Plan Review Details - Permit 06030394
Plan Review Stops For Permit 06030394
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-07-12 Cont ID  
Sent By mjacobs Date 2006-07-12 Time 11:39 Rev Time 0.00
Received By mjacobs Date 2006-07-12 Time 11:21 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-06-24 Cont ID  
Sent By mjacobs Date 2006-06-24 Time 06:53 Rev Time 0.00
Received By mjacobs Date 2006-06-24 Time 06:35 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-05-13 Cont ID  
Sent By mjacobs Date 2006-05-13 Time 09:36 Rev Time 0.00
Received By mjacobs Date 2006-05-13 Time 07:29 Sent To  
Notes
2006-05-13 00:00:001) MANEUVERING CLEARANCES AT DOORS.
 MINIMUM MANEUVERING CLEARANCES AT DOORS
 THAT ARE NOT AUTOMATIC OR POWER ASSISTED
 SHALL BE AS SHOWN IN FIGURE 11-25. THE
 MINIMUM CLEARANCE ON THE PULL SIDE SHALL
 BE 18". SEE NEW DOOR FOR MEN'S ROOM AND
 THE DOOR NEXT TO THE STAIRS.SHEET 2.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-01 Cont ID  
Sent By mjacobs Date 2006-04-01 Time 14:37 Rev Time 0.00
Received By mjacobs Date 2006-04-01 Time 13:22 Sent To PC
Notes
2006-04-01 00:00:001) (2004 FBC) 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND REVELENT
 LAWS, ORDINANCES, AND RULES AND
 REGULATIONS AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 2) PROVIDE A DRAWING OF THE EXISTING
 BATHROOMS AND DRAWINGS OF THE PROPOSED
 BATHROOMS.
  
 3) SHOW DETAIL DRAWINGS OF THE NEW RATED
 WALL AND NEW DOOR OPENINGS. ALSO HAVE A
 KEY SHOWING THE DIFFERENT WALLS,SUCH AS
 WHICH ONES TO BE REMOVED, WHAT IS NEW
 AND WHAT STAYS.
  
 4) NOTE: ON THE PULL SIDE OF DOORS A
 18"MIN IS REQUIREED.SEE MANEUVERING
 CLEARANCE AT DOORS FBC CH:11
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2006-07-12 Cont ID  
Sent By btrobaug Date 2006-07-12 Time 09:50 Rev Time 0.33
Received By btrobaug Date 2006-07-12 Time 09:46 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-06-21 Cont ID  
Sent By btrobaug Date 2006-06-21 Time 14:51 Rev Time 0.50
Received By btrobaug Date 2006-06-21 Time 13:42 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-05-16 Cont ID  
Sent By btrobaug Date 2006-05-16 Time 17:28 Rev Time 0.50
Received By btrobaug Date 2006-05-16 Time 16:37 Sent To  
Notes
2006-05-16 00:00:00 
  
 THE COMMENTS FROM THE PRIOR REVIEW WHERE
 NOT ADDRESSED. PLEASE SEE THAT THE
 ENGINEER OF RECORD SEE THE ATTACHED
 FLORIDA STATE STATUTE, THE FINE IS
 LEVIED ON THE PERSON RESPONSIBLE FOR THE
 PLAN.
  
  
 PLEASE INDICATE THE CIRCUIT NUMBER FOR
 THE LIGHTING . SHOW COMPLIANCE WITH
 700.12(E) FOR EMERGENCY LIGHTING.
  
 SHOW THE REQUIRED EXIT AND EMERGENCY
 LIGHT LOCATIONS.
  
 AN ELECTRICAL PERMIT IS REQUIRED FOR THE
 SCOPE OF THIS PROJECT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-13 Cont ID  
Sent By btrobaug Date 2006-03-13 Time 10:25 Rev Time 0.50
Received By btrobaug Date 2006-03-13 Time 10:21 Sent To  
Notes
2006-03-13 00:00:00 
 PLEASE INDICATE THE CIRCUIT NUMBER FOR
 THE LIGHTING . SHOW COMPLIANCE WITH
 700.12(E) FOR EMERGENCY LIGHTING.
  
 SHOW THE REQUIRED EXIT AND EMERGENCY
 LIGHT LOCATIONS.
  
 AN ELECTRICAL PERMIT IS REQUIRED FOR THE
 SCOPE OF THIS PROJECT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-06-22 Cont ID  
Sent By mwennerg Date 2006-06-22 Time 10:45 Rev Time 0.00
Received By mwennerg Date 2006-06-22 Time 10:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-05-17 Cont ID  
Sent By mwennerg Date 2006-05-17 Time 10:49 Rev Time 0.00
Received By mwennerg Date 2006-05-17 Time 10:49 Sent To  
Notes
2006-05-17 00:00:00***DENIED***
  
 1) PLEASE SEE ELECTRICAL REVIEW COMMENT
 IN REGARDS TO EXIT LIGHT/EMERGENCY LIGHT
 REQUIREMENTS THAT HAVE NOT BEEN
 ADDRESSED.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-03-21 Cont ID  
Sent By mwennerg Date 2006-03-21 Time 09:03 Rev Time 0.00
Received By mwennerg Date 2006-03-21 Time 09:03 Sent To  
Notes
2006-03-21 00:00:00******PROVISO******
  
 PLEASE SEE ELECTRICAL COMMENTS #1&2.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-07 Cont ID  
Sent By adarroug Date 2006-07-07 Time 10:45 Rev Time 0.00
Received By adarroug Date 2006-07-07 Time 10:45 Sent To P
Notes
2006-07-07 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-14 Cont ID  
Sent By adarroug Date 2006-06-14 Time 14:31 Rev Time 0.00
Received By adarroug Date 2006-06-14 Time 14:31 Sent To  
Notes
2006-06-21 00:00:00TO "BOB"#11
2006-06-14 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-08 Cont ID  
Sent By adarroug Date 2006-05-08 Time 16:05 Rev Time 0.00
Received By adarroug Date 2006-05-08 Time 16:05 Sent To  
Notes
2006-05-10 00:00:00TO "BOB"#17
2006-05-08 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-04-01 Time   Rev Time 0.00
Received By adarroug Date 2006-03-10 Time 11:23 Sent To  
Notes
2006-03-10 00:00:00TO "BOB"#14

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-06-01 Cont ID  
Sent By tgordon Date 2006-06-01 Time 08:59 Rev Time 0.15
Received By tgordon Date 2006-06-01 Time 08:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-07-12 Cont ID  
Sent By jleech Date 2006-07-12 Time 11:44 Rev Time 0.00
Received By jleech Date 2006-07-12 Time 11:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-06-21 Cont ID  
Sent By btrobaug Date 2006-06-21 Time 14:51 Rev Time 0.00
Received By jleech Date 2006-06-21 Time 15:14 Sent To  
Notes
2006-06-21 00:00:00DENIED;
 1. ONE SERVICE SINK AND ONE DRINKING
 FOUNTAIN IS REQUIRED TO MEET MINIMUM
 PLUMBING FIXTURES REQUIRED PER TABLE
 403.1.
 2.ONE URINAL MUST BE HANDICAP HIGHTH,
 PLEASE ADD NOTE TO PLAN. SEC.
 11-4.,18.2.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-03-16 Cont ID  
Sent By jleech Date 2006-03-16 Time 14:03 Rev Time 1.50
Received By jleech Date 2006-03-16 Time 14:03 Sent To  
Notes
2006-03-16 00:00:00DENIED;
 1.NOT ENOUGH INFORMATION TO DO A
 PLUMBING PLAN REVIEW;
 A.TYPE OF OCCUPANCY.
 B.MAX. NUMBER OF PEOPLE.
 C.SHOW COMPLIANCE WITH FBC-2004
 TABLE 403.1 MIN. FIXTURES
 D.WHAT DID BATHROOMS LOOK LIKE
 BEFORE CHANGE?
 2.NEW TOILET STALL IN WOMANS ROOM DOES
 NOT MEET HANDICAP CODES. IF ADDITIONAL
 HANDICAP FACILIIES ARE NEEDED HAVE A
 TOILET STALL ONLY. A LAV IS NOT REQUIRED
 FOR A SECOND H/C STALL. CLEAR FLOOR
 SPACE DOESNOT EXIST.
 3.ONE URINAL IN MEN'S ROOM MUST COMPLY
 WITH FBC-2004 CHAPTEWR 11 SEC.
 11-4.18.2,.3 AND.4.
 4. NO TURNING RADIUS EXISTS IN WOMENS
 ROOM. ( SEE HIGHLIGHTED CIRCLE ON ONE
 SET OF PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  