| 2006-03-20 00:00:00 | *** DENIED *** |
| | 1) PLANS MAY NOT BE DONE IN PENCIL. |
| | |
| | 2) PLEASE SUBMIT TWO COPYS OF PLANS. |
| | ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA |
| | SHALL BEAR THE NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. PER |
| | FBC 104.2.1 . |
| | |
| | 3) PLEASE SHOW ON MECHANICAL PLANS AN |
| | EQUIPMENT LISTING WITH MANUFACTURE NAME, |
| | MODEL NUMBER, TONS, SEER, HEATER KW, |
| | TOTAL COOLING BTU'S; SENSIBLE COOLING |
| | BTU'S; AND COPPER LINE SIZES. |
| | |
| | 4) AS REQUESTED IN LAST REVIEW, PLEASE |
| | SIGN BOLTH COPYS OF ENERGY CAL'S. |
| | |
| | 5) PLEASE SHOW SIZE OF SUPPLY AIR DUCT |
| | (FLEX) FROM AHU TO TO THE MIXING BOX. |
| | |
| | 6) PLEASE SUPPLY RETURN AIR TO THE |
| | BEDROOMS, SEE NOTE #7. |
| | |
| | 7)BALANCED RETURN AIR. |
| | THIS MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | 8) PLEASE PROVIDE LIABILITY INSURANCE |
| | INFORMATION FOR EWING & EWING AIR COND. |
| | NOT EWING HEATING & AIR INC.. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |