Plan Review Details - Permit 06030256
Plan Review Stops For Permit 06030256
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-24 Cont ID  
Sent By mjacobs Date 2006-04-24 Time 15:38 Rev Time 0.00
Received By mjacobs Date 2006-04-21 Time 14:26 Sent To PC
Notes
2006-04-21 00:00:00 
 1) 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORIC SURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED
 SITES.ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) 104.6.5 BUILDING PERMIT VALUATION. IF
 IN THE OPINION OF THE BUILDING OFFICIAL
 THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED, UNLESS THE
 APPLICANT CAN SHOW DETAILED ESTIMATES
 AND/OR BONA FIDED SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR
 PERMITTING PURPOSES, VALUATION FOR
 BUILDINGS AND SYSTEMS SHALL BE FOUND IN
 MARSHALL AND
 SWIFT OR THE SOUTHERN BUILDING CODE
 CONGRESS INTERNATIONAL VALUATION TABLES,
 LATEST EDITION, AND SHALL BE BASED ON
 TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN
 FEES, OVERHEAD AND PROFIT, EXCLUDING
 ONLY LAND VALUE.
  
 4) BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE ACTUAL PERMIT PLANS
 MUST BE STAMPED BY THAT OFFICE, AND A
 COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 5) 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1. GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30
 FEET (9.1 M) ABOVE GRADE SHALL MEET THE
 PROVISIONS OF THE SMALL MISSILE TEST.
  
 6) THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3 PRODUCT
 APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. PRODUCT APPROVAL
 REQUIRED FOR EXTERIOR DOORS/WINDOWS/
 ROOFING PRODUCTS/SHUTTERS/
 ETC.TWO COPIES OF EACH PRODUCT IS
 REQUIRED FOR PLAN REVIEW.
  
 7) TRUSS DESIGN
 R802.10.1 TRUSS DESIGN DRAWINGS.
 TRUSS DESIGN DRAWINGS, PREPARED IN
 CONFORMANCE WITH SECTION R802.10.1 ,
 SHALL BE PROVIDED TO THE BUILDING
 OFFICIAL AND APPROVED PRIOR TO
 INSTALLATION. TRUSS DESIGN DRAWINGS
 SHALL INCLUDE, AT A MINIMUM, THE
 INFORMATION SPECIFIED BELOW. TRUSS
 DESIGN DRAWING SHALL BE PROVIDED WITH
 THE SHIPMENT OF TRUSSES DELIVERED TO THE
 JOBSITE.
  
 8)ENERGY CALCULATIONS NEED TO BE ON FORM
 600A-04 (2004) PER FBC 13-600.3.A.
 THESE FORMS SHALL BE SINGED AND DATED BY
 THE OWNER/AGENT.
  
 9) STATE THE CORRECT MEAN ROOF HEIGHT ON
 THE DRAWINGS (SHEET A-2). ONLY THE
 PERSON WHO SIGN AND SEAL THE DRAWINGS
 ARE ALLOWED TO MAKE CHANGES TO THEM. SEE
 SHEET A-2 WHERE THE WORD SCREENED WAS
 SCRATCHED OUT. THE ARCHITECT WILL HAVE
 TO SIGN AND DATE EACH HAND WRITTEN
 CHANGE MADE OR SUBMIT A COMPLETE SET OF
 NEW DRAWINGS WITH CHANGES.
  
 10) ON SHEET S-1 THE TRUSS DESIGN
 CRITERIA MENTION THE 2001 FL BLDG CODE.
 NOTE: WE ARE UNDER THE 2004 BLDG CODE.
 PLEASE CORRECT THIS INFORMATION. WHERE
 IS DETAIL #3 ON SHEET S-4?
  
 11) SHEET S-4 THE DETAIL FOR THE FLOOR
 JOIST INDICATE A SIMPSON LUS26 WHICH HAS
 A WIDTH OF (1 9/16") IF THE FLOOR JOISTS
 ARE (2) 2X12. HOW WILL THE LUS26 WORK?
 PLEASE CLARIFY, AND SHOW THE CORRECT
 STRAP.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
 FAX:(561)805-6731
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-04-19 Cont ID  
Sent By btrobaug Date 2006-04-19 Time 15:44 Rev Time 0.50
Received By btrobaug Date 2006-04-19 Time 14:31 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-04-24 Time   Rev Time 0.00
Received By adarroug Date 2006-04-19 Time 14:17 Sent To  
Notes
2006-04-19 00:00:00TO "LMARTINEZ' DESK-EXPIDITED

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-04-20 Cont ID  
Sent By lmartine Date 2006-04-20 Time 10:38 Rev Time 0.00
Received By lmartine Date 2006-04-20 Time 10:38 Sent To  
Notes
2006-04-20 00:00:00NO PLANS SUBMITTED

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-04-20 Cont ID  
Sent By jleech Date 2006-04-20 Time 10:21 Rev Time 0.00
Received By jleech Date 2006-04-20 Time 10:21 Sent To M
Notes
2006-04-20 00:00:00DENIED;
 SANITARY RISER DIAGRAM NOT TO CODE.
 1.BATHROOM #3 NO HORIZONTAL DRY VENTS
 PERMITED. RED LINED ONE SET OF PLANS TO
 HELP WITH LAYOUT.
 2.TRAPS NOT REQUIRED ON TOILETS TRAP
 BUILT INTO FIXTURE.
 3.AUTOMATIC CLOTHES WASHER CANNOT
 DISCHARGE INTO A BATHROOM GROUP. MUST
 DISCHARGE DOWN STREAM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2006-04-20 Cont ID  
Sent By mmclean Date 2006-04-20 Time 16:52 Rev Time 0.00
Received By mmclean Date 2006-04-20 Time 16:52 Sent To B
Notes
2006-04-20 00:00:00NOTE: DEMO PERMIT FOR BOTH STRUCTURE IN
 REAR 05090574.
  
 NOTE: MUST PULL A SEPARATE PERMIT FOR
 FENCE/WALL/GATE WITH EASEMENT APPROVAL
 FROM THE CITY OF WEST PALM UTILITY DEPT.
  
 NOTEL MUST PULL A SEPARATE PERMIT FOR
 POOL/SPA/DECK.