUM INFORMATION
 FOR PLAN REVIEW.
 C) INFORMATION SUBMITTED IS FOR LOT
 30. THIS IS LOT 22. REVISE AS REQUIRED.
  
 10- UPDATE CONTRACTORS INFORMATION WITH
 PEMITING CLERK. NAME ON THE APPLICATION
 DOESN'T MATCH NAME SHOWN ON CONTRACTOR'S
 SCREEN. APPLICATION SAYS MONTICELLO
 HOMES, WHILE CONTRACTOR'S SCREEN SAYS AR
 CUSTOM HOMES.
  
 11- ENERGY CALCULATIONS: A) CALCULATIONS
 NEED TO BE DONE FOR WORST CASE SCENARIO
 OR CALCULATED ACCORDING TO THE ACTUAL
 HOUSE ORIENTATION. CALCS SUBMITTED DON'T
 COMPLY WITH EITHER ONE. REVISE AS REQ'D.
 B) REVISE UNDER ATTIC AREA. NEED TO
 INCLUDE WALLS CONSIDERED AS CEILING AREA
 REQ'D BY SEC. 13-604.1.A.1 OF FBC 2004.
 C) COMPLETE INFORMATION ON TOP OF FORM
 INCLUDING CORRECT PROJECT NAME & ADDRESS
  
 12- SOIL TEST REPORT NEEDS TO HAVE
 ENGINEER'S ORIGINAL SEAL AND SIGNATURE
 AS REQ'D BY CHAPTER 471 FLORIDA STATUTES
  
 13- PROVIDE BBQ GRILL APPROVED LISTING
 AND SPECIFICATIONS THAT ALLOWS BBQ
 GRILLS TO BE INSTALLED IN THE REAR PORCH
 OR PROVIDE APPROVED LISTING AND SPECS
 FOR EXTERIOR USE HODD ABOVE BBQ GRILL.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
  
  
 14- OWES $1184.51 FOR UPDATED VALUATION
 AND RADON FEES.
  
 15- DETAIL 7 OF SHEET 4S1: SPECIFY
 SPACING FOR 2"X4" BLOCKING. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 16- DETAIL 4 OF SHEET 4S2: A) SPECIFY
 ALL FASTENERSINCLUDING ATTACHMENT OF
 "L" BRACE AT TOP AND BOTTOM.
 B) HOW LONG ARE THE ANCHOR BOLTS.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
 C) HOW IS THE SIMPSON CONNECTOR HPAHD22
 INSTALLED TO ALLOW THE 10" MIN.
 EMBEDMENT INTO THE U BLOCK BEAM. SEE
 SIMPSON CATALOGUE.
  
 17- REVISE DETAIL 8 OF SHEET 4S2: SEE
 TABLE 2304.9.1 FBC 2004 FOR MINIMUM NAIL
 SPACING REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-18 Cont ID  
Sent By dpalmer Date 2006-03-18 Time 18:51 Rev Time 0.00
Received By dpalmer Date 2006-03-18 Time 18:27 Sent To Z
Notes
2006-03-18 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SEE THAT ALL PLANS SHALL
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLR FOR PLANS/
 DESIGN.
 PLEASE SEE FBC 2004, ADIMINSTRATIVE CODE
 AS ADOPTED BY THE CITY OF WEST PALM
 BEACH. 106.3.4.3, 104.2.1
  
 2)NOTE: PLEASE SEE ALL OTHER SHEETS
 CONTAINING THE ENGINEERING FIRMM TITLE
 BLOCKS,; THESE ARE MISSING THE REQUIRED
 CERTIFICATE OF AUTHORIZATION NUMBER AS
 REQUIRED PER FLORIDA ADMINISTRATIVE
 CODE, 61G15-23.002 ANDPER FLORIDA
 STATUES, 471.023
 THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHETHER ORNOT COMMENT IS
 MADE BY OTHER TRADES.
  
 3)NOTE: PLEASE SEE SOME MISSING RECEPTS
 PER 210.52.
 THESE AHVE BEEN REDLINED ON PLANS.
  
 4)NOTE: PLEASE SEE PLANS ARE MISSING
 PANEL "C' WHICH IS SHOWN ON RISER AND
 PANEL SCHEDULE, HOWEVER COULD NOT LOCATE
 THIS ON PLANS.
 215.5
  
 5)NOTE: PLEASE CLARIFY PANEL "C" AS,
 PANEL "C" SHOWS 80A, YET PANEL "B" SHOWS
 60A FEED?
 215.5
  
 6)NOTE: PLEASE SEE KITCHEN ISLAND RECEPT
 TO BE SHOWN AS GFI PER 210.8A6
  
 PLEASE COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT THE NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. ONLY ONE SET OF THE
 REMOVED OLD/VOIDED SHEETS ARE TO BE
 SUBMITTED BACK FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REIVEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-19 Cont ID  
Sent By jgomez Date 2006-04-19 Time 17:31 Rev Time 0.00
Received By jgomez Date 2006-03-17 Time 15:53 Sent To  
Notes
2006-03-17 00:00:00TO "SFR" "E"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-03-21 Cont ID  
Sent By tgordon Date 2006-03-21 Time 09:44 Rev Time 0.45
Received By tgordon Date 2006-03-21 Time 09:44 Sent To Z
Notes
2006-03-21 00:00:00*** DENIED ***
 1)ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 2) MECHANICAL PLANS NEED THE JOB ADDRESS
 ON THEM.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-03-20 Cont ID  
Sent By jleech Date 2006-03-20 Time 09:16 Rev Time 0.00
Received By jleech Date 2006-03-20 Time 09:16 Sent To Z
Notes
2006-03-20 00:00:00DENIED;
 SANITARY RISER DIAGRAM IS REQUIRED PER
 FBC-2004 CHAPTER 1 SEC. 106.3.5.4 (9).
 SIZE ALL PIPES AND SHOW ALL VENTS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status F Date 2006-03-22 Cont ID  
Sent By mmclean Date 2006-03-22 Time 14:17 Rev Time 0.00
Received By mmclean Date 2006-03-22 Time 14:17 Sent To B
Notes
2006-03-22 00:00:00DENIED,
 1. THE SITEPLAN DOES NOT IDENTIFY THE
 ADDRESS OF THE JOB.
 2. NEED TO PROVIDE TWO COPY OF SURVEY OF
 PROPERTY.
  
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/SPA/SCREEN ENCLOSURE.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720