| Plan Review Stops For Permit 06030341 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2006-07-20 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-07-20 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-07-19 |
Time |
16:24 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2006-06-24 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-06-24 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-06-24 |
Time |
08:45 |
Sent To |
|
|
| Notes |
| 2006-06-24 00:00:00 | PLANS ON MJ DESK. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-05-15 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-05-15 |
Time |
18:19 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-05-15 |
Time |
13:34 |
Sent To |
PC |
|
| Notes |
| 2006-05-15 00:00:00 | 1) SUBMIT AN EXISTING FLOOR PLAN OF THE | | | BUILDING TO SHOW ALL NEW CHANGES OF THE | | | PROPOSED LAY-OUT. | | | | | | 2) 110.2* W. P. B. ADMINISTRATIVE CODE, | | | INFORMATION THAT IS REQUIRED FOR RECORD | | | KEEPING & FOR CERTIFICATE OF OCCUPANCY: | | | A) THE EDITION OFTHE CODE UNDER WHICH | | | THE PERMIT WAS ISSUED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | | WITH THE PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | | IN CHAPTER 6, TABLE 601. | | | D) THE DESIGN OCCUPANT LOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | | IS REQUIRED. | | | F) ANY SPECIAL STIPULATIONS & CONDITIONS | | | OF THE BUILDING PERMIT. | | | | | | 3) SHEET D-1 #1. A PORTION OF THE MAIN | | | COUNTER WHICH IS A MINIMUM OF 36" IN | | | LINGTH SHALL BE PROVIDED WITH A MAXIMUM | | | HEIGHT OF 36". OR AN AUXILIARY COUNTER | | | WITH A MAXIMUM HEIGHT OF 36" IN CLOSE | | | PROXIMITY TO THE MAIN COUNTER SHALL BE | | | PROVIDED: 11-7 (I)(II). THE DIMENTIONS | | | GIVEN WILL HAVE A COUNTER HEIGHT OF | | | 37"AFF. | | | | | | 4) SHEET D-2 MENTION SEE DETAIL 5/D2, | | | HOWEVEER,THERE IS NO #5 DETAIL ON SHEET | | | D-2. A DETAIL DRAWING FOR EACH WALL IS | | | REQUIRED INDICATING TOP AND BOTTOM | | | ATTATCHMENT AND ALL MATERIALS. ALSO | | | INDICATE THE STUD SPACING OF EACH WALL. | | | CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY TO INDICATE THE | | | NATURE AND EXTENT OF THE WORK PROPOSED | | | AND SHOW IN DETAIL THAT THE WORK WILL | | | MEET 2004 FBC. AND RELEVENT LAWS. | | | FBC.SEC.106.1.1 | | | | | | 5) A SEPERATE PERMIT IS REQUIRED FOR THE | | | NEW DOORS AND WINDOWS. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | TEL:(561)805-6726 | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-04-05 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-04-05 |
Time |
18:02 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-04-05 |
Time |
14:40 |
Sent To |
PC |
|
| Notes |
| 2006-04-05 00:00:00 | 1) IF THE DESIGN PROFESSIONAL IS AN | | | ARCHITECT OR ENGINEER LEGALLY REGISTERED | | | UNDER THE LAWS OF THIS STATE REGULATING | | | THE PRACTICE OF ARCHITECTURE AS PROVIDED | | | FOR IN CHAPTER 481, FLORIDA STATUTES, | | | PART I, OR ENGINEERING AS PROVIDED FOR | | | IN CHAPTER 471, FLORIDA STATUTES, THEN | | | HE OR SHE SHALL AFFIX HIS OR HER | | | OFFICIAL SEAL, SIGNATURE AND DATE TO | | | SAID DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA, AS REQUIRED BY | | | FLORIDA STATUTE. IF THE DESIGN | | | PROFESSIONAL IS A LANDSCAPE ARCHITECT | | | REGISTERED UNDER THE LAWS OF THIS STATE | | | REGULATING THE PRACTICE OF LANDSCAPE | | | ARCHITECTURE AS PROVIDED FOR IN CHAPTER | | | 481, FLORIDA STATUTES, PART II, THEN HE | | | OR SHE SHALL AFFIX HIS OR HER SEAL, | | | SIGNATURE AND DATE TO SAID DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA AS | | | DEFINED IN SECTION | | | 481.303(6)(A)(B)(C)(D), FS. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT BEFORE A | | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLY COMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | | | 3) SHOW THE FRONT ELEVATION OF THE FRONT | | | DESK TO MEET THE REQUIRMENTS OF FBC SEC. | | | 11-7. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | TEL:(561)805-6726 | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-11-21 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-11-21 |
Time |
11:12 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-11-21 |
Time |
11:01 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2006-05-16 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-05-16 |
Time |
16:36 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2006-05-16 |
Time |
15:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-03-30 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-03-30 |
Time |
12:10 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2006-03-30 |
Time |
09:59 |
Sent To |
|
|
| Notes |
| 2006-03-30 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | THE PLANS MUST BE DRAWN BY A DESIGN | | | PROFESSIONAL PER 481 FS AND SIGNED AND | | | SEALED PER 481 FS. | | | | | | 1} PROVIDE A PANEL SCHEDULE OR SCHEDULES | | | INDICATING ALL CIRCUITS IN THE AREA OF | | | WORK AND RATINGS OF PANELS. | | | | | | 2} SUBMIT A LOAD CALCULATION PER 106 FBC | | | AND 215.5 NEC. | | | | | | 3} INDICATE CIRCUIT NUMBERS AT ALL | | | LIGHTS AND DEVICES THAT BRANCH CIRCUIT | | | AND ARTICLE 700. | | | | | | 4} INDICATE LOCATIONS OF ALL EXIT AND | | | EMERGENCY LIGHTING. | | | | | | 5} LABEL REQUIRED GFI RECEPTACLES PER | | | 210.8 NEC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2006-05-17 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-05-17 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-05-17 |
Time |
10:30 |
Sent To |
|
|
| Notes |
| 2006-05-17 00:00:00 | ***APPROVED*** | | | | | | SEPARATE SHOP DRAWINGS AND PERMITS | | | REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM SYSTEMS REMODEL IF APPLICABLE. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-04-03 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2006-04-03 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2006-04-03 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2006-04-03 00:00:00 | **********DENIED:************** | | | | | | 1) CONSTRUCTION, RENOVATION, AND | | | DEMOLITION SHALL COMPLY WITH NFPA 241. | | | | | | 2) LIFE SAFETY SHALL BE IN COMPLIANCE | | | WITH NFPA 101 LIFE SAFETY CODE, 2003 | | | EDITION. | | | | | | 3) PLEASE INDICATE THE MINIMUM INTERIOR | | | FINISH CLASSIFICATION FOR WALLS AND | | | CEILINGS. | | | | | | 4) PLEASE SHOW ALL EXIT SIGNS AND | | | EMERGENCY LIGHTING ON THE PLAN. | | | | | | 5) SEPARATE SHOP DRAWINGS ARE REQUIRED | | | FOR FIRE SPRINKLER AND OR FIRE ALARM | | | SYSTEMS REMODEL. | | | | | | | | | NATE MCCRAY, ASSISTANT FIRE MARSHAL | | | 561-804-4754 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-11-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-08 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-08 |
Time |
15:56 |
Sent To |
I |
|
| Notes |
| 2006-11-17 11:26:00 | TO "BOB"#1 | | 2006-11-08 15:59:37 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-10-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-10 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-10 |
Time |
10:40 |
Sent To |
P |
|
| Notes |
| 2006-10-10 10:40:51 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-07-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-13 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-13 |
Time |
13:44 |
Sent To |
B |
|
| Notes |
| 2006-07-18 00:00:00 | TO "BOB"#15 | | 2006-07-13 00:00:00 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-06-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-12 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-12 |
Time |
13:15 |
Sent To |
|
|
| Notes |
| 2006-06-14 00:00:00 | TO "BOB"#1 | | 2006-06-12 00:00:00 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-05-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-08 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-08 |
Time |
09:26 |
Sent To |
|
|
| Notes |
| 2006-05-10 00:00:00 | TO "BOB"#9 | | 2006-05-08 00:00:00 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2006-04-05 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-03-09 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2006-03-30 00:00:00 | TO "BOB"#1 | | 2006-03-09 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2007-02-13 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2007-02-13 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2007-02-13 |
Time |
14:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2006-06-20 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-06-20 |
Time |
16:38 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2006-06-20 |
Time |
16:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2006-05-30 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-05-30 |
Time |
15:49 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-05-30 |
Time |
15:49 |
Sent To |
|
|
| Notes |
| 2006-05-30 00:00:00 | *** DENIED *** | | | 1) RETURN AIR TRANSFER DUCT TO | | | CONSULTATION ROOM IS TO SMALL, SEE NOTE | | | #3. | | | | | | 2) PLEASE SHOW ON MECHANICAL PLANS HOW | | | OUTSIDE AIR WILL BE GETTING TO AHU. | | | | | | 3)BALANCED RETURN AIR. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | | INCREASING THE RETURN TRANSFER ONE AND | | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING | | | AND THE DOOR HAVING AT LEAST AN | | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | | PROPER RETURN AIR BALANCE. PER 2004 | | | FBC/M 601.4 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2006-03-30 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-03-30 |
Time |
14:04 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2006-03-30 |
Time |
14:04 |
Sent To |
|
|
| Notes |
| 2006-03-30 00:00:00 | NO MECHANICAL PLANS SUBMITTED, AND NO | | | MECHANICAL PERMIT NUMBER APPLIED FOR AT | | | THIS TIME. |
|
|
| Review Stop |
MEDGAS |
MEDICAL GAS |
| Rev No |
6 |
Status |
P |
Date |
2006-11-18 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-11-18 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-11-18 |
Time |
14:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
MEDGAS |
MEDICAL GAS |
| Rev No |
5 |
Status |
F |
Date |
2006-10-21 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-10-21 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-10-21 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2006-10-21 10:51:40 | MED-GAS REVIEW | | | DENIED; | | | 1.MED-GAS PERMIT REQUIRED. CONTRACTOR MUST BE LICENSED | | | TO INSTALL MEDICAL GAS EQUIPMENT AND PIPING | | | COPY OF INSTALLERS LICENSE MUST BE SUBMITED WITH | | | PLANS AND APPLICATION. | | | 2.EQUIPMENT ELEVATION DRAWING ARE NOT OF SUFFICIENT | | | CLARITY, 1/8" SCALE. (I CAN NOT READ NOTES). | | | 3.PLEASE SHOW EQUIPMENT ROOM DETAIL WITH LOCATION OF | | | EQUIPMENT AND ALL PIPING REQUIRED. (A) COMPRESOR | | | AIR SUPPLY NFPA 99C 2002 EDITION SECTION 5.3.3.5.7.1 | | | (B) VACUUM VENT AND WASTE DISPOSAL SECTION | | | 5.3.3.6.3.1. | | | 4.SUBMIT MANUFACTURE INSTALLATION INSTRUCTIONS. | | | 5.ADD NOTE VACUUM PIPE TO SLOPE A MIM. OF 1/4" PER TEN | | | FEET TOWARDS VACUUM PUMB. | | | 6.ACCESSIBLE CLEANOUTS ARE REQUIRED TO COMPLY WITH | | | SECTION 5.3.10.10.10.3. | | | 7.WATER LINES FROM FILTERED WATER TO DENTAL CHAIRS NOT | | | SHOWN ON PLANS. SIZE AND LOCATION REQUIRED. | | | MED-GAS PLANREVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
MEDGAS |
MEDICAL GAS |
| Rev No |
4 |
Status |
N |
Date |
2006-07-19 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-07-19 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-07-19 |
Time |
07:43 |
Sent To |
|
|
| Notes |
| 2006-07-19 00:00:00 | ALL MED-GAS WAS REMOVED FROM PLANS, TO | | | BE SUBMITED AT A LATER TIME BY OTHERS. |
|
|
| Review Stop |
MEDGAS |
MEDICAL GAS |
| Rev No |
3 |
Status |
F |
Date |
2006-06-22 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-06-22 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-06-22 |
Time |
12:19 |
Sent To |
|
|
| Notes |
| 2006-06-22 00:00:00 | DENIED; | | | PLEASE USE NFPA 99C 2002 ADITION CHAPTER | | | 5, LEVEL 3 PIPING FOR VACUUM AND | | | COMPRESSORS. | | | SEC.5.3.10.1. WILL LIST THE PIPING | | | MATERIAL PERMITED TO BE USED. | | | SEC.5.3.10.3. LISTS THE EXCEPTED | | | FITTINGS AND HOW THEY ARE INSTALL ONTO | | | THE PIPE. | | | IF COPPER TUBING AND FITTING ARE BRAZED | | | SEE SEC.5.3.10.7. | | | YOU CAN ALSO CONTACT THE EQUIPMENT | | | COMPANIES FOR SIZING AND MATERIAL | | | REQUIREMENTS FOR THEIR EQUIPMENT. | | | COLLECTOR TANK DRAIN TAIL PEACE CAN BE | | | NO LONGER THAN 2' AND THE TRAP MUST B3E | | | SERVICEABLE. SEE ATTACHED COPY OF | | | FIG.A.5.3.3.6.3(B). | | | MED GAS REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
MEDGAS |
MEDICAL GAS |
| Rev No |
2 |
Status |
F |
Date |
2006-05-30 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-05-30 |
Time |
12:23 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-05-30 |
Time |
12:23 |
Sent To |
|
|
| Notes |
| 2006-05-30 00:00:00 | DENIED; | | | 1.(SECOND REQUEST) ADD TO NOTES; | | | LICENSED MED-GAS CONTRACTOR REQUIRED TO | | | INSTALL VACUUM AND COMPRESSED AIR LINES. | | | SEPARATE PERMIT REQUIRED. | | | 2.AIR COMPRESSOR DETAIL; DELETE LAST 1/2 | | | OF MAKE UP AIR NOTE."TO NEAREST RETURN | | | AIR DUCT". | | | 3.COMPRESSOR DETAIL; 1/2" SUPPLY AIR | | | LINES ARE SHOWN, FLAT DRAWING SHOWS 1" | | | LINES. PLEASE CLEARLY SHOW PIPE SIZE TO | | | BE USED ON A RISER DIAGRAM. | | | 4. VACUUM PUMP DETAIL; DISCHARGE FROM | | | COLLECTION TANK SHALL BE DIRECT PER. | | | FBC-2004 PLUMBING SEC. 713.7. | | | MED-GAS REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
MEDGAS |
MEDICAL GAS |
| Rev No |
1 |
Status |
F |
Date |
2006-04-03 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-04-03 |
Time |
07:33 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-04-03 |
Time |
07:33 |
Sent To |
|
|
| Notes |
| 2006-04-03 00:00:00 | DENIED; | | | 1. ADD TO NOTES: LICENSED MED-GAS | | | CONTRACTOR REQUIRED TO INSTALL VACUUM | | | AND COMPRESSED AIR LINES SEPARATE PERMIT | | | REQUIRED. | | | 2.VACUUM SYSTEM EXHAUST TO DISCHARGE | | | SEPARATELY TO OPEN AIR. FBC-2004 | | | PLUMBING SEC713.6 AND NFPA 99C 2002 | | | EDITION SEC.5.3.3.6.4.1. | | | 3.SHOW TYPE OF PIPE USED FOR VACUUM AND | | | COMPESSURE LINES. | | | 4.PLEASE SUBMIT MANUFACTOR EQUIPMENT | | | SHEETS WITH PLANS. (VACUUM, COMPRESSOR, | | | AND STERILIZER) | | | 5.MAKE UP AIR REQUIRED FOR COMPRESSOR, | | | SHOW ON PLANS. | | | 6.THE PLANS MUST BE DRAWN BY A DESIGN | | | PROFESSIONAL AND SIGNED AND SEALED PER | | | 481 FS. | | | MED-GAS PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2006-11-18 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-11-18 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-11-18 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2006-11-18 13:48:52 | PROVISO; | | | A CHECK VALVE, UNION AND A SHUTOFF VALVE IS REQUIRED ON | | | SUMP PUMP DISCHARGE LINE. SEE SECTION 712.2 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2006-10-21 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-10-21 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-10-21 |
Time |
09:45 |
Sent To |
|
|
| Notes |
| 2006-10-21 10:14:30 | PLUMBING REVISIONS | | | DENIED; | | | 1.PAGE P-1 REVISION 1 AND 2 WERE DELETED FROM NEW PLAN, | | | (ADA REQUIREMENTS FOR BREAK SINK PLEASE PUT BACK ON | | | PLAN. | | | 2.PAGE P-1 CHANGES MADE ON PLANS AND NOT CLOUDED; (A) | | | AIR ADMITTANCE VALVE AT HAND SINK, THE ADV MUST COMPLY | | | WITH | | | FBC-2004 PLUMBING SECTION 917.3.1. (B)ADDITION OF | | | MOP SINK AND LAVATORY IN CLOSET. (C) MOVED LOCATION OF | | | LAVATORY | | | IN ADA BATHROOM. (D) DELETED 2" VENT UP. (E) DELETED | | | FSC BOX LOCATIONS. | | | 3.PAGE P-2 (OWNERS CHANGES 10-2-06) (A) TANKLESS WATER | | | HEATER ADDED PLEASE DELETE WATER HEATER SCHEMATIC. | | | ELECTRICAL REVISION REQUIRED | | | (B) EXISTING FLOOR DRAIN DELETED. | | | 4.NEW SANITARY AND WATER RISER DIAGRAMS REQUIRED | | | SHOWING CHANGES MADE IN THE PLUMBING SYSTEM. | | | 5. PAGE P-2 HOT WATER REQUIRED TO MOP SINK SECTION | | | 607.1. | | | 6. THE VENT AND DRAIN PIPES FOR VACUUM EQUIPMENT IS NOT | | | SHOWN ON PLANS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2006-07-19 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-07-19 |
Time |
07:45 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-07-19 |
Time |
07:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2006-06-22 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-06-22 |
Time |
12:03 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-06-22 |
Time |
12:03 |
Sent To |
|
|
| Notes |
| 2006-06-22 00:00:00 | DENIED; | | | 1.PAGE P-1, NOTE AT BREAK SINK ABOUT | | | GARBAGE DISPOSAL. DISPOSAL CANNOT BE | | | INSTALLED IN THE CLEAR FLOOR SPACEAND | | | KNEE SPACE OF THE SINK. PAGE A-3 DETAIL | | | SINK DOES NOT SHOW G/D. | | | 2.PRIVATE BATHROOM MUST BE H/C ADAPTABLE | | | SEE SEC. 11-4.1.3(11). FLOOR SPACE DOES | | | NOT ALLOW THE BATHROOM TO BE ADAPTABLE. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2006-05-30 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-05-30 |
Time |
12:45 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-05-30 |
Time |
12:45 |
Sent To |
|
|
| Notes |
| 2006-05-30 00:00:00 | DENIED; | | | 1.BREAK SINK; SUPPORTS FOR TOE PLATE | | | MUST BE REMOVABLE ALSO. SHOW DETAIL OF | | | REMOVABLE FRONT TO AVOID PROBLEMS DURING | | | CONSTUCTION. | | | 2.DEPTH OF BREAK SINK; | | | PAGE AN-1PLUMBING SCHEDULE STILL SHOWS | | | SINK AT 8" MUST BE A MAX. OF 6 1/2" | | | DEEP. | | | 3.( SECOND REQUEST) DRINKING FOUNTAIN IS | | | REQUIRED TABLE 403.1. FIRST DRINKING | | | FOUNTAIN IS REQUIRED TO BE INSTALLED TO | | | THE PLUMBING SYSTEM. SEE FBC-2004 | | | PLUMBING SEC 410.1. | | | 4.(SECOND REQUEST) WATER HAMMER ARRESTOR | | | TO BE INSTALLED WHERE QUICK CLOSING | | | VALVES ARE INSTALLED. SEC.604.9. | | | 5.(SECOND REQUEST)RISER DIAGRAMS | | | REQUIRED, SANITARY, WATER AND MED-GAS. | | | AMENDMENTS TO THE BUILDING CODE CHAPTER | | | 1, SEC. 106.3.5.1.3(13). | | | 6.WATER HEATER DIAGRAM; SHOW MEANS OF | | | THERMAL EXPANTION PROTECTION PER SEC | | | 607.3. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-04-03 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-04-03 |
Time |
07:03 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-04-03 |
Time |
07:03 |
Sent To |
|
|
| Notes |
| 2006-04-03 00:00:00 | DENIED; | | | 1.BREAK SINK; SHOW FRONTAL, CLEAR FLOOR | | | SPACE ON FLOOR PLAN. SEC11-47.24.3. | | | IN-SINKERATOR CANNOT BE INSTALLED ON | | | SINK BECAUSE OF KNEE CLEARANCE. SEC. | | | 11-24..3. | | | THE DEPTH OF SINK IS A MAX. OF 6 1/2". | | | SEC.11-24.4. PLEASE CHANGE PLUMBING | | | SCHEDULE ON PAGE AN1. | | | ADD NOTE THAT EXPOSED PIPES TO BE | | | INSULATED. | | | 2.A DRINKING FOUINTAIN IS REQUIRED. | | | FBC-2004 PLUMBING TABLE 403.1, ALSO SEE | | | SEC. 410.1. | | | 3.SIZE AND LOCATION OF WATER HEATER, NOT | | | SHOWN ON DRAWINGS. ALSO LIST ON PLUMBING | | | SCHEDULE. | | | 4.WATER HAMMER ARRESTORS TO BE INSTALLED | | | WHERE EVER QUICK-CLOSING VALVES ARE | | | INSTALLED. SEC. 604.9 SEE PAGE P-2 WATER | | | SOLENOID SCHEMATIC. | | | 5.RISER DIAGRAMS REQUIRED WATER AND | | | SANITARY. AMENDMENTS TO THE FLORIDA | | | BUILDING CODE CHAPTER 1, 2004 EDITTION | | | SEC. 106.3.5.1.3(13). | | | 6.STERILIZERS TO BE INDIRECT WASTED MUST | | | COMPLY WITH SEC.713.3 AND VENT SIZE TO | | | COMPLY WITH TABLE 713.11.1 | | | 7.THE PLANS MUST BE DRAWN BY A DESIGN | | | PROFESSIONAL, PER 481 FS AND SIGNED AND | | | SEALED PER. 481 FS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|