Plan Review Details - Permit 06030606
Plan Review Stops For Permit 06030606
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-10-13 Cont ID  
Sent By mjacobs Date 2006-10-13 Time 06:43 Rev Time 0.00
Received By mjacobs Date 2006-10-13 Time 06:13 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2006-10-02 Cont ID  
Sent By mjacobs Date 2006-10-02 Time 11:12 Rev Time 0.00
Received By mjacobs Date 2006-10-02 Time 09:54 Sent To PC
Notes
2006-10-02 00:00:00 
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: REV.
 ACTION: DENIED
  
 1) PLANS ARE TO BE SIGNED WITH A FULL
 SIGNATURE FROM THE ARCHETECT OF RECORD
 PER 481.221 WITH A MINIMUM OF FIRST AND
 LAST NAME AS SHOWN ON THE ARCHITECTS'
 LICENSE, FAC 61G1-16.003
  
 2) FAC. 61G-16.004 A TITLE BLOCK MUST
 APPEAR ON ALL ARCHITECTRUAL OR INTERIOR
 DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS, THE TITLE BLOCK
 MUST, AT A MINIMUM,CONTAIN THE FOLLOWING
 INFORMATION:
 (1) FIRM NAME,ADDRESS,AND TELEPHONE #
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFACTION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND
 DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF
 THE PERSON SEALING THE DOCUMENT.
  
  
 3) THE SCALES MENTION ON THE DRAWINGS
 DOES NOT CORRESPOND WITH THE DEATILS.
 ADJUST THE SCALE TO REFLECT THE CORRECT
 DIMENTIONS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-08-02 Cont ID  
Sent By mjacobs Date 2006-08-02 Time 17:21 Rev Time 0.00
Received By mjacobs Date 2006-08-02 Time 16:46 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-07-25 Cont ID  
Sent By mjacobs Date 2006-07-25 Time 13:39 Rev Time 0.00
Received By mjacobs Date 2006-07-24 Time 17:43 Sent To  
Notes
2006-07-24 00:00:00 
 1) W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 EACH PRODUCT SHALL BE APPROVED BY THE
 DESIGNER OF RECORD. PLEASE SUBMIT
 APPROVED AND UP-DATEDPRODUCT
 APPROVALS. SOME OF THEPRODUCTS
 SUBMITTED WERE OUT-DATED.
  
 2) THE ACCESSIBILITY CODE REFERENCE BOOK
 BEING USE NOW IS THE 2004 NOT THE 2001.
 CORRECT PLANS ACCORDINGLY. SEE PAGE T.1
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-19 Cont ID  
Sent By mjacobs Date 2006-06-19 Time 13:31 Rev Time 0.00
Received By mjacobs Date 2006-06-19 Time 07:54 Sent To  
Notes
2006-06-19 00:00:00 
 1) ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE. SEE SHEET T.1
  
 2) THE UL ASSEMBLY X526 ON THE DRAWINGS
 DOES NOT MATCH THE DESIGN IN THE UL
 BOOK. SUBMIT A DESIGN WHICH CORRESPOND
 WITH ONE OF THE DESIGNS IN THE UL BOOK.
 SEE SHEET A.1.
  
 3) PRODUCT APPROVALS ARE REQUIED FOR THE
 NEW STOREFRONT AND DOORS.
 WPB ADMIN CODE 106.3* PRODUCT APPROVALS.
 THOSE PRODUCT WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-11 Cont ID  
Sent By mjacobs Date 2006-04-11 Time 11:03 Rev Time 0.00
Received By mjacobs Date 2006-04-11 Time 07:02 Sent To PC
Notes
2006-04-11 00:00:001) ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 2) ALL CHANGES ON THE DRAWINGS HAS TO BE
 DONE BY THE PERSON WHO SIGN AND SEALED
 THE DRAWINGS. EACH CHANGE SHALL BE
 INITIAL AND DATED BY THAT PERSON OR NEW
 SHEETS SUBMITTED WITH THE NEW CHANGES.
  
 3) A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME AND AFFIX HIS SEAL TO ALL
 PLANS, SPECIFICATIONS, REPORTS AND FINAL
 BID DOCUMENTS PROVIDED TO THE OWNER OR
 THE OWNER'S REPRESENTATIVE, OR OTHER
 DOCUMENTS PREPARED OR ISSUED BY SAID
 REGISTRANT AND BEING FILED FOR PUBLIC
 RECORD. THE DATE THAT THE SIGNATURE AND
 SEAL IS AFFIXED AS PROVIDED HEREIN SHALL
 BE ENTERED ON SAID PLANS,
 SPECIFICATIONS, REPORTS, OR OTHER
 DOCUMENTS IMMEDIATELY UNDER THE
 SIGNATURE OF THE PROFESSIONAL ENGINEER,
 FAC 61G15-23.002(1)
 FS 471.025
  
 4) PLANS ARE TO BE SIGNED WITH A FULL
 SIGNATURE FROM THE ARCHETECT OF RECORD
 PER 481.221 WITH A MINIMUM OF FIRST AND
 LAST NAME AS SHOWN ON THE ARCHITECTS'
 LICENSE, FAC 61G1-16.003
  
 5) 61G1-16.004FL. ADMIN. CODE.PLANS
 PREPARED BY A REGISTERED ARCHITECT SHALL
 INCLUDE A TITLE BLOCK WHICH MUST:
 - STATE THE FIRM NAME, ADDRESS AND
 TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND
 DATED SEAL
 - INCLUDE THE PRINTED NAME OF THE
 ARCHITECT SEALING THE PLANS
  
 6) SHEET D1 INDICATES THE DOOR TO BE
 DEMO.ON SHEET A1 THE DOOR IS IN A
 DIFFERENT LOCATION. IF THE DOOR IS
 REMAINING WHERE IT IS, WHY SHEET A1
 SHOWS IT IN A DIFFERENT LOCATION?
 PROVIDE PRODUCT APPROVALS FOR THE NEW
 DOOR OR THE DRAWINGS MUST SHOW THE DOOR
 IN THE SAME LOCATION AS IT IS ON SHEET
 D1.
  
 7) PROVIDE NEW SHEETS SHOWING THE
 PROPOSED WORK AT THE LOCATION. HAND
 WRITTEN NOTES ARE NOT ACCEPTABLE ON
 DRAWINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-08-02 Cont ID  
Sent By jleahy Date 2006-08-02 Time 16:30 Rev Time 0.45
Received By jleahy Date 2006-08-02 Time 16:29 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-07-23 Cont ID  
Sent By jleahy Date 2006-07-23 Time 23:12 Rev Time 1.00
Received By jleahy Date 2006-07-23 Time 23:10 Sent To  
Notes
2006-07-23 00:00:00UNSAT 3RD REVIEW
  
  
 1) NOTE:PLAN STILL SHOWS NO CONTROL OF
 LIGHTING PER 13-415 OF THE FBC.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND
 .1.3
 PLEASE SEE 13-415.1.AB.1,13-415.2.ABC.1
 AND TABLES 415.2.C.1, 415.2.B.1
 PLEASE KNOW ORIGIANL DESIGN WAS UNDER
 THE 2001 FBC , HOWEVER PLEASE SEE
 DESIGNS ARE UNDER 2004 FBC AS THESE WERE
 SUBMITTED FOR PERMIT AFTER OCT. 1ST 2005
 WHEN THE NEW CODE WENT INTO EFFECT.
 PLEASE ALSO SEE 13-415.1AB
  
 2) NOTE: PLEASE SEE PLANS, 1999 NEC IS
 REFERENCED ON COVER FBC
 USES 2002 NEC, CHAPTER 27.
  
 3) NOTE: PLEASE SEE AS THE SAME REVIEW
 COMMENTS HAVE NOT BEEN ADDRESSEDA 4X
 FEE HAS NOW BEEN ASSESSED FOR THE PLAN
 REVIEW PORTION OF THE BASE PERMIT FEE.
 PLEASE SEE 553.802B.
 PLEASE KNOW, THIS IS A REQUIRED FEE
 UNDER FLORIDA STATUES AND WILL APPLY FOR
 EACH REVIEW IF THE SAME CODE COMPLIANCE
 COMMENT(S) ARE NOT ADDRESSED.
 PLEASE KNOW AS FEE OF $1680.00 MUST BE
 PAID BEFORE RESUBMITTING PLANS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 JAKE LEAHY
 561-805-6740
 OR
 DEWEY PALMER
 561-805-6717

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-23 Cont ID  
Sent By jleahy Date 2006-06-22 Time 07:41 Rev Time 1.15
Received By jleahy Date 2006-06-22 Time 07:41 Sent To  
Notes
2006-06-22 00:00:00SEE NOTES FROM FIRST REVIEWJL

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-13 Cont ID  
Sent By jleahy Date 2006-04-03 Time 09:30 Rev Time 1.00
Received By jleahy Date 2006-04-03 Time 09:30 Sent To  
Notes
2006-04-03 00:00:00JLEAHY PUT IN COMMENTS FOR P PETTY
  
 LIGHTING, A/C, AND EQUIPMENT SHALL MEET
 THE REQUIREMENTS OF CHAPTER 13 OF THE
 FLORIDA BUILDING CODE.
  
 NO SIGN CIRCUIT SHOWN ON DRAWINGS OR
 LOAD CALCULATION.
  
 QUESTIONS CALL PHIL 805-6742

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-08-02 Cont ID  
Sent By nmccray Date 2006-08-02 Time 10:22 Rev Time 0.00
Received By nmccray Date 2006-08-02 Time 10:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-06-22 Cont ID  
Sent By mwennerg Date 2006-06-22 Time 10:22 Rev Time 0.00
Received By mwennerg Date 2006-06-22 Time 10:22 Sent To  
Notes
2006-06-22 00:00:00***DENIED***
  
 1) IN ADDITION TO APPLICABLE BUILDING
 CODES, LIFE SAFETY SHALL COMPLY WITH
 NFPA 101, 2003 EDITION.
  
 2) PLEASE MAKE CORRECTIONS REGARDING
 CODE EDITIONS ON PLANS.
  
 3) AN ADDRESS OF 530 HIBISCUS AND 700 S.
 ROSEMARY ARE SHOWN. PLEASE VERIFY
 CORRECT ADDRESS AND PROVIDE APPROPRIATE
 SUITE NUMBER IN APPROVED LOCATION.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-04-06 Cont ID  
Sent By mwennerg Date 2006-04-06 Time 13:33 Rev Time 0.00
Received By mwennerg Date 2006-04-06 Time 13:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-09-29 Cont ID  
Sent By adarroug Date 2006-09-29 Time 10:08 Rev Time 0.00
Received By adarroug Date 2006-09-29 Time 10:08 Sent To B
Notes
2006-09-29 00:00:00TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-18 Cont ID  
Sent By adarroug Date 2006-07-18 Time 15:04 Rev Time 0.00
Received By adarroug Date 2006-07-18 Time 15:04 Sent To  
Notes
2006-07-21 00:00:00TO "BOB"#3
2006-07-18 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-09 Cont ID  
Sent By adarroug Date 2006-06-09 Time 13:56 Rev Time 0.00
Received By adarroug Date 2006-06-09 Time 13:56 Sent To  
Notes
2006-06-14 00:00:00TO "BOB"#3
2006-06-09 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2006-04-11 Time   Rev Time 0.00
Received By adarroug Date 2006-03-30 Time 16:00 Sent To  
Notes
2006-03-30 00:00:00TO "BOB"#10-STOREFRONT SHEETS CHANGED
 OUT TO PUT ON "BOB"-OK PER "LMARTINEZ"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-04-11 Time   Rev Time 0.00
Received By adarroug Date 2006-03-15 Time 12:41 Sent To  
Notes
2006-03-15 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-07-21 Cont ID  
Sent By tgordon Date 2006-07-21 Time 14:03 Rev Time 0.30
Received By tgordon Date 2006-07-21 Time 14:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-06-23 Cont ID  
Sent By tgordon Date 2006-06-20 Time 16:04 Rev Time 0.30
Received By tgordon Date 2006-06-23 Time 08:01 Sent To  
Notes
2006-06-23 00:00:00*** DENIED ***
 1) SEE BUILDING REVIEW NOTE #1 AND
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-03-30 Cont ID  
Sent By tgordon Date 2006-03-30 Time 16:42 Rev Time 0.20
Received By tgordon Date 2006-03-30 Time 16:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-07-24 Cont ID  
Sent By jleech Date 2006-07-24 Time 09:59 Rev Time 0.00
Received By jleech Date 2006-07-24 Time 09:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-06-22 Cont ID  
Sent By jleech Date 2006-06-20 Time 08:29 Rev Time 0.00
Received By jleech Date 2006-06-22 Time 08:58 Sent To  
Notes
2006-06-22 00:00:00DENIED;
 THE PLANS ARE BEING REVIEWED UNDER THE
 FBC-2004 CODES NOT 2001. PLEASE CORRECT.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-04-04 Cont ID  
Sent By jleech Date 2006-04-04 Time 08:41 Rev Time 0.00
Received By jleech Date 2006-04-04 Time 08:41 Sent To  
Notes
***NONE***