Plan Review Details - Permit 06030341
Plan Review Stops For Permit 06030341
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-07-20 Cont ID  
Sent By mjacobs Date 2006-07-20 Time 16:42 Rev Time 0.00
Received By mjacobs Date 2006-07-19 Time 16:24 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-06-24 Cont ID  
Sent By mjacobs Date 2006-06-24 Time 10:41 Rev Time 0.00
Received By mjacobs Date 2006-06-24 Time 08:45 Sent To  
Notes
2006-06-24 00:00:00PLANS ON MJ DESK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-05-15 Cont ID  
Sent By mjacobs Date 2006-05-15 Time 18:19 Rev Time 0.00
Received By mjacobs Date 2006-05-15 Time 13:34 Sent To PC
Notes
2006-05-15 00:00:001) SUBMIT AN EXISTING FLOOR PLAN OF THE
 BUILDING TO SHOW ALL NEW CHANGES OF THE
 PROPOSED LAY-OUT.
  
 2) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 3) SHEET D-1 #1. A PORTION OF THE MAIN
 COUNTER WHICH IS A MINIMUM OF 36" IN
 LINGTH SHALL BE PROVIDED WITH A MAXIMUM
 HEIGHT OF 36". OR AN AUXILIARY COUNTER
 WITH A MAXIMUM HEIGHT OF 36" IN CLOSE
 PROXIMITY TO THE MAIN COUNTER SHALL BE
 PROVIDED: 11-7 (I)(II). THE DIMENTIONS
 GIVEN WILL HAVE A COUNTER HEIGHT OF
 37"AFF.
  
 4) SHEET D-2 MENTION SEE DETAIL 5/D2,
 HOWEVEER,THERE IS NO #5 DETAIL ON SHEET
 D-2. A DETAIL DRAWING FOR EACH WALL IS
 REQUIRED INDICATING TOP AND BOTTOM
 ATTATCHMENT AND ALL MATERIALS. ALSO
 INDICATE THE STUD SPACING OF EACH WALL.
 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE
 NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT THE WORK WILL
 MEET 2004 FBC. AND RELEVENT LAWS.
 FBC.SEC.106.1.1
  
 5) A SEPERATE PERMIT IS REQUIRED FOR THE
 NEW DOORS AND WINDOWS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-05 Cont ID  
Sent By mjacobs Date 2006-04-05 Time 18:02 Rev Time 0.00
Received By mjacobs Date 2006-04-05 Time 14:40 Sent To PC
Notes
2006-04-05 00:00:001) IF THE DESIGN PROFESSIONAL IS AN
 ARCHITECT OR ENGINEER LEGALLY REGISTERED
 UNDER THE LAWS OF THIS STATE REGULATING
 THE PRACTICE OF ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES,
 PART I, OR ENGINEERING AS PROVIDED FOR
 IN CHAPTER 471, FLORIDA STATUTES, THEN
 HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO
 SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY
 FLORIDA STATUTE. IF THE DESIGN
 PROFESSIONAL IS A LANDSCAPE ARCHITECT
 REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF LANDSCAPE
 ARCHITECTURE AS PROVIDED FOR IN CHAPTER
 481, FLORIDA STATUTES, PART II, THEN HE
 OR SHE SHALL AFFIX HIS OR HER SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA AS
 DEFINED IN SECTION
 481.303(6)(A)(B)(C)(D), FS.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) SHOW THE FRONT ELEVATION OF THE FRONT
 DESK TO MEET THE REQUIRMENTS OF FBC SEC.
 11-7.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-11-21 Cont ID  
Sent By btrobaug Date 2006-11-21 Time 11:12 Rev Time 0.50
Received By btrobaug Date 2006-11-21 Time 11:01 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-05-16 Cont ID  
Sent By btrobaug Date 2006-05-16 Time 16:36 Rev Time 1.00
Received By btrobaug Date 2006-05-16 Time 15:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-30 Cont ID  
Sent By btrobaug Date 2006-03-30 Time 12:10 Rev Time 1.00
Received By btrobaug Date 2006-03-30 Time 09:59 Sent To  
Notes
2006-03-30 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 THE PLANS MUST BE DRAWN BY A DESIGN
 PROFESSIONAL PER 481 FS AND SIGNED AND
 SEALED PER 481 FS.
  
 1} PROVIDE A PANEL SCHEDULE OR SCHEDULES
 INDICATING ALL CIRCUITS IN THE AREA OF
 WORK AND RATINGS OF PANELS.
  
 2} SUBMIT A LOAD CALCULATION PER 106 FBC
 AND 215.5 NEC.
  
 3} INDICATE CIRCUIT NUMBERS AT ALL
 LIGHTS AND DEVICES THAT BRANCH CIRCUIT
 AND ARTICLE 700.
  
 4} INDICATE LOCATIONS OF ALL EXIT AND
 EMERGENCY LIGHTING.
  
 5} LABEL REQUIRED GFI RECEPTACLES PER
 210.8 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-05-17 Cont ID  
Sent By mwennerg Date 2006-05-17 Time 10:30 Rev Time 0.00
Received By mwennerg Date 2006-05-17 Time 10:30 Sent To  
Notes
2006-05-17 00:00:00***APPROVED***
  
 SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS REMODEL IF APPLICABLE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-04-03 Cont ID  
Sent By nmccray Date 2006-04-03 Time 14:13 Rev Time 0.00
Received By nmccray Date 2006-04-03 Time 13:56 Sent To  
Notes
2006-04-03 00:00:00**********DENIED:**************
  
 1) CONSTRUCTION, RENOVATION, AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
 2) LIFE SAFETY SHALL BE IN COMPLIANCE
 WITH NFPA 101 LIFE SAFETY CODE, 2003
 EDITION.
  
 3) PLEASE INDICATE THE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS.
  
 4) PLEASE SHOW ALL EXIT SIGNS AND
 EMERGENCY LIGHTING ON THE PLAN.
  
 5) SEPARATE SHOP DRAWINGS ARE REQUIRED
 FOR FIRE SPRINKLER AND OR FIRE ALARM
 SYSTEMS REMODEL.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-11-08 Cont ID  
Sent By adarroug Date 2006-11-08 Time 15:56 Rev Time 0.00
Received By adarroug Date 2006-11-08 Time 15:56 Sent To I
Notes
2006-11-17 11:26:00TO "BOB"#1
2006-11-08 15:59:37WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-10-10 Cont ID  
Sent By adarroug Date 2006-10-10 Time 10:40 Rev Time 0.00
Received By adarroug Date 2006-10-10 Time 10:40 Sent To P
Notes
2006-10-10 10:40:51TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-13 Cont ID  
Sent By adarroug Date 2006-07-13 Time 13:44 Rev Time 0.00
Received By adarroug Date 2006-07-13 Time 13:44 Sent To B
Notes
2006-07-18 00:00:00TO "BOB"#15
2006-07-13 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-12 Cont ID  
Sent By adarroug Date 2006-06-12 Time 13:15 Rev Time 0.00
Received By adarroug Date 2006-06-12 Time 13:15 Sent To  
Notes
2006-06-14 00:00:00TO "BOB"#1
2006-06-12 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-08 Cont ID  
Sent By adarroug Date 2006-05-08 Time 09:26 Rev Time 0.00
Received By adarroug Date 2006-05-08 Time 09:26 Sent To  
Notes
2006-05-10 00:00:00TO "BOB"#9
2006-05-08 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-04-05 Time   Rev Time 0.00
Received By adarroug Date 2006-03-09 Time 14:32 Sent To  
Notes
2006-03-30 00:00:00TO "BOB"#1
2006-03-09 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-02-13 Cont ID  
Sent By hmoser Date 2007-02-13 Time 14:30 Rev Time 0.00
Received By hmoser Date 2007-02-13 Time 14:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-06-20 Cont ID  
Sent By tgordon Date 2006-06-20 Time 16:38 Rev Time 0.25
Received By tgordon Date 2006-06-20 Time 16:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-05-30 Cont ID  
Sent By tgordon Date 2006-05-30 Time 15:49 Rev Time 0.30
Received By tgordon Date 2006-05-30 Time 15:49 Sent To  
Notes
2006-05-30 00:00:00*** DENIED ***
 1) RETURN AIR TRANSFER DUCT TO
 CONSULTATION ROOM IS TO SMALL, SEE NOTE
 #3.
  
 2) PLEASE SHOW ON MECHANICAL PLANS HOW
 OUTSIDE AIR WILL BE GETTING TO AHU.
  
 3)BALANCED RETURN AIR.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE. PER 2004
 FBC/M 601.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-03-30 Cont ID  
Sent By tgordon Date 2006-03-30 Time 14:04 Rev Time 0.20
Received By tgordon Date 2006-03-30 Time 14:04 Sent To  
Notes
2006-03-30 00:00:00NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop MEDGAS MEDICAL GAS
Rev No 6 Status P Date 2006-11-18 Cont ID  
Sent By jleech Date 2006-11-18 Time 14:06 Rev Time 0.00
Received By jleech Date 2006-11-18 Time 14:06 Sent To  
Notes
***NONE***

Review Stop MEDGAS MEDICAL GAS
Rev No 5 Status F Date 2006-10-21 Cont ID  
Sent By jleech Date 2006-10-21 Time 10:24 Rev Time 0.00
Received By jleech Date 2006-10-21 Time 10:24 Sent To  
Notes
2006-10-21 10:51:40MED-GAS REVIEW
 DENIED;
 1.MED-GAS PERMIT REQUIRED. CONTRACTOR MUST BE LICENSED
 TO INSTALL MEDICAL GAS EQUIPMENT AND PIPING
 COPY OF INSTALLERS LICENSE MUST BE SUBMITED WITH
 PLANS AND APPLICATION.
 2.EQUIPMENT ELEVATION DRAWING ARE NOT OF SUFFICIENT
 CLARITY, 1/8" SCALE. (I CAN NOT READ NOTES).
 3.PLEASE SHOW EQUIPMENT ROOM DETAIL WITH LOCATION OF
 EQUIPMENT AND ALL PIPING REQUIRED. (A) COMPRESOR
 AIR SUPPLY NFPA 99C 2002 EDITION SECTION 5.3.3.5.7.1
 (B) VACUUM VENT AND WASTE DISPOSAL SECTION
 5.3.3.6.3.1.
 4.SUBMIT MANUFACTURE INSTALLATION INSTRUCTIONS.
 5.ADD NOTE VACUUM PIPE TO SLOPE A MIM. OF 1/4" PER TEN
 FEET TOWARDS VACUUM PUMB.
 6.ACCESSIBLE CLEANOUTS ARE REQUIRED TO COMPLY WITH
 SECTION 5.3.10.10.10.3.
 7.WATER LINES FROM FILTERED WATER TO DENTAL CHAIRS NOT
 SHOWN ON PLANS. SIZE AND LOCATION REQUIRED.
 MED-GAS PLANREVIEW BY;
 JOHN LEECH
 805-6695

Review Stop MEDGAS MEDICAL GAS
Rev No 4 Status N Date 2006-07-19 Cont ID  
Sent By jleech Date 2006-07-19 Time 07:43 Rev Time 0.00
Received By jleech Date 2006-07-19 Time 07:43 Sent To  
Notes
2006-07-19 00:00:00ALL MED-GAS WAS REMOVED FROM PLANS, TO
 BE SUBMITED AT A LATER TIME BY OTHERS.

Review Stop MEDGAS MEDICAL GAS
Rev No 3 Status F Date 2006-06-22 Cont ID  
Sent By jleech Date 2006-06-22 Time 12:19 Rev Time 0.00
Received By jleech Date 2006-06-22 Time 12:19 Sent To  
Notes
2006-06-22 00:00:00DENIED;
 PLEASE USE NFPA 99C 2002 ADITION CHAPTER
 5, LEVEL 3 PIPING FOR VACUUM AND
 COMPRESSORS.
 SEC.5.3.10.1. WILL LIST THE PIPING
 MATERIAL PERMITED TO BE USED.
 SEC.5.3.10.3. LISTS THE EXCEPTED
 FITTINGS AND HOW THEY ARE INSTALL ONTO
 THE PIPE.
 IF COPPER TUBING AND FITTING ARE BRAZED
 SEE SEC.5.3.10.7.
 YOU CAN ALSO CONTACT THE EQUIPMENT
 COMPANIES FOR SIZING AND MATERIAL
 REQUIREMENTS FOR THEIR EQUIPMENT.
 COLLECTOR TANK DRAIN TAIL PEACE CAN BE
 NO LONGER THAN 2' AND THE TRAP MUST B3E
 SERVICEABLE. SEE ATTACHED COPY OF
 FIG.A.5.3.3.6.3(B).
 MED GAS REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status F Date 2006-05-30 Cont ID  
Sent By jleech Date 2006-05-30 Time 12:23 Rev Time 0.00
Received By jleech Date 2006-05-30 Time 12:23 Sent To  
Notes
2006-05-30 00:00:00DENIED;
 1.(SECOND REQUEST) ADD TO NOTES;
 LICENSED MED-GAS CONTRACTOR REQUIRED TO
 INSTALL VACUUM AND COMPRESSED AIR LINES.
 SEPARATE PERMIT REQUIRED.
 2.AIR COMPRESSOR DETAIL; DELETE LAST 1/2
 OF MAKE UP AIR NOTE."TO NEAREST RETURN
 AIR DUCT".
 3.COMPRESSOR DETAIL; 1/2" SUPPLY AIR
 LINES ARE SHOWN, FLAT DRAWING SHOWS 1"
 LINES. PLEASE CLEARLY SHOW PIPE SIZE TO
 BE USED ON A RISER DIAGRAM.
 4. VACUUM PUMP DETAIL; DISCHARGE FROM
 COLLECTION TANK SHALL BE DIRECT PER.
 FBC-2004 PLUMBING SEC. 713.7.
 MED-GAS REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status F Date 2006-04-03 Cont ID  
Sent By jleech Date 2006-04-03 Time 07:33 Rev Time 0.00
Received By jleech Date 2006-04-03 Time 07:33 Sent To  
Notes
2006-04-03 00:00:00DENIED;
 1. ADD TO NOTES: LICENSED MED-GAS
 CONTRACTOR REQUIRED TO INSTALL VACUUM
 AND COMPRESSED AIR LINES SEPARATE PERMIT
 REQUIRED.
 2.VACUUM SYSTEM EXHAUST TO DISCHARGE
 SEPARATELY TO OPEN AIR. FBC-2004
 PLUMBING SEC713.6 AND NFPA 99C 2002
 EDITION SEC.5.3.3.6.4.1.
 3.SHOW TYPE OF PIPE USED FOR VACUUM AND
 COMPESSURE LINES.
 4.PLEASE SUBMIT MANUFACTOR EQUIPMENT
 SHEETS WITH PLANS. (VACUUM, COMPRESSOR,
 AND STERILIZER)
 5.MAKE UP AIR REQUIRED FOR COMPRESSOR,
 SHOW ON PLANS.
 6.THE PLANS MUST BE DRAWN BY A DESIGN
 PROFESSIONAL AND SIGNED AND SEALED PER
 481 FS.
 MED-GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 6 Status P Date 2006-11-18 Cont ID  
Sent By jleech Date 2006-11-18 Time 13:40 Rev Time 0.00
Received By jleech Date 2006-11-18 Time 13:40 Sent To  
Notes
2006-11-18 13:48:52PROVISO;
 A CHECK VALVE, UNION AND A SHUTOFF VALVE IS REQUIRED ON
 SUMP PUMP DISCHARGE LINE. SEE SECTION 712.2

Review Stop P PLUMBING
Rev No 5 Status F Date 2006-10-21 Cont ID  
Sent By jleech Date 2006-10-21 Time 09:45 Rev Time 0.00
Received By jleech Date 2006-10-21 Time 09:45 Sent To  
Notes
2006-10-21 10:14:30PLUMBING REVISIONS
 DENIED;
 1.PAGE P-1 REVISION 1 AND 2 WERE DELETED FROM NEW PLAN,
 (ADA REQUIREMENTS FOR BREAK SINK PLEASE PUT BACK ON
 PLAN.
 2.PAGE P-1 CHANGES MADE ON PLANS AND NOT CLOUDED; (A)
 AIR ADMITTANCE VALVE AT HAND SINK, THE ADV MUST COMPLY
 WITH
 FBC-2004 PLUMBING SECTION 917.3.1. (B)ADDITION OF
 MOP SINK AND LAVATORY IN CLOSET. (C) MOVED LOCATION OF
 LAVATORY
 IN ADA BATHROOM. (D) DELETED 2" VENT UP. (E) DELETED
 FSC BOX LOCATIONS.
 3.PAGE P-2 (OWNERS CHANGES 10-2-06) (A) TANKLESS WATER
 HEATER ADDED PLEASE DELETE WATER HEATER SCHEMATIC.
 ELECTRICAL REVISION REQUIRED
 (B) EXISTING FLOOR DRAIN DELETED.
 4.NEW SANITARY AND WATER RISER DIAGRAMS REQUIRED
 SHOWING CHANGES MADE IN THE PLUMBING SYSTEM.
 5. PAGE P-2 HOT WATER REQUIRED TO MOP SINK SECTION
 607.1.
 6. THE VENT AND DRAIN PIPES FOR VACUUM EQUIPMENT IS NOT
 SHOWN ON PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-07-19 Cont ID  
Sent By jleech Date 2006-07-19 Time 07:45 Rev Time 0.00
Received By jleech Date 2006-07-19 Time 07:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-06-22 Cont ID  
Sent By jleech Date 2006-06-22 Time 12:03 Rev Time 0.00
Received By jleech Date 2006-06-22 Time 12:03 Sent To  
Notes
2006-06-22 00:00:00DENIED;
 1.PAGE P-1, NOTE AT BREAK SINK ABOUT
 GARBAGE DISPOSAL. DISPOSAL CANNOT BE
 INSTALLED IN THE CLEAR FLOOR SPACEAND
 KNEE SPACE OF THE SINK. PAGE A-3 DETAIL
 SINK DOES NOT SHOW G/D.
 2.PRIVATE BATHROOM MUST BE H/C ADAPTABLE
 SEE SEC. 11-4.1.3(11). FLOOR SPACE DOES
 NOT ALLOW THE BATHROOM TO BE ADAPTABLE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-05-30 Cont ID  
Sent By jleech Date 2006-05-30 Time 12:45 Rev Time 0.00
Received By jleech Date 2006-05-30 Time 12:45 Sent To  
Notes
2006-05-30 00:00:00DENIED;
 1.BREAK SINK; SUPPORTS FOR TOE PLATE
 MUST BE REMOVABLE ALSO. SHOW DETAIL OF
 REMOVABLE FRONT TO AVOID PROBLEMS DURING
 CONSTUCTION.
 2.DEPTH OF BREAK SINK;
 PAGE AN-1PLUMBING SCHEDULE STILL SHOWS
 SINK AT 8" MUST BE A MAX. OF 6 1/2"
 DEEP.
 3.( SECOND REQUEST) DRINKING FOUNTAIN IS
 REQUIRED TABLE 403.1. FIRST DRINKING
 FOUNTAIN IS REQUIRED TO BE INSTALLED TO
 THE PLUMBING SYSTEM. SEE FBC-2004
 PLUMBING SEC 410.1.
 4.(SECOND REQUEST) WATER HAMMER ARRESTOR
 TO BE INSTALLED WHERE QUICK CLOSING
 VALVES ARE INSTALLED. SEC.604.9.
 5.(SECOND REQUEST)RISER DIAGRAMS
 REQUIRED, SANITARY, WATER AND MED-GAS.
 AMENDMENTS TO THE BUILDING CODE CHAPTER
 1, SEC. 106.3.5.1.3(13).
 6.WATER HEATER DIAGRAM; SHOW MEANS OF
 THERMAL EXPANTION PROTECTION PER SEC
 607.3.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-04-03 Cont ID  
Sent By jleech Date 2006-04-03 Time 07:03 Rev Time 0.00
Received By jleech Date 2006-04-03 Time 07:03 Sent To  
Notes
2006-04-03 00:00:00DENIED;
 1.BREAK SINK; SHOW FRONTAL, CLEAR FLOOR
 SPACE ON FLOOR PLAN. SEC11-47.24.3.
 IN-SINKERATOR CANNOT BE INSTALLED ON
 SINK BECAUSE OF KNEE CLEARANCE. SEC.
 11-24..3.
 THE DEPTH OF SINK IS A MAX. OF 6 1/2".
 SEC.11-24.4. PLEASE CHANGE PLUMBING
 SCHEDULE ON PAGE AN1.
 ADD NOTE THAT EXPOSED PIPES TO BE
 INSULATED.
 2.A DRINKING FOUINTAIN IS REQUIRED.
 FBC-2004 PLUMBING TABLE 403.1, ALSO SEE
 SEC. 410.1.
 3.SIZE AND LOCATION OF WATER HEATER, NOT
 SHOWN ON DRAWINGS. ALSO LIST ON PLUMBING
 SCHEDULE.
 4.WATER HAMMER ARRESTORS TO BE INSTALLED
 WHERE EVER QUICK-CLOSING VALVES ARE
 INSTALLED. SEC. 604.9 SEE PAGE P-2 WATER
 SOLENOID SCHEMATIC.
 5.RISER DIAGRAMS REQUIRED WATER AND
 SANITARY. AMENDMENTS TO THE FLORIDA
 BUILDING CODE CHAPTER 1, 2004 EDITTION
 SEC. 106.3.5.1.3(13).
 6.STERILIZERS TO BE INDIRECT WASTED MUST
 COMPLY WITH SEC.713.3 AND VENT SIZE TO
 COMPLY WITH TABLE 713.11.1
 7.THE PLANS MUST BE DRAWN BY A DESIGN
 PROFESSIONAL, PER 481 FS AND SIGNED AND
 SEALED PER. 481 FS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved