Plan Review Details - Permit 06030473
Plan Review Stops For Permit 06030473
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-17 Cont ID  
Sent By shill Date 2006-07-17 Time 08:38 Rev Time 0.00
Received By shill Date 2006-07-17 Time 08:38 Sent To  
Notes
2006-07-17 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 FROM PREVIOUS LIST:
  
 _XX_ 9.ON THE ANCHORING SCHEDULE,
 YOU HAVE INDICATED THAT THIS APPLICATION
 IS POURED CONCRETE.AREN'T THERE FILLED
 CELLS AT SOME OF THE OPENINGS?
  
 THE ANCHORING OF 16" IS NOT CODE
 COMPLIANT FOR FILLED CELLS/HOLLOW BLOCK.
 YOU HAVE SPECIFIED 2.5IN EDGE DISTANCE,
 BUT THIS DIMENSION IS NOT ON THE
 ANCHORING SCHEDULE.
  
 _XX_10.)NOTE THAT THERE WAS ONLY ONE
 PRODUCT APPROVAL SUBMITTED, WHICH I
 BELIEVE IS DIFFERENT FROM THE ONE
 PREVIOUSLY SUBMITTED.THE RESUB SHEET
 STATES "ADDED PRODUCT APPROVALS" BUT YOU
 HAVE REPLACED THE PREVIOUS PRODUCT
 APPROVAL.THIS IS ACCEPTABLE; BUT TO
 AVOID DELAYS IN THE FIELD I AM
 CONFIRMING THAT THIS IS YOUR INTENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-04 Cont ID  
Sent By shill Date 2006-04-04 Time 10:10 Rev Time 0.00
Received By shill Date 2006-04-04 Time 10:10 Sent To  
Notes
2006-04-04 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED
 ITEMS APPLY
  
 ____1.A NOTICE OF COMMENCEMENT MUST
 BE FILED WITH THE CLERK OF COURTS BEFORE
 A PERMIT CAN BE ISSUED, FS713.13.
  
 ____2.PROVIDE BUILDING HEIGHT.
 DESIGN PRESSURES FOR BUILDINGS OVER
 60FEET ARE REQUIRED TO BE DESIGNED USING
 ASCE7, FBC1609.1.1. DOCUMENTS PREPARED
 BY AN ENGINEER AND SUBMITTED FOR PUBLIC
 RECORD ARE TO BE SIGNED SEALED ORIGINALS
 FAC61G15-23.002.
  
 ____3.PROVIDE A COPY OF THE CONDO
 ASSOCIATION APPROVAL.
  
 ____4.COMPLETE THE ATTACHED
 INSTALLATION SCHEDULE OR PROVIDE
 REQUIRED INFORMATION IN A SIMILAR
 FORMAT.YOU MAY SHOW ANCHOR SPACING BY
 CIRCLING IT ON THE APPROPRIATE CHARTS ON
 THE PRODUCT APPROVAL.
  
 _XX_5.FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72,
 WWW.FLORIDABUILDING.ORG.
  
 THE PRODUCT APPROVAL SUBMITTED IS
 EXPIRED, FBC2001 RATHER THAN FBC2004.
  
 _XX_6.ON THE PRODUCT APPROVAL, MARK
 WHICH DETAILS APPLY TO THIS JOB.PLEASE
 USE INK RATHER THAN A HIGHLIGHTER.
  
 ____7.SHOW THE EMERGENCY MEANS OF
 ESCAPE, FBC R310.
  
 ____8.PROVIDE A FLOOR PLAN SHOWING
 WHERE THE SHUTTERS WILL BE INSTALLED AND
 PANEL SIZES WHICH CORRELATES WITH THE
 INSTALLATION SCHEDULE, ITEM 4 ABOVE.
  
 _XX_ 9.ON THE ANCHORING SCHEDULE,
 YOU HAVE INDICATED THAT THIS APPLICATION
 IS POURED CONCRETE.AREN'T THERE FILLED
 CELLS AT SOME OF THE OPENINGS?
  
 _XX_ 10.IT IS NOT CLEAR HOW YOU HAVE
 ARRIVED AT THE DESIGN PRESSURES
 DECLARED.SEE TABLE FBC1609.6B, WHICH
 HAS THE LOWEST PRESSURE AS -33, BUT YOUR
 PAPERWORK SHOWS -28.435.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-14 Cont ID  
Sent By adarroug Date 2006-07-14 Time 17:46 Rev Time 0.00
Received By adarroug Date 2006-07-14 Time 17:46 Sent To B
Notes
2006-07-14 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-07 Cont ID  
Sent By adarroug Date 2006-06-07 Time 10:12 Rev Time 0.00
Received By adarroug Date 2006-06-07 Time 10:12 Sent To B
Notes
2006-06-07 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-04 Cont ID  
Sent By shill Date 2006-04-04 Time 10:22 Rev Time 0.00
Received By shill Date 2006-03-13 Time 16:02 Sent To  
Notes
2006-03-13 00:00:00TO "MISC" BOX#1