Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-03-21 Cont ID  
Sent By tgordon Date 2006-03-21 Time 11:56 Rev Time 0.30
Received By tgordon Date 2006-03-21 Time 11:56 Sent To  
Notes
2006-03-21 00:00:00*** PROVISO ***
 1)THE DWELLING WILL BE REQUIRED TO HAVE
 SMOKE ALARMS INSTALLED IF NOT ALREADY
 PRESENT, PER 2004 FBC/R 313.1.1, AND SEE
 2004 FEBC 303.1 LEVEL ONE ALTERATION
 INCLUDE REPLACEMENT OF EQUIPMENT.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-03-13 Cont ID  
Sent By tgordon Date 2006-03-13 Time 09:15 Rev Time 0.30
Received By tgordon Date 2006-03-13 Time 09:15 Sent To  
Notes
2006-03-13 00:00:00*** DENIED ***
 1) MECHANICAL PLANS HAVE TO MUCH
 ELECTRICAL PLAN ON THEM AND ARE
 DIFFICULT TO READ. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY. PER 2004 FBC 106.1.1 .
  
 2) MACHANICAL PLANS MUST ALSO HAVE ON
 THEM THE A/C EQUIPMENT LISTING WITH ALL
 THE PERTINENT INFORMATION, AND SHOW ALL
 DUCT (FLEX) SIZES.
  
 3) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT.
  
 4) PLEASE PROVIDE WITH TWO COPYS OF THE
 ENERGY CALCULATIONS A MANUAL J (LONG
 FORM) SHOWING CFM'S. TO EACH ROOM, PER
 2004 FBC 13-607.1.ABC.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.