Plan Review Details - Permit 06030410
Plan Review Stops For Permit 06030410
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-04-04 Cont ID  
Sent By amorse Date 2006-04-04 Time 08:21 Rev Time 0.75
Received By amorse Date 2006-04-04 Time 08:21 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-10 Cont ID  
Sent By amorse Date 2006-03-10 Time 16:04 Rev Time 0.75
Received By amorse Date 2006-03-10 Time 16:04 Sent To PC
Notes
2006-03-10 00:00:00 
  
 DENIED
  
 1) AN ENGINEER PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS SHALL
 INDICATE THEIR NAME AND LICENCE #, AS
 WELL AS THE NAME,ADDRESS AND CERTIFICATE
 OF AUTHORIZATION #ON EACH SHEET PER
 61G15-23.002 (1)- (5)
  
 NOTE: CA# NOT ON SHEETS
  
 2) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT. THESE SHOULD INCLUDE THE
 FLORIDA STATE APPROVAL COVER PAGES, AND
 THE PRODUCT NOA THAT LISTS THE SYSTEM
 COMPONENTS/ FASTENER LIST PAGES, THE
 PAGES WITH THE CHOSEN ASSEMBLY/ SYSTEM
 TO BE USED AND THE GENERAL LIMITATIONS
 PAGE. ALL CAN BE FOUND ON
 WWW.FLORIDABUILDING.ORG
  
  
 3) THOSE PRODUCTS THAT ARE REGULATED BY
 DCA RULE 9B-72 REQUIRE FLORIDA PRODUCT
 APPROVAL OR PRODUCT(S) CAN BE SUBMITTED
 FOR LOCAL PRODUCT APPROVAL (SEE ATTACHED
 APPLICATION)
  
 4) INSTALLATION OF ROOF STANDS WOULD
 REQUIRE A GC LICENCE OR A/C CONTRACTORS
 LICENCE. IT IS NOT UNDER SCOPE OF WORK
 FOR ROOFING CONTRACTOR. ALSO ROOF STANDS
 ARE NOW INCLUDED UNDER RULE 9B-72 AND AS
 SUCH REQUIRE PRODUCT APPROVALS
  
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-03-10 Time   Rev Time 0.00
Received By adarroug Date 2006-03-10 Time 11:28 Sent To  
Notes
2006-03-10 00:00:00TO "AMORSE" DESK