Plan Review Details - Permit 06030627
Plan Review Stops For Permit 06030627
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-09-27 Cont ID  
Sent By alange Date 2006-09-27 Time 08:45 Rev Time 1.00
Received By alange Date 2006-09-27 Time 08:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-08-15 Cont ID  
Sent By alange Date 2006-08-15 Time 08:39 Rev Time 0.50
Received By alange Date 2006-08-15 Time 08:39 Sent To  
Notes
2006-08-15 00:00:00 
 DENIED
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 5.SELECT THE ROOFING ASSEMBLY USED ON
 THE PRODUCT APPROVAL.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
  
  
 A.SHOW ROOM USE OF ROOM BEING BUILT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEWHE
 SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-08-01 Cont ID  
Sent By alange Date 2006-08-01 Time 11:02 Rev Time 1.00
Received By alange Date 2006-08-01 Time 11:02 Sent To  
Notes
2006-08-01 00:00:00 
 DENIED
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 5.SELECT THE ROOFING ASSEMBLY USED ON
 THE PRODUCT APPROVAL.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
  
  
 A.SHOW ROOM USE OF ROOMS ADJACENT TO
 THE ROOM ADDITION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEWHE
 SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-05-26 Cont ID  
Sent By alange Date 2006-05-26 Time 09:04 Rev Time 1.00
Received By alange Date 2006-05-26 Time 08:58 Sent To  
Notes
2006-05-26 00:00:00 
 DENIED
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 5.SELECT THE ROOFING ASSEMBLY USED ON
 THE PRODUCT APPROVAL.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 10.INCLUDE A SITE PLAN.
  
 NEW COMMENT;
 A.SHOW ROOM USE OF ADDITION AND ROOMS
 ADJACENT TO THE ROOM ADDITION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEWHE
 SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-07 Cont ID  
Sent By alange Date 2006-04-07 Time 09:05 Rev Time 1.50
Received By alange Date 2006-04-07 Time 09:02 Sent To Z
Notes
2006-04-07 00:00:00 
 DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 5.PRODUCT APPROVALS REQUIRED FOR ROOF,
 WINDOWS AND IMPACT PROTECTION.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
  
 9.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 10.INCLUDE A SITE PLAN.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEWHE
 SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-08-14 Cont ID  
Sent By btrobaug Date 2006-08-14 Time 07:14 Rev Time 0.50
Received By btrobaug Date 2006-08-14 Time 06:41 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-08-01 Cont ID  
Sent By btrobaug Date 2006-08-01 Time 08:02 Rev Time 0.50
Received By btrobaug Date 2006-08-01 Time 07:48 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-05-25 Cont ID  
Sent By btrobaug Date 2006-05-25 Time 13:33 Rev Time 0.50
Received By btrobaug Date 2006-05-25 Time 12:21 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-03-24 Cont ID  
Sent By btrobaug Date 2006-03-24 Time 08:01 Rev Time 0.33
Received By btrobaug Date 2006-03-24 Time 07:56 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-09-08 Cont ID  
Sent By adarroug Date 2006-09-08 Time 18:37 Rev Time 0.00
Received By adarroug Date 2006-09-08 Time 18:37 Sent To B
Notes
2006-09-08 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-08-12 Cont ID  
Sent By adarroug Date 2006-08-12 Time 16:17 Rev Time 0.00
Received By adarroug Date 2006-08-12 Time 16:17 Sent To E
Notes
2006-08-12 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-07 Cont ID  
Sent By adarroug Date 2006-08-07 Time 17:07 Rev Time 0.00
Received By adarroug Date 2006-08-07 Time 17:07 Sent To Z
Notes
2006-08-07 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-07-31 Cont ID  
Sent By adarroug Date 2006-07-31 Time 12:42 Rev Time 0.00
Received By adarroug Date 2006-07-31 Time 12:42 Sent To E
Notes
2006-07-31 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-24 Cont ID  
Sent By adarroug Date 2006-07-24 Time 10:27 Rev Time 0.00
Received By adarroug Date 2006-07-24 Time 10:27 Sent To Z
Notes
2006-07-24 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-24 Cont ID  
Sent By adarroug Date 2006-05-24 Time 15:37 Rev Time 0.00
Received By adarroug Date 2006-05-24 Time 15:37 Sent To E
Notes
2006-05-24 00:00:00TO "E" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-08 Cont ID  
Sent By adarroug Date 2006-05-08 Time 10:53 Rev Time 0.00
Received By adarroug Date 2006-05-08 Time 10:53 Sent To Z
Notes
2006-05-08 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-07 Cont ID  
Sent By alange Date 2006-04-07 Time 09:02 Rev Time 0.00
Received By alange Date 2006-03-16 Time 11:51 Sent To  
Notes
2006-03-16 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-03-24 Cont ID  
Sent By btrobaug Date 2006-03-24 Time 08:07 Rev Time  
Received By btrobaug Date   Time   Sent To  
Notes
2006-03-24 00:00:00 
  
 NOT REQUIRED PER TOM./WRT.

Review Stop Z ZONING
Rev No 4 Status P Date 2006-08-11 Cont ID  
Sent By mmclean Date 2006-08-11 Time 13:37 Rev Time 0.00
Received By mmclean Date 2006-08-11 Time 13:37 Sent To I
Notes
2006-08-11 00:00:00REPLACE OF EXISTING STRUCTURE (FIRE
 DAMANGED)

Review Stop Z ZONING
Rev No 3 Status F Date 2006-07-29 Cont ID  
Sent By mmclean Date 2006-07-29 Time 11:33 Rev Time 0.00
Received By mmclean Date 2006-07-29 Time 11:33 Sent To I
Notes
2006-07-29 00:00:00DENIED,
 1. THE PLANS A-1, INDICATE A 93.33SQ FT
 ADDITION TO THE DAMANGED FIRE STRUCTURE.
 2. PLEASE SHOW THE LOCATION OF THE WORK
 ON THE TWO COPY OF CURRENT SURVEY.
 3. IF THERE IS NO ADDITION,PLEASE REMOVE
 FROM PLANS AND INDICATE ON THE SURVEY
 AND PLANS TO SAY ONLY INTERIOR WORK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status F Date 2006-05-23 Cont ID  
Sent By mmclean Date 2006-05-23 Time 09:22 Rev Time 0.00
Received By mmclean Date 2006-05-23 Time 09:22 Sent To I
Notes
2006-05-23 00:00:00DENIED, (2ND REQUEST)
 1. MUST PROVIDE TWO COPY OF CURRENT
 SURVEY SHOWING THE LOCATION OF THE
 PROPOSED ADDITION (93.33SQ FT), WITH
 SETBACKS.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-04-12 Cont ID  
Sent By mmclean Date 2006-04-12 Time 14:46 Rev Time 0.00
Received By mmclean Date 2006-04-12 Time 14:46 Sent To  
Notes
2006-04-12 00:00:00DENIED,
 1. MUST PROVIDE TWO COPY OF CURRENT
 SURVEY SHOWING THE LOCATION OF THE
 PROPOSED ADDITION (95SQ FT).
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720