Plan Review Details - Permit 06030641
Plan Review Stops For Permit 06030641
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-07-14 Cont ID  
Sent By btrobaug Date 2006-07-14 Time 19:12 Rev Time 0.50
Received By btrobaug Date 2006-07-14 Time 19:02 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-24 Cont ID  
Sent By btrobaug Date 2006-03-24 Time 16:45 Rev Time 0.50
Received By btrobaug Date 2006-03-24 Time 16:10 Sent To P
Notes
2006-03-24 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE KITCHEN RECEPTACLE SPACING MUST
 COMPLY WITH 210.52(C)(1)- WALL COUNTER
 SPACES. A RECEPTACLE OUTLET SHALL BE
 INSTALLED AT EACH WALL COUNTER SPACE
 THAT IS 300 MM (12 IN.) OR WIDER.
 RECEPTACLE OUTLETS SHALL BE INSTALLED SO
 THAT NO POINT ALONG THE WALL LINE IS
 MORE THAN 600 MM (24 IN.) MEASURED
 HORIZONTALLY FROM A RECEPTACLE OUTLET IN
 THAT SPACE.
  
 2} 210.52(A) GENERAL PROVISIONS. IN
 EVERY KITCHEN, FAMILY ROOM, DINING ROOM,
 LIVING ROOM, PARLOR, LIBRARY, DEN,
 SUNROOM, BEDROOM, RECREATION ROOM, OR
 SIMILAR ROOM OR AREA OF DWELLING UNITS,
 RECEPTACLE OUTLETS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE GENERAL PROVISIONS
 SPECIFIED IN 210.52(A)(1) THROUGH
 (A)(3).
 (1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED
 HORIZONTALLY ALONG THE FLOOR LINE IN ANY
 WALL SPACE IS MORE THAN 1.8 M (6 FT)
 FROM A RECEPTACLE OUTLET.
  
 3} PLEASE PROVIDE A PANEL SCHEDULE WITH
 WIRE AND BREAKER SIZES PER 106.3.5.4
 FBC.
  
 4} THE COTTAGE MUST HAVE A DISCONNECT
 PER 225.31 GROUNDED PER 250.32, IF IT IS
 A SEPARATE STRUCTURE. PROVIDE A RISER
 DIAGRAM OF THE ENTIRE SERVICE SO
 COMPLIANCE WITH THESE ARTICLES CAN BE
 DETERMINED.
  
 PLEASE USE ACCEPTED ELCTRICAL SYMBOLS
 FOR THE DEVICES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-28 Cont ID  
Sent By spalmer Date 2007-03-28 Time 17:22 Rev Time 0.00
Received By spalmer Date 2007-03-28 Time 17:22 Sent To E
Notes
2007-03-28 17:23:06TO BILL TROBAUGH

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-12 Cont ID  
Sent By adarroug Date 2006-07-12 Time 15:26 Rev Time 0.00
Received By adarroug Date 2006-07-12 Time 15:26 Sent To E
Notes
2006-07-12 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-24 Cont ID  
Sent By btrobaug Date 2006-03-24 Time 16:10 Rev Time 0.00
Received By btrobaug Date 2006-03-17 Time 10:57 Sent To E
Notes
2006-03-17 00:00:00TO "E" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-07-18 Cont ID  
Sent By mperson Date 2006-07-18 Time 09:51 Rev Time 0.33
Received By mperson Date 2006-07-18 Time 09:51 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-04-03 Cont ID  
Sent By mperson Date 2006-04-03 Time 08:16 Rev Time 0.33
Received By mperson Date 2006-04-03 Time 08:16 Sent To B
Notes
2006-04-03 00:00:00****DENIED****
 REFERENCE: FBC-2004 PLUMBING, CITY OF
 WEST PALM BEACH, AMENDMENTS TO FBC-2004
 CHAPTER 1, ADMINISTRATION:
  
 PLEASE ADJUST YOUR DRAWINGS TO REFLECT
 THE FOLLOWING INFOMATION REQUIRED FOR
 PLAN REVIEW:
  
 1. MORE INFORMATION REQUIRED. PLEASE
 INDCATE ON DRAWING EXISTING PLUMBING
 LAYOUT, AND INDICATE ON DRAWING NEW
 PROPOSED PLUMBING LAYOUT. IF NEW
 PROPOSED PLUMBING LAYOUT IS DIFFERENT
 FROM EXISTING PLEASE FOLLOW WHAT IS
 REQUIRED IN #2. IF LAYOUT IS THE SAME
 PLEASE INDICATE ON DRAWING FIXTURE
 CHANGE OUT ONLY.
 2. 106.3.5.4 RESIDENTIAL (ONE AND TWO
 FAMILY) SUBMIT A PLUMBING SANITARY
 ISOMETRIC RISER DIAGRAM INDICATING ALL
 WASTE, VENTS, AND TRAPS WITH SIZES.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  