| Plan Review Stops For Permit 06030376 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
P |
Date |
2008-02-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-02-19 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-02-19 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2008-02-19 16:30:18 | PROVISO - SUBMIT DETAIL 4/S222 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
F |
Date |
2008-02-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-02-04 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-02-04 |
Time |
09:34 |
Sent To |
|
|
| Notes |
| 2008-02-04 09:45:42 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.SHEET 4 S222 IS TO INCLUDE ALL INFORMATION REQUIRED | | | BY FAC61G15-23.002. | | | | | | 2.PLEASE INCORPORATE THE REVISION INTO THE PLAN | | | SHEET(S) WHICH IT REPLACES.DOESN'T THIS AFFECT MORE | | | THAN THE FOUNDATION PLAN, SUCH AS THE ELEVATIONS?THE | | | OLD SHEETS IN OUR RECORD SET WILL BE VOIDED, REPLACED | | | WITH THE NEW SHEETS. | | | | | | 3.THE SKETCH IS NOT REFERENCED ON THE PLAN PROVIDED. | | | DOES THIS DETAIL REPLACE ANOTHER DETAIL OR IS IT | | | SUPPLEMENTARY?WHERE WILL THE 2'X6" REINFORCED | | | CONCRETE BE INSTALLED, AND FOR WHAT LENGTH?PLEASE | | | REVISE THE PLAN TO MAKE USE OF THIS DETAIL CLEAR. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2008-01-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-01-17 |
Time |
12:03 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-01-17 |
Time |
12:03 |
Sent To |
|
|
| Notes |
| 2008-01-17 12:04:21 | RESTAMP OF TRUSS ENGINEERING, PARTIAL (REMOVED NON | | | COMPLIANT SHEETS, SPOKE WITH CONTRACTOR AND ENGINEER) |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2007-12-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-12-28 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-12-28 |
Time |
09:26 |
Sent To |
|
|
| Notes |
| 2007-12-28 09:26:52 | RESTAMP OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2007-01-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-01-29 |
Time |
18:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-01-29 |
Time |
18:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2007-01-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-01-23 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-01-23 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2007-01-23 14:03:08 | REVISION |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2006-11-16 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-11-16 |
Time |
10:00 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-11-16 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2006-11-16 10:00:42 | DENIED | | | | | | 1. PLEASE SIGN AND SEAL BOTH SETS OF PLANS | | | SUBMITTED. | | | | | | 2.SKYLIGHTS SHOWN ON UN SIGNED ELECTRICAL PAGE. | | | | | | 3.SUBMIT TWO COMPLETE SETS OF PRODUCT APPROVALS. | | | | | | 4.ACORDING TO ICC BUILDING VALUATION DATA THE PERMIT | | | VALUATION HAS BEEN REVISED TO $34,375.ADDITION PERMIT | | | FEES ARE DUE. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | CONSTRUCTION SERVICES DEPARTMENT | | | 561-805-6672 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2006-08-25 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-08-25 |
Time |
14:14 |
Rev Time |
1.50 |
| Received By |
alange |
Date |
2006-08-25 |
Time |
11:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-04-07 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-04-07 |
Time |
08:33 |
Rev Time |
2.00 |
| Received By |
alange |
Date |
2006-04-07 |
Time |
08:28 |
Sent To |
|
|
| Notes |
| 2006-04-07 00:00:00 | DENIED | | | | | | | | | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT | | | SHALL BE RECORDED AT PALM BEACH COUNTY | | | COURTHOUSE AND A COPY SUBMITTED TO THIS | | | OFFICE BEFORE A PERMIT CAN BE ISSUED. | | | BLANK FORMS ARE AVAILABLE FROM THIS | | | OFFICE. | | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE | | | RE-RECORDED IF THE DESCRIBED IMPROVEMENT | | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | | 90 DAYS OF RECORDING. | | | | | | 2.MINIMUM FOOTING DEPTH BELOW GRADE IS | | | 12" R403.1.4 | | | | | | 3.BASED ON ICC BUILDING VALUATION DATA | | | THE PERMIT VALUE HAS BEEN REVISED TO | | | $25,594.ADDITIONAL PERMIT FEES ARE | | | DUE. | | | | | | 4. THERMATRUE DOOR MISSING STATE PRODUCT | | | APPROVAL. | | | ALL PRODUCT APPROVALS SUBMITTED WITH | | | QUALITY ASSURANCE SHALL HAVE THE | | | FOLLOWING STATE APPROVAL ATTACHED. | | | | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A STATE PRODUCT APPROVAL | | | SHEETS THAT LISTS THE PRODUCT IDENTITY | | | NUMBER FROM THE STATE. IF THE PRODUCT | | | DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT | | | AN APPLICATION FOR LOCAL PRODUCT | | | APPROVAL OR SITE SPECIFIC FORM PER RULE | | | 9B-72. SEE ATTACHMENT. | | | WWW.FLORIDABUILDING.ORG | | | | | | 5.THOSE PRODUCT APPROVALS WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL.WPB | | | AMENDMENT TO FBC 106.3.3. | | | | | | 6.SUBMIT TWO SETS OF TRUSS DRAWINGS | | | FOR REVIEW PER 2004 FBC R-802.10.1 | | | | | | 7.A DESIGN PROFESSIONAL OR AN OWNER | | | MUST ELECT ONE OR A COMBINATION OF | | | LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 303, 304 AND 305 OF THIS CODE. | | | SHOW HOW PLANS WILL COMPLY WITH THE | | | SECTION(S) SELECTED.2004 FBC EXISTING | | | BUILDING 301.5 | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. SUBMIT ONE COPY OF | | | OLD PAGES FOR REFERENCE. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET | | | OR SPECIFICATION PAGE WHERE THE CHANGES | | | CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | ART LANGE | | | CONSTRUCTION SERVICES DEPARTMENT | | | BUILDING PLANS EXAMINER | | | 561-805-6672 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-02-14 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-02-14 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-02-14 |
Time |
15:56 |
Sent To |
B |
|
| Notes |
| 2008-02-14 15:57:13 | | | | | | | REVISION AND FILE SET TO SAMANTHA, MET WITH CONTRACTOR | | | WHO WANTED BUILDING REVIEW ONLY FOR CHANGING GARAGE | | | DOOR FROM DOUBLE TO SINGLE./WRT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2006-08-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-08-24 |
Time |
11:40 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-08-24 |
Time |
11:15 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-03-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-03-24 |
Time |
11:26 |
Rev Time |
0.33 |
| Received By |
btrobaug |
Date |
2006-03-24 |
Time |
11:16 |
Sent To |
P |
|
| Notes |
| 2006-03-24 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 250.32 TWO OR MORE BUILDINGS OR | | | STRUCTURES SUPPLIED FROM A COMMON | | | SERVICE. | | | (A) GROUNDING ELECTRODE. WHERE TWO OR | | | MORE BUILDINGS OR STRUCTURES ARE | | | SUPPLIED FROM A COMMON AC SERVICE BY A | | | FEEDER(S) OR BRANCH CIRCUIT(S), THE | | | GROUNDING ELECTRODE(S) REQUIRED IN PART | | | III OF THIS ARTICLE AT EACH BUILDING OR | | | STRUCTURE SHALL BE CONNECTED IN THE | | | MANNER SPECIFIED IN 250.32(B) OR (C). | | | WHERE THERE ARE NO EXISTING GROUNDING | | | ELECTRODES, THE GROUNDING ELECTRODE(S) | | | REQUIRED IN PART III OF THIS ARTICLE | | | SHALL BE INSTALLED. | | | | | | PLEASE INDICATE ON THE RISER . | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2008-02-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-07 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-07 |
Time |
16:37 |
Sent To |
E |
|
| Notes |
| 2008-02-07 16:38:01 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2008-01-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-29 |
Time |
16:18 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-29 |
Time |
16:18 |
Sent To |
B |
|
| Notes |
| 2008-01-29 16:18:37 | TO "SHILL" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2008-01-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-15 |
Time |
08:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-15 |
Time |
08:27 |
Sent To |
B |
|
| Notes |
| 2008-01-15 08:27:57 | TO "SHILL" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2007-12-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-12-18 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-12-18 |
Time |
09:47 |
Sent To |
B |
|
| Notes |
| 2007-12-18 09:48:17 | TO "SHILL" DESK/RESTAMP |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-12-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-01 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-01 |
Time |
11:40 |
Sent To |
B |
|
| Notes |
| 2006-12-01 11:41:24 | TO "LMARTINEZ" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-11-01 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-11-16 |
Time |
10:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-01 |
Time |
11:27 |
Sent To |
B |
|
| Notes |
| 2006-11-01 11:27:53 | TO "ALANGE" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-08-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-22 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-22 |
Time |
13:29 |
Sent To |
E |
|
| Notes |
| 2006-08-22 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-08-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-12 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-12 |
Time |
16:36 |
Sent To |
Z |
|
| Notes |
| 2006-08-12 00:00:00 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-03-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-03-23 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-03-23 |
Time |
16:33 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-04-07 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-04-07 |
Time |
08:34 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-03-10 |
Time |
10:14 |
Sent To |
|
|
| Notes |
| 2006-03-10 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2006-03-24 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-03-24 |
Time |
14:58 |
Rev Time |
0.15 |
| Received By |
tgordon |
Date |
2006-03-24 |
Time |
14:58 |
Sent To |
B |
|
| Notes |
| 2006-03-24 00:00:00 | *** NOTE *** | | | 1) A MECHANICAL PERMIT WILL BE REQUIRED | | | DUE TO BATHROOM EXHAUST FAN AND DRYER | | | VENT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2006-03-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-02-15 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-03-24 |
Time |
14:13 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2006-08-19 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-08-19 |
Time |
06:17 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-08-19 |
Time |
06:17 |
Sent To |
I |
|
| Notes |
| 2006-08-19 00:00:00 | APPROVED BY ZBA BOARD, VARIANCE CASE | | | #3161 FOR A DETACHED GARAGE 6FT |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-11-16 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-03-22 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-03-22 |
Time |
15:17 |
Sent To |
I |
|
| Notes |
| 2006-03-22 00:00:00 | DENIED, | | | 1. THE PROPOSED GARAGE MUST SIT BACK | | | 25FT FROM FRONT SETBACK. (FLAGLER ST) | | | 2. THE PROPOSED GARAGE MUST BE 12.5 FT | | | FROM SIDE SETBACK. ( POINSETTIA AVE). | | | 3. THE PROPOSED GARAGE MUST BE A MINIMUM | | | OF 6FT FROM THE MAIN STRUCTURE. | | | 4. THE SITEPLAN DOES NOT IDENTIFY THE | | | LOCATION OF THE PROPOSED WORK. | | | 5. THE SITPLAN DOES NOT SHOW THE | | | DIEMNSION OF LOT AND SETBACKS OF THE | | | EXISTING STRUCTURE. | | | 6. PLEASE SHOW THE PROPOSED GARAGE ON | | | THE TWO COPY OF SURVEY (THAT WAS | | | SUBMITTED), SHOWING THE SETBACK SIDE & | | | FRONT SETBACK AND DISTANCE FROM THE MAIN | | | STRUCTURE. | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|