Plan Review Details - Permit 06030342
Plan Review Stops For Permit 06030342
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-08-11 Cont ID  
Sent By amorse Date 2006-08-11 Time 08:21 Rev Time 0.00
Received By amorse Date 2006-08-11 Time 08:21 Sent To PC
Notes
2006-08-11 00:00:00 
  
 **************RESTAMP**************
  
 LOST ORIGINAL PLANS HAS PERMIT CARD

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-08-11 Cont ID  
Sent By amorse Date 2006-08-09 Time 08:19 Rev Time 0.00
Received By amorse Date 2006-08-09 Time 08:19 Sent To P
Notes
2006-08-11 00:00:00 
  
 **************REVISION************

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-05-02 Cont ID  
Sent By amorse Date 2006-05-02 Time 16:29 Rev Time 1.00
Received By amorse Date 2006-05-02 Time 16:29 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-06 Cont ID  
Sent By amorse Date 2006-04-06 Time 11:11 Rev Time 2.00
Received By amorse Date 2006-04-06 Time 11:11 Sent To PC
Notes
2006-04-06 00:00:00 
  
 DENIED
  
 1) COMPLETE SUBMITAL OF PRODUCT
 APPROVALS, PAGES MISSING
  
 2) BUCK ATTACHMENT DETAIL OR NOTE
 REQUIRED
  
 3) STRUCTURAL REQUIREMENTS SHALL INCLUDE
 A WALL SECTION FROM FOUNDATION THROUGH
 ROOF, INCLUDING ASSEMBLY AND MATERIALS,
 CONNECTOR TABLES, WIND REQUIREMENTS, AND
 STRUCTURAL CALCULATIONS PER 106.3.5.4
 (6) FBC*
  
 NOTE: SUBMIT WALL SECTION THAT IDENTIFYS
 TIE BEAM SPEC'S, RAFTER OR TRUSS TIE
 DOWN, FOUNDATION TYPE AND SPEC'S, WINDOW
 SILL SPEC'S, ETC (SEE ATTACHED DRAWING)
  
 4) CLARIFY INFORMATION ON DRAWINGS (SEE
 COMMENTS)
  
 5) CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE
 LOCATION,NATURE, AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 PER 106.1.1 FBC*
  
 NOTE: SEPARATE AND LABEL DRAWINGS EG.
 MAIN BATHROOM ADDITION, BEDROOM #3
 REMODEL ALSO EACH DRAWING SHALL HAVE THE
 PRINTED NAME,ADDRESS AND PHONE# OF THE
 PERSON RESPONSIBLE FOR THE DRAWINGS.
 THEY SHALL ALSO CARRY THE SIGNATURE WITH
 DATE
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2006-03-24 Cont ID  
Sent By btrobaug Date 2006-03-24 Time 10:33 Rev Time 0.33
Received By btrobaug Date 2006-03-24 Time 10:07 Sent To M
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2006-03-09 Cont ID  
Sent By swurafti Date 2006-03-09 Time 08:40 Rev Time 0.00
Received By swurafti Date 2006-03-09 Time 08:40 Sent To  
Notes
2006-03-09 00:00:00HISTORIC APPROVED COULDN'T MAKE OUT
 SIGNATURE

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-10 Cont ID  
Sent By adarroug Date 2006-08-10 Time 16:13 Rev Time 0.00
Received By adarroug Date 2006-08-10 Time 16:13 Sent To B
Notes
2006-08-10 00:00:00TO "AMORSE" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-09 Cont ID  
Sent By adarroug Date 2006-08-09 Time 10:26 Rev Time 0.00
Received By adarroug Date 2006-08-09 Time 10:26 Sent To B
Notes
2006-08-09 00:00:00TO "AMORSE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-01 Cont ID  
Sent By adarroug Date 2006-05-01 Time 10:54 Rev Time 0.00
Received By adarroug Date 2006-05-01 Time 10:54 Sent To P
Notes
2006-05-01 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-23 Cont ID  
Sent By dpalmer Date 2006-03-23 Time 16:33 Rev Time 0.00
Received By dpalmer Date 2006-03-23 Time 16:33 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-04-06 Time   Rev Time 0.00
Received By adarroug Date 2006-03-09 Time 18:33 Sent To  
Notes
2006-03-09 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-03-24 Cont ID  
Sent By tgordon Date 2006-03-24 Time 16:16 Rev Time 0.15
Received By tgordon Date 2006-03-24 Time 16:16 Sent To P
Notes
2006-03-24 00:00:00NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-05-02 Cont ID  
Sent By mperson Date 2006-05-02 Time 14:35 Rev Time 0.00
Received By mperson Date 2006-05-02 Time 14:35 Sent To B
Notes
2006-05-02 00:00:00NOTE: JACUZZI BATH REFERENCE PERMIT
 #06010896

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-05-01 Cont ID  
Sent By mperson Date 2006-05-01 Time 13:37 Rev Time 0.33
Received By mperson Date 2006-05-01 Time 13:37 Sent To B
Notes
2006-05-01 00:00:00******DENIED 2ND TIME******
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1,
 ADMINISTRATION
  
 THE FOLLOWING INFORMATION IS STILL
 REQUIRED FOR PLAN REVIEW FOR A PLUMBING
 PERMIT:
  
 1.PER AMENDMENTS TO FBC-2004 CHAPTER 1,
 ADMINISTRATION, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO FAMILY)
 PLUMBING: A SANITARY ISOMETRIC RISER
 DIAGRAM IS STILL REQUIRED INDICATING ALL
 WASTE, VENTS, AND TRAPS WITH SIZES.
 2. SHEET 2 OF 6 DEMO FLOOR PLAN: THE
 EXISTING WATER CLOSET (WC) NEEDS TO BE
 INDICATED ON THE DRAWING IN THE SHOWER
 BATHROOM.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-03-31 Cont ID  
Sent By mperson Date 2006-03-31 Time 11:35 Rev Time 1.00
Received By mperson Date 2006-03-31 Time 11:35 Sent To B
Notes
2006-03-31 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING, AND CITY
 OF WEST PALM BEACH, AMENDMENTS TO
 FBC-2004, CHAPTER 1, ADMINISTRATION:
  
 PLEASE ADJUST YOUR DRAWINGS TO REFLECT
 THE FOLLOWING INFORMATION REQUIRED FOR
 PLAN REVIEW:
  
 1. NOTE: PER CITY OF WEST PALM BEACH
 AMENDMENTS TO FBC-2004, CHAPTER 1,
 SECTION 106.3.5.4.
 RESIDENTIAL (ONE-AND-TWO-FAMILY)
 PLUMBING SANITARY RISER DIAGRAM REQUIRED
 2. NOTE: PER SECTION 421 WHIRLPOOL BATH-
 TUBS.
 421.2 INSTALLATION: "THE PUMMP SHALL BE
 LOCATED ABOVE THE WIER OF THE TRAP.
 ACCESS SHALL BE PROVIDED TO THE PUMP."
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 3 Status P Date 2006-05-02 Cont ID  
Sent By mmclean Date 2006-05-02 Time 16:42 Rev Time 0.00
Received By mmclean Date 2006-05-02 Time 16:42 Sent To B
Notes
2006-05-02 00:00:00REMOVAL OF GARAGE DOOR & ADDITION
 (MASTER BATH) ON THE SIDE.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-04-03 Cont ID  
Sent By mmclean Date 2006-04-03 Time 11:13 Rev Time 0.00
Received By mmclean Date 2006-04-03 Time 11:12 Sent To B
Notes
2006-04-03 00:00:00REMOVAL OF GARAGE DOOR & ADDITION
 (MASTER BATH) ON THE SIDE.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-03-22 Cont ID  
Sent By mmclean Date 2006-03-22 Time 16:54 Rev Time 0.00
Received By mmclean Date 2006-03-22 Time 16:54 Sent To I
Notes
2006-03-22 00:00:00DENIED,
 1. THE SURVEY & SITEPLAN PLAN DOES NOT
 MATCH. PACKET HAS 2 SETS OF DIFFERENT
 SITEPLAN.
 2. MUST PROVIDE (2) COPY OF CURRENT
 SURVEY SHOWING ALL WORK THAT WAS
 APPROVED FOR PROPERTY & THEN SHOW THE
 PROPOSED WORK.
 3. THE PROPOSED WORK MUST SHOW THE
 SETBACK FROM STRUCTURE TO PROPERTY LINE.
 4. PLEASE IDENTIFY THE GARAGE DOOR TO BE
 REMOVED ON TWO CURRENT SURVEY.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720