Plan Review Details - Permit 06030544
Plan Review Stops For Permit 06030544
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-06-01 Cont ID  
Sent By mjacobs Date 2006-06-01 Time 14:01 Rev Time 0.00
Received By mjacobs Date 2006-05-25 Time 06:47 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-05-08 Cont ID  
Sent By mjacobs Date 2006-05-08 Time 18:53 Rev Time 0.00
Received By mjacobs Date 2006-05-08 Time 18:32 Sent To PC
Notes
2006-05-08 00:00:00 
 1) AS I MENTIONED IN PREVIOUS REVIEW,
 EACH SHEET WHICH IS BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE ORIGINAL
 SEAL/SINGATURE AND DATE BY THE PERSON
 RESPONSIBLE. THE REPORTS AND DRAWINGS
 FROM CATEGORY 5 NEEDS THE ORIGINAL SEAL
 AND SIGNATURE OF EMMA T. MELLINGER P.E.
 61G15-23.002 SEAL, SIGNATURE AND DATE
 SHALL BE AFFIXED.
 (1) A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME AND AFFIX HIS SEAL TO ALL
 PLANS, SPECIFICATIONS, REPORTS, FINAL
 BID DOCUMENTS PROVIDED TO THE OWNER OR
 THE OWNER?S REPRESENTATIVE, OR OTHER
 DOCUMENTS PREPARED OR ISSUED BY SAID
 REGISTRANT AND BEING FILED FOR PUBLIC
 RECORD. THE DATE THAT THE SIGNATURE AND
 SEAL IS AFFIXED AS PROVIDED HEREIN SHALL
 BE ENTERED ON SAID PLANS,
 SPECIFICATIONS, REPORTS, OR OTHER
 DOCUMENTS IMMEDIATELY UNDER THE
 SIGNATURE OF THE PROFESSIONAL ENGINEER.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-30 Cont ID  
Sent By mjacobs Date 2006-03-30 Time 18:49 Rev Time 0.00
Received By mjacobs Date 2006-03-30 Time 18:01 Sent To PC
Notes
2006-03-30 00:00:00 
 1) FBC (EXUSTUBG BUILDING) 501.2
 CONFORMANCE.
 AN EXISTING BUILDING OR PORTION THEREOF
 SHALL NOT BE ALTERED SUCH THAT THE
 BUILDING BECOMES LESS SAFE OR ENERGY
 EFFICIENT THAN ITS EXISTING CONDITION.
 IF IN THE ALTERATION THE CURRENT LEVEL
 OF SAFETY OR SANITATION IS TO BE
 REDUCED, THE PORTION ALTERED SHALL
 CONFORM TO THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2) EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471, F.S., SHALL BE SEALED,
 SIGNED AND DATED BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE.
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS, AND LICENSE NUMBER
 ON EACH SHEET. IF PRACTICING THROUGH A
 DULY AUTHORIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS, THE
 NAME, ADDRESS, AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK ON
 EACH SHEET CONTAINING THE PRINTED NAME,
 ADDRESS, AND LICENSE NUMBER OF THE
 ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE
 NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS WILL SATISFY THIS
 REQUIREMENT. ALSO, SEE FBC 106.1
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
 EMAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-24 Cont ID  
Sent By adarroug Date 2006-05-24 Time 18:19 Rev Time 0.00
Received By adarroug Date 2006-05-24 Time 18:18 Sent To B
Notes
2006-05-24 00:00:00TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-06 Cont ID  
Sent By adarroug Date 2006-05-06 Time 14:20 Rev Time 0.00
Received By adarroug Date 2006-05-06 Time 14:20 Sent To B
Notes
2006-05-06 00:00:00TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-24 Cont ID  
Sent By adarroug Date 2006-03-30 Time   Rev Time 0.00
Received By adarroug Date 2006-03-14 Time 10:19 Sent To  
Notes
2006-03-14 00:00:00TO "MISC" BOX#1